nVent GM-TA Thermostat User Manual
Technical data
Technical data GM-TA (PCN 1244-017783)
Supply voltage
230 Vac, +10%/–10%, 50 Hz
Relay switching capacity
Power consumption
Terminal size
Max 16 A (resistive load)
Max 5 VA
Max. 2,5 mm2, screwed
–20°C to +50°C
Storage temperature
Operation ambient
temperature range
–25°C to +40°C
Switching hysteresis
Accuracy
+/–1 K
+/– 1,5 K incl. sensor accuracy
Programmable parameters
Default
Temperature setting range Set point : 0°C to 6°C
2°C
–10°C
0,5 h
Lower temperature range –5°C to –25°C
Post heating time
0 to 3 hours
On: normal operation
Off: relay off (open)
Operating modus
Test: relay On (30 minutes)
Enclosure thermostat
Installation
DIN-rail-mounted
IP rating
IP 20
Ambient sensor GM-TA-AS (PCN 1244-017965) included
IP rating
IP 65
Installation
Wall mounted / outdoors
202AT +/-1% NTC 2.0 K @ 25°C
Ambient sensor type
Approvals
CE, UKCA, RoHS, REACH
Error codes
Ambient sensor open circuit
or short circuit / Check
E1
connections and resistance
E2
Internal error / Replace GM-TA
8
|
nVent.com/RAYCHEM
| General | Details |
|---|---|
| Name | nVent GM-TA Thermostat User Manual |
| Make | nVent |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.45 MB |

nVent RAYCHEM E507S-LS Line Sensing Thermostat Instruction Manual