Home > Aprilaire > Aprilaire S86N MU Multi Stage Universal Thermostat Instruction Manual

Aprilaire S86N MU Multi Stage Universal Thermostat Instruction Manual

TABLE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS (S86N MUPR ONLY)  
TABLE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS (S86N MUPR ONLY)  
System  
setting  
Factory default setting  
(bold) and setting range  
System  
setting  
Factory default setting  
(bold) and setting range  
Description  
Description  
Low Vent RH  
Limit  
Sets the ventilation indoor RH lockout limitꢀ (Only  
20%  
Enables high mixing temperatureꢀ  
(Only available is HVAC Fan with Vent is set to  
Yes with high and low limitsꢀ)  
High Mixing  
Disabled  
available if Low Vent RH Limit is set to Enabledꢀ)  
10% to 30%  
Temperature  
Enabled  
High Vent  
Temperature  
Limit  
Enables high ventilation temperature lockout  
limitꢀ (Only available if an outdoor sensor option  
is enabledꢀ)  
Disabled  
Enabled  
Sets the high mixing temperatureꢀ  
(Only available if High Mixing Temperature is set  
to Enabledꢀ)  
High Mixing  
Temperature  
80°F or (26°C)  
60°F to 105°F (14°C to 41°C)  
High Vent  
Temperature  
Limit  
Sets high ventilation temperature lockout limitꢀ  
(Only available if High Vent Temperature Limit is  
set to Enabledꢀ)  
100°F (38°C)  
85°F to 105°F (29°C to 41°C)  
Enables low mixing temperatureꢀ  
(Only available is HVAC Fan with Vent is set to  
Yes with high and low limitsꢀ)  
Low Mixing  
Temperature  
Disabled  
Enabled  
Low Vent  
Temperature  
Limit  
Enables low ventilation temperature lockout  
limitꢀ (Only available if an outdoor sensor option  
is enabledꢀ)  
Disabled  
Enabled  
Sets the Low mixing temperatureꢀ  
(Only available if Low Mixing Temperature is set  
to Enabledꢀ)  
Low Mixing  
Temperature  
40°F (6°C)  
0°F to 50°F (-18°C to 12°C)  
Low Vent  
Temperature  
Limit  
Sets low ventilation temperature lockout limitꢀ  
(Only available if Low Vent Temperature Limit is  
set to Enabledꢀ)  
10°F (-12°C)  
-10°F to 40°F (-24°C to 6°C)  
Fresh Air  
Reminder  
Enable or disable the Service Fresh Air  
messageꢀ  
Disabled  
Enabled  
Selects if ventilation forces the fan onꢀ (Yes with  
high and low limits is only available if an  
outdoor sensor option is enabledꢀ)  
Yes  
Select number of months between Service  
Fresh Air messagesꢀ  
12 Months  
1 to 12 Months  
HVAC Fan  
with Vent?  
Recurrence  
Yes with high and low limits  
No  
34  
35  
GeneralDetails
NameAprilaire S86N MU Multi Stage Universal Thermostat Instruction Manual
MakeAprilaire
LanguageEnglish
FiletypePDF (Download)
File size0.37 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Aprilaire 8570 Premium Programmable Thermostat Instruction Manual
Aprilaire 8570 Premium Programmable Thermostat Instruction Manual
Aprilaire 8538 Digital Heat Cool Thermostat Owner’s Manual
Aprilaire 8538 Digital Heat Cool Thermostat Owner’s Manual
AprilAire S86W MUPR WiFi Thermostat User Guide
AprilAire S86W MUPR WiFi Thermostat User Guide
Aprilaire S86WMUPR Programmable Wi-Fi Multi Stage Universal Thermostat Installation Guide
Aprilaire S86WMUPR Programmable Wi-Fi Multi Stage Universal Thermostat Installation Guide
Aprilaire S86N MUPR Multi Stage Universal Thermostat Owner’s Manual
Aprilaire S86N MUPR Multi Stage Universal Thermostat Owner’s Manual
Aprilaire S84N 1H1C Programmable Single Stage Universal Thermostat Owner’s Manual
Aprilaire S84N 1H1C Programmable Single Stage Universal Thermostat Owner’s Manual

Aprilaire S86N MU Multi Stage Universal Thermostat Instruction Manual