Staging Logic
4
WSHP Fault Codes
Staging response determines how the thermostat stages heating or cooling calls
based on the difference between space temperature and the set point (1.0°F or
1.5°F).
If your Bosch Connected Control (BCC) thermostat is connected to one of Bosch’s
Water Source Heat Pump (WSHP) products, the following WSHP fault codes can
be displayed on the BCC. Please refer to the WSHP product’s installation and
operation manual for more details on troubleshooting.
3.1 Staging Timers
4.1 High Pressure Alarm
There are 4 timers defined in the stage algorithm, MRT (Minimum Run Timer), ASC
(Anti-Short Cycle Timer), Stage Delay and a fixed 3 minutes timer for quick staging
down.
The equipment has detected a high head pressure condition and prohibited heating
and cooling calls. Contact your local contractor for service. Press the enter key to
return to normal thermostat display.
•
When any stage is on, it has to run for the MRT, except in the scenario of
quick staging down where the heating/cooling is turned off.
4.2 Low Pressure Alarm
•
•
When any stage is up or down, it has to wait for Stage Delay to expire.
The equipment has detected a low head pressure condition and prohibited heating
and cooling calls. Contact your local contractor for service. Press the enter key to
return to normal thermostat display.
When all stages are turned off, the system has to wait for ASC to expire
before it can be turned on again. Please note, the ASC timers run
concurrently with Fan off Delay timer defined elsewhere.
4.3 Condenser Coil Freeze Alarm
Interval
Minimum
3 Minutes
Maximum
90 Minutes
Stage Delay
5 Minutes
3 Minutes
Default
10 Minutes
5 Minutes
5 Minutes
3 Minutes
Resolution
1 Minute
1 Minute
1 Minute
Fixed
The equipment has detected a freeze condition and prohibited heating and
cooling calls. The sensor that has triggered this fault is monitoring the refrigerant
temperature between the TXV and the air coil. The UPM board is aware of the mode
of operation, and this sensor will be monitored in the cooling mode. Contact your
local contractor for service. Press enter key to return to normal thermostat display.
Stage Delay
MRT(Minimum Run Time) 3 Minutes
ASC (Anti-Short Cycle)
Quick Stage Down
0 Minutes
3 Minutes
Table 1 Stage Timers
4.4 Condensate Alarm
The equipment has detected a condensate line blockage condition and prohibited
cooling calls. Contact your local contractor for service. Press the enter key to
return to normal thermostat display.
3.2 Staging Temp
Stage temperature is use to determine whether there is a need for quick staging up
or staging down based on a temperature setpoint differential.
4.5 Brown Out Alarm
Interval
Minimum
0°F
Maximum
15°F
Default
4°F
Resolution
1°F
The equipment has detected a power brownout condition and prohibited heating
and cooling calls. Contact your local contractor for service. Press the enter key to
return to normal thermostat display.
Stage Temp
Table 2 Stage Temp
4.6 Evaporator Coil Freeze Alarm
The equipment has detected a freeze condition and prohibited heating and
cooling calls. The sensor that has triggered this fault is monitoring the refrigerant
temperature between the TXV and the water coil. The UPM board is aware of the
mode of operation, and this sensor will be monitored in the heating mode. Contact
your local contractor for service. Press enter key to return to normal thermostat
display.
Bosch Connected Control Thermostat (05.2024)
| 21
| General | Details |
|---|---|
| Name | BOSCH BCC110 Connected Control Thermostat Instruction Manual |
| Make | Bosch |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.4 MB |

BOSCH BCC110 Connected Control Wi-Fi Thermostat User Manual

BOSCH RT_II_230V Room Thermostat Instructions

BOSCH Smart Home Room Thermostat Instruction Manual

BOSCH RT20 RF Room Thermostat User Manual

BOSCH 6721807275 Smart Radiator Thermostat Installation Guide

BOSCH Thermostat atmosphere Smart Home 230 V Instruction Manual

BOSCH 8750000270 Radiator Thermostat II Smart Home Radiator Thermostat Instructions

BOSCH II 230V Room Thermostat Instruction Manual

BOSCH Radiator Thermostat Instructions

BOSCH BCC110 Thermostat User Guide