T8168B-2 BACnet® INSTALLATION GUIDE  
The PECO BACnet® T8168B-2 thermostat  
!
WARNING  
▲
Thank you for choosing a PECO® Performance PRO™ thermostat. The  
T8168B-2 thermostat is intended for commercial and residential enviroments. It  
supports both programmable and non-programmable operation.  
Key features include: Either BACnet® IP or MS/TP Connectivity, auto-  
changeover; optional remote sensor; three levels of keypad lockout with optional  
PIN access code; a heat/cool Demand Indicator; up to four scheduled events per  
day, a 365-day calendar, 20 holidays, holiday override and temporary override.  
• READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO  
INSTALL, OPERATE OR SERVICE THIS THERMOSTAT.  
• Failure to observe safety information and comply with instructions could  
result in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.  
• To avoid electrical shock or damage to equipment, disconnect power  
before installing or servicing and use only wiring with insulation rated for full  
thermostat operating voltage.  
Applications  
• Use care to avoid electrostatic discharge.  
• To avoid potential fire and/or explosion do not use in potentially flammable  
or explosive atmospheres.  
The PECO® Performance PRO™ T8168 applications include fan coil, PTAC and  
conventional system with a single, multi speed or 0-10 VDC Fan.  
System Mode Selections: Off-Heat-Cool-Auto  
ON-OFF Heat/Cool Outputs: Up to 2 Heat, 2 Cool  
Proportional Heat/Cool Outputs: Three Wire Floating or 0-10 VDC Control  
Fan Control: Cycling (Auto) or Continuous (On); Up to 3 Speeds or Staged  
Permanent Memory: All device settings are stored in permanent memory.  
Optional Connections: Remote Sensor, Pipe Sensor, Fault Detection and Setback  
• Retain these instructions for future reference.  
• This product, when installed, will be part of an engineered system whose  
specifications and performance characteristics are not designed or  
controlled by PECO® . Review applications and national and local codes to  
assure that the installation will be functional and safe.  
CAUTION!  
TERMINAL BLOCK DESIGNATIONS  
• 24 VAC low-voltage thermostat. Do not install on voltages higher than 30 VAC.  
!
Terminal  
\Description  
Return To  
▲
• Use copper wire only  
• Use care to avoid electrostatic discharge to the thermostat.  
24 VAC-1 24 VAC 1 (UNSWITCHED)  
24 VAC-2 24 VAC 2  
RATINGS  
Outputs: Y1, Y2, W1, W2, G, G1  
24 VAC (20-30 VAC); 50/60 Hz  
10 VA  
Outputs: WD, GD, YD  
0-10 VDC: Loads must be 1.2K ohms minimum  
4-20 mA: Loads must be 600 ohms maximum  
This thermostat uses triacs switching for accuracy and quiet operation.  
24 VAC-2 24 VAC 2  
Note: A load must be  
connected to outputs  
for testing  
Y1  
W1  
Y2  
W2  
G
COOL 1  
HEAT 1  
COOL Open (TWF)  
HEAT Open (TWF)  
24 VAC 1  
24 VAC 1  
24 VAC 1  
24 VAC 1  
24 VAC 1  
24 VAC 1  
24 VAC 2  
24 VAC 2  
24 VAC 2  
SC  
COOL 2 or FAN 3 (MED) COOL Close (TWF)  
HEAT 2  
HEAT Close (TWF)  
FAN 1 (HI)  
G1  
YD  
WD  
GD  
S1  
S2  
SC  
4A  
4B  
4C  
FAN LO or DAMPER Configurable  
0-10VDC COOL (4-20mA)  
0-10VDC HEAT (4-20mA)  
0-10VDC FAN (4-20mA)  
REMOTE SENSOR, FAULT DETECTION  
PIPE SENSOR  
INSTALLATION INSTRUCTIONS  
Select an appropriate thermostat location  
Locate the thermostat about four feet (1.2m) above the floor on a wall with good  
ventilation, average temperature and good response to temperature changes.  
The T8168 may be mounted on a:  
• Horizontal or vertical 2” X 4” device box  
• Horizontal 4” X 4” device box  
• Flat surface  
SC  
DC/SENSOR COMMON  
RS485A (-)  
Do not locate the thermostat where it can be affected by:  
• Direct sunlight  
• Drafts or dead areas behind doors  
• Radiating heat or cool from appliances or equipment  
• Concealed pipes or chimneys  
RS485B (+)  
RS485 COMMON  
• Outside walls or unheated/uncooled areas  
Required components (not included, unless otherwise specified):  
• Screws and wall anchors (included)  
• WARNING: Disconnect power before beginning installation.  
• CAUTION: Use copper wire only  
• CAUTION: Do not connect unused wires together  
!
▲
• Screwdrivers: Phillips (for wallplate); small flathead (for terminal blocks)  
• Drill with 3/16” drill bit (or 7/32” for plaster)  
• Wire cutter and stripper  
TECHNICAL SPECIFICATIONS  
Temperature Control Range: 50° to 90° F (10° to 32° C)  
Differential: 1° F (0.5°C)  
• Level  
Input Power: 24 VAC (20-30 VAC) 50/60 Hz (+/- 10%)  
Terminal Connections: 14-24 AWG stranded or solid wire  
Operating Temperature: 0° to 120°F (-18° to 49°C)  
Shipping/Storage Temperature: -20° to 130°F (-29° to 54°C)  
Operating Humidity: 5% to 95% RH, non-condensing  
Physical Dimensions: 4.3” H x 5.7” W x 1.3”D  
Proportional Output Band Width: 2°F (1°C)  
Mounting holes  
Mounting holes  
Wiring passage  
Proportional Stroke Time Default: 2 Minutes (Configurable)  
© COPYRIGHT 2024 PECO, INC. ALL RIGHTS RESERVED.  
P/N 74599 3220-2406 REV 00  
1
GeneralDetails
NamePECO T8168B-2 BACnet Proportional Thermostat Installation Guide
MakePECO
LanguageEnglish
FiletypePDF (Download)
File size0.42 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PECO T8168 Performance Pro Thermostat Installation Guide
PECO T8168 Performance Pro Thermostat Installation Guide
PECO T372P Thermostat Instruction Manual
PECO T372P Thermostat Instruction Manual
PECO TW180 Thermostat Instruction Manual
PECO TW180 Thermostat Instruction Manual

PECO T8168B-2 BACnet Proportional Thermostat Installation Guide