8.4 Advanced programming  
When the thermostat is off, press and hold the keys  
+
for 5 sec to  
enter the advanced programming menu. Here you can view or change  
the values of the current status parameters according to the table below.  
Code  
Function  
Setting and options  
Default  
Temperature  
compensation  
1
From -9 to +9°C  
-3  
00: When the room  
temperature reaches the set-  
point, the fan switches off 01:  
When the room temperature  
reaches the set-point, the fan  
continues at minimum speed  
2
Fan control  
00  
00: All keys are locked except  
on/off  
3
Key lock  
01  
01  
01: All keys are locked  
00: Cooling / Ventilation  
01: Cooling / Heating /  
Ventilation  
Customising  
operating mode  
4
Min. set-point  
temperature  
5
6
5-15°C  
5
Max temp. set-  
15-45°C  
35  
point  
00: Mostra sia temp. set-point  
che temp. ambiente  
01: Mostra solo temp. set-  
point  
7
Display mode  
00  
00: In the absence of a room  
card, energy-saving is active  
01: In the absence of a room  
card, the thermostat is off  
Room card  
function  
8
9
00  
20  
Heating  
energy-saving  
temp.  
10-30°C  
DECLARATION OF CONFORMITY  
Cooling energy-  
saving temp.  
A
B
C
D
10-30°C  
0-8  
26  
1
The company Cordivari S.r.l., with registered oce in Zona Industriale  
Pagliare, Morro d’Oro (TE), Italy, declares under its own responsibility  
that the thermostats referred to in para. 2 comply with the following  
standards:  
Daytime display  
brightness  
Night display  
brightness  
0-8  
1
Inactive area  
1-5°C  
1
temp.  
EN 60950-1:2006+A11:2009+A1:2010+A12:2011+A2:2013  
EN 62321-1:2013  
00: No ring light  
01: The ring light is active after  
one rotation  
02: Ring light always on  
03: Ring light continues to  
rotate  
Ring light visual  
eect in standby  
EN IEC 61000-3-2:2019+A1:2021  
EN 61000-3-3:2013+A1:2019+A2:2021  
EN 55032 :2015  
E
01  
EN 55035 :2017  
F
Version number  
U7  
All settings will be automatically conrmed at the next switching on.  
and therefore meet the essential requirements of the following European  
Regulations and Directives:  
Directive 2014/53/EU  
Directive 2014/35/EU  
Directive 2014/30/EU  
Directive 2012/19/EU  
Directive 2011/65/EU amended by 2015/863/EU and 2017/2102/EU  
Morro D’Oro, 01/07/2024  
Cav. Ercole Cordivari  
Amministratore unico  
Cod. 1910000000402 - nv00  
- 13 -  
GeneralDetails
NameCORDIVARI Stand Alone Control Thermostat for VENTANA Fan Coils User Manual
MakeCORDIVARI
LanguageEnglish
FiletypePDF (Download)
File size0.84 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
CORDIVARI Ardesia Electric Radiators with Digital Thermostat Instruction Manual
CORDIVARI Ardesia Electric Radiators with Digital Thermostat Instruction Manual