Technical data  
Technical data GM-TA (PCN 1244-017783)  
Supply voltage  
230 Vac, +10%/–10%, 50 Hz  
Relay switching capacity  
Power consumption  
Terminal size  
Max 16 A (resistive load)  
Max 5 VA  
Max. 2,5 mm2, screwed  
20°C to +50°C  
Storage temperature  
Operation ambient  
temperature range  
25°C to +40°C  
Switching hysteresis  
Accuracy  
+/–1 K  
+/– 1,5 K incl. sensor accuracy  
Programmable parameters  
Default  
Temperature setting range Set point : 0°C to 6°C  
2°C  
10°C  
0,5 h  
Lower temperature range 5°C to –25°C  
Post heating time  
0 to 3 hours  
On: normal operation  
Off: relay off (open)  
Operating modus  
Test: relay On (30 minutes)  
Enclosure thermostat  
Installation  
DIN-rail-mounted  
IP rating  
IP 20  
Ambient sensor GM-TA-AS (PCN 1244-017965) included  
IP rating  
IP 65  
Installation  
Wall mounted / outdoors  
202AT +/-1% NTC 2.0 K @ 25°C  
Ambient sensor type  
Approvals  
CE, UKCA, RoHS, REACH  
Error codes  
Ambient sensor open circuit  
or short circuit / Check  
E1  
connections and resistance  
E2  
Internal error / Replace GM-TA  
8
|