TABLE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS (S86N MUPR ONLY)
TABLE 5 – FRESH AIR VENTILATION SYSTEM SETTINGS (S86N MUPR ONLY)
System
setting
Factory default setting
(bold) and setting range
System
setting
Factory default setting
(bold) and setting range
Description
Description
Low Vent RH
Limit
Sets the ventilation indoor RH lockout limitꢀ (Only
20%
Enables high mixing temperatureꢀ
(Only available is HVAC Fan with Vent is set to
Yes with high and low limitsꢀ)
High Mixing
Disabled
available if Low Vent RH Limit is set to Enabledꢀ)
10% to 30%
Temperature
Enabled
High Vent
Temperature
Limit
Enables high ventilation temperature lockout
limitꢀ (Only available if an outdoor sensor option
is enabledꢀ)
Disabled
Enabled
Sets the high mixing temperatureꢀ
(Only available if High Mixing Temperature is set
to Enabledꢀ)
High Mixing
Temperature
80°F or (26°C)
60°F to 105°F (14°C to 41°C)
High Vent
Temperature
Limit
Sets high ventilation temperature lockout limitꢀ
(Only available if High Vent Temperature Limit is
set to Enabledꢀ)
100°F (38°C)
85°F to 105°F (29°C to 41°C)
Enables low mixing temperatureꢀ
(Only available is HVAC Fan with Vent is set to
Yes with high and low limitsꢀ)
Low Mixing
Temperature
Disabled
Enabled
Low Vent
Temperature
Limit
Enables low ventilation temperature lockout
limitꢀ (Only available if an outdoor sensor option
is enabledꢀ)
Disabled
Enabled
Sets the Low mixing temperatureꢀ
(Only available if Low Mixing Temperature is set
to Enabledꢀ)
Low Mixing
Temperature
40°F (6°C)
0°F to 50°F (-18°C to 12°C)
Low Vent
Temperature
Limit
Sets low ventilation temperature lockout limitꢀ
(Only available if Low Vent Temperature Limit is
set to Enabledꢀ)
10°F (-12°C)
-10°F to 40°F (-24°C to 6°C)
Fresh Air
Reminder
Enable or disable the Service Fresh Air
messageꢀ
Disabled
Enabled
Selects if ventilation forces the fan onꢀ (Yes with
high and low limits is only available if an
outdoor sensor option is enabledꢀ)
Yes
Select number of months between Service
Fresh Air messagesꢀ
12 Months
1 to 12 Months
HVAC Fan
with Vent?
Recurrence
Yes with high and low limits
No
34
35
| General | Details |
|---|---|
| Name | Aprilaire S86N MU Multi Stage Universal Thermostat Instruction Manual |
| Make | Aprilaire |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.37 MB |

Aprilaire 8570 Premium Programmable Thermostat Instruction Manual

Aprilaire 8538 Digital Heat Cool Thermostat Owner’s Manual

AprilAire S86W MUPR WiFi Thermostat User Guide

Aprilaire S86WMUPR Programmable Wi-Fi Multi Stage Universal Thermostat Installation Guide

Aprilaire S86N MUPR Multi Stage Universal Thermostat Owner’s Manual

Aprilaire S84N 1H1C Programmable Single Stage Universal Thermostat Owner’s Manual