ADVANCED CONFIGURATION SERVICE MENUS  
CONFIGURE SERVICE MENUS  
The following Service Menus (SM) commonly require configuration. Please verify that  
these are set for your specific application. Additional configuration may be required.  
SM 100 = Programmable or Nonprogrammable  
SM 110 = System Type  
SM 120 = Fan Control for Heating  
SM 135 = W1 Heat Output NO or NC  
SM 170 = Remote Sensors  
SM 240 = Number of Programmable Events per Day  
SM 395 = Override Duration for Programmable Operation  
SM 340 = Keypad Lock Out  
Service Menu  
Number  
Selected  
Option  
SERVICE MENU ACCESS  
1. Hold lower right and lower left keys for five seconds.  
2. Press Next or Go Back button to select a Service Menu.  
3. Press ▲/ ▼ to select option.  
4. Press Done when complete.  
Menu  
Feature  
Option  
Description  
100  
Schedule Format  
0 = Nonprogrammable (Default)  
1 = Programmable  
Selects the schedule format. In non-programmable mode all scheduling functions are  
removed from the display.  
2 = 5-1-1 Schedule Mode  
3 = 5-2 Schedule Mode  
0 = Disabled (Default)  
1 = Enabled (2007 US Format)  
101  
110  
Daylight Savings  
System Type  
When enabled daylight savings time follows the US 2007 format. (Begins second Sunday  
of March at 2AM and ends on the first Sunday of November at 2AM.  
1
2
3
4
1 Stage Heat /1 Stage Cool (Default)  
2 Stage Heat /1 Stage Cool  
1 Stage Heat Only  
Heat Stage 2 takes the place of this outside air damper output.  
1 Stage Cool Only  
111  
Outside Air Damper  
Configuration  
0 = Damper Continuous  
Damper output is not available when being used as a fan speed.  
0: Output runs continuously when thermostat is not in System OFF Mode.  
1: Output cycles with a heat or cool demand.  
1 = Damper Cycled with Demand (Default)  
0 = OFF for Heating (Gas/Oil Heat)  
1= Electric Furnace (Default)  
1 = Single Speed Fan  
120  
121  
Fan Control (Heating)  
Fan Speeds  
0: The thermostat will Not activate the fan with a heating demand.  
1: The thermostat will activate the fan with heat demand.  
Single Speed - White/Orange Lead  
2-Speeds - White/Orange & White Brown Leads  
3-Speeds - White/Orange, White/Red & White Brown Leads  
2 = 2-Speed Fan  
3 = 3-Speed Fan (Default)  
134  
135  
170  
Cool Output Configuration 0 = NC: Normally Closed Operation (Default)  
Reverses the ON/OFF operation for the heat output. NC operation powers on with a  
demand. NO opreation powers off with a demand and will be on with no demand unless  
main power is removed from the thermostat.  
1 = NO: Normally Open Operation  
W1 Heat Output  
Configuration  
0 = NC: Normally Closed Operation (Default)  
1 = NO: Normally Open Operation  
Reverses the ON/OFF operation for the first stage heat output. NC operation powers on  
with a demand. NO opreation powers off with a demand and will be on with no demand  
unless main power is removed from the thermostat.  
Remote Sensor Input  
0= No Remote Sensors (Default)  
0: Remote temperature sensing is disabled.  
1: The TW180 uses the remote sensor only for temperature sensing.  
2: The TW180 averages the local and remote sensor for temperature sensing.  
When using a remote sensor an open or short will turn off outputs and display either  
2Ero(open) or 2Erc (closed). Fault detection settings are not used.  
1= Remote Indoor Sensor Connected  
2 = Remote Sensor Connected And Sensor  
Averaging  
171  
Pipe Sensor  
0 = Disabled (Default)  
1 = Two Pipe Operation  
Enables fan coil pipe sensor operation. Connect a PECO pipe sensor or dry switch closure  
for change over from Summer (cold water) to Winter (hot water) on COOL output (blue  
wire). 2-pipe operation uses the COOL output for heating and cooling. Heat 1 is disabled.  
4-pipe operation allows heat 1 in summer mode of operation.  
2 = Four Pipe Operation (use for 2-pipe with  
electric heat relay)  
Available when SM 110 = 1 or 2  
172  
173  
Pipe Sensor Threshold for 50F to 72F (Default 60F)  
Cooling  
Available when SM 171 = 1 or 2. Changes to Cool when pipe temp is below threshold.  
Pipe Sensor Threshold for 75F to 90F (Default 80F)  
Heating  
Available when SM 171 = 1 or 2. Changes to Heat when pipe temp is above threshold.  
© COPYRIGHT 2023 PECO, INC. ALL RIGHTS RESERVED.  
P/N 74150 3220-2384 REV 04  
4
GeneralDetails
NamePECO TW180 Thermostat Instruction Manual
MakePECO
LanguageEnglish
FiletypePDF (Download)
File size0.56 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PECO T8168 Performance Pro Thermostat Installation Guide
PECO T8168 Performance Pro Thermostat Installation Guide
PECO T372P Thermostat Instruction Manual
PECO T372P Thermostat Instruction Manual
PECO T8168B-2 BACnet Proportional Thermostat Installation Guide
PECO T8168B-2 BACnet Proportional Thermostat Installation Guide

PECO TW180 Thermostat Instruction Manual