Home > Bosch > BOSCH BCC110 Connected Control Thermostat Instruction Manual

BOSCH BCC110 Connected Control Thermostat Instruction Manual

Advanced Settings Guide  
3
Staging Logic  
4
WSHP Fault Codes  
Staging response determines how the thermostat stages heating or cooling calls  
based on the difference between space temperature and the set point (1.0°F or  
1.5°F).  
If your Bosch Connected Control (BCC) thermostat is connected to one of Bosch’s  
Water Source Heat Pump (WSHP) products, the following WSHP fault codes can  
be displayed on the BCC. Please refer to the WSHP product’s installation and  
operation manual for more details on troubleshooting.  
3.1 Staging Timers  
4.1 High Pressure Alarm  
There are 4 timers defined in the stage algorithm, MRT (Minimum Run Timer), ASC  
(Anti-Short Cycle Timer), Stage Delay and a fixed 3 minutes timer for quick staging  
down.  
The equipment has detected a high head pressure condition and prohibited heating  
and cooling calls. Contact your local contractor for service. Press the enter key to  
return to normal thermostat display.  
•
When any stage is on, it has to run for the MRT, except in the scenario of  
quick staging down where the heating/cooling is turned off.  
4.2 Low Pressure Alarm  
•
•
When any stage is up or down, it has to wait for Stage Delay to expire.  
The equipment has detected a low head pressure condition and prohibited heating  
and cooling calls. Contact your local contractor for service. Press the enter key to  
return to normal thermostat display.  
When all stages are turned off, the system has to wait for ASC to expire  
before it can be turned on again. Please note, the ASC timers run  
concurrently with Fan off Delay timer defined elsewhere.  
4.3 Condenser Coil Freeze Alarm  
Interval  
Minimum  
3 Minutes  
Maximum  
90 Minutes  
Stage Delay  
5 Minutes  
3 Minutes  
Default  
10 Minutes  
5 Minutes  
5 Minutes  
3 Minutes  
Resolution  
1 Minute  
1 Minute  
1 Minute  
Fixed  
The equipment has detected a freeze condition and prohibited heating and  
cooling calls. The sensor that has triggered this fault is monitoring the refrigerant  
temperature between the TXV and the air coil. The UPM board is aware of the mode  
of operation, and this sensor will be monitored in the cooling mode. Contact your  
local contractor for service. Press enter key to return to normal thermostat display.  
Stage Delay  
MRT(Minimum Run Time) 3 Minutes  
ASC (Anti-Short Cycle)  
Quick Stage Down  
0 Minutes  
3 Minutes  
Table 1 Stage Timers  
4.4 Condensate Alarm  
The equipment has detected a condensate line blockage condition and prohibited  
cooling calls. Contact your local contractor for service. Press the enter key to  
return to normal thermostat display.  
3.2 Staging Temp  
Stage temperature is use to determine whether there is a need for quick staging up  
or staging down based on a temperature setpoint differential.  
4.5 Brown Out Alarm  
Interval  
Minimum  
0°F  
Maximum  
15°F  
Default  
4°F  
Resolution  
1°F  
The equipment has detected a power brownout condition and prohibited heating  
and cooling calls. Contact your local contractor for service. Press the enter key to  
return to normal thermostat display.  
Stage Temp  
Table 2 Stage Temp  
4.6 Evaporator Coil Freeze Alarm  
The equipment has detected a freeze condition and prohibited heating and  
cooling calls. The sensor that has triggered this fault is monitoring the refrigerant  
temperature between the TXV and the water coil. The UPM board is aware of the  
mode of operation, and this sensor will be monitored in the heating mode. Contact  
your local contractor for service. Press enter key to return to normal thermostat  
display.  
Bosch Connected Control Thermostat (05.2024)  
| 21  
GeneralDetails
NameBOSCH BCC110 Connected Control Thermostat Instruction Manual
MakeBosch
LanguageEnglish
FiletypePDF (Download)
File size0.4 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
BOSCH BCC110 Connected Control Wi-Fi Thermostat User Manual
BOSCH BCC110 Connected Control Wi-Fi Thermostat User Manual
BOSCH RT_II_230V Room Thermostat Instructions
BOSCH RT_II_230V Room Thermostat Instructions
BOSCH Smart Home Room Thermostat Instruction Manual
BOSCH Smart Home Room Thermostat Instruction Manual
BOSCH RT20 RF Room Thermostat User Manual
BOSCH RT20 RF Room Thermostat User Manual
BOSCH 6721807275 Smart Radiator Thermostat Installation Guide
BOSCH 6721807275 Smart Radiator Thermostat Installation Guide
BOSCH Thermostat atmosphere Smart Home 230 V Instruction Manual
BOSCH Thermostat atmosphere Smart Home 230 V Instruction Manual
BOSCH 8750000270 Radiator Thermostat II Smart Home Radiator Thermostat Instructions
BOSCH 8750000270 Radiator Thermostat II Smart Home Radiator Thermostat Instructions
BOSCH II 230V Room Thermostat Instruction Manual
BOSCH II 230V Room Thermostat Instruction Manual
BOSCH Radiator Thermostat Instructions
BOSCH Radiator Thermostat Instructions
BOSCH BCC110 Thermostat User Guide
BOSCH BCC110 Thermostat User Guide

BOSCH BCC110 Connected Control Thermostat Instruction Manual