7. Reconnect power to the HVAC equipment. You are now  
ready to configure your thermostat for operation.  
°F or °C Temperature Display  
Select between °F (Fahrenheit) or °C (Celsius) temperature  
display. °F (Fahrenheit) is the default.  
COMMON CONTROL SETUP  
Minimum On Time  
Default: 2 minutes Select between 0-5 Minutes. The value is  
displayed on the main display. The system will operate for a  
minimum of 0 minutes to 5 minutes depending on your setting.  
ONE COMPRESSOR CONFIGURATION  
Aux Heat Differential (Heat Pump Operation)  
Default: 1˚F (0.5˚C) Select between 1-6˚F (0.5-3˚C). The value  
is displayed on the main display. Proceed to Aux Heat Delay.  
TOUCHSCREEN INSTALLER MENU SETTINGS  
TWO COMPRESSOR CONFIGURATION  
2nd Stage Differential  
Press and hold the Menu Button  
on the lower left of the  
D
Minimum Off Time  
Default: 4 minutes Select between 2 to 5 Minutes. The value is  
displayed on the main display. The system will allow equipment  
recovery for 2 to 5 minutes before turning on again.  
thermostat touchscreen for 5 seconds to access. Installer  
Menu will briefly display in the Dot Matrix Area followed by  
Conventional/HP. To save a setting and advance to the next  
Default: 1˚F (0.5˚C) Select between 1-6˚F (0.5-3˚C). The value  
menu item, press the Checkmark Button  
(Right Arrow). To  
M
is displayed in the main display.  
return to the previous menu item, press the Back Button  
L
Remote Sensor (Averaging)  
(Left Arrow).  
2nd Stage Delay  
Switching between Remote Only or Remote + Tstat, the X5N-  
NX thermostat can either use the remote sensors (default) or can  
average the remote sensor and the internal temperature sensor.  
Default: 20 minutes. Select between 5-40 Minutes in 5  
Conventional/ Heat Pump  
Select between Conventional or Heat Pump operation.  
Conventional is the default.  
1
2
3
minute increments. The value is displayed in the main display.  
NOTE: The preceding options only apply to multi-stage  
A NOTE: If no remote sensors are detected, the thermostat will  
default to the internal temperature sensor regardless of the  
selected option.  
WARNING: Your thermostat is NOT ready to use. You  
C
heat pump configuration.  
NOTE: If Conventional is Selected Proceed to Stages Cool.  
must complete the Thermostat Setup section before using  
the thermostat. Failure to do this can result in damage to your  
equipment.  
If Heat Pump is selected, proceed to # of Compressors.  
Aux Heat Delay  
Default: 20 minutes. Select between 5-40 Minutes in 5  
minute increments. The value is displayed in the main display.  
Temperature Override Range (During Lockout)  
Default: ±3˚F (±1.5˚C) This setting adjusts the temperature  
variance allowed from the scheduled setpoint when the  
faceplate locked. The range is from ±2˚F (±1˚C) to ±8˚F(±4˚C).  
CONVENTIONAL SETUP  
Stages Cool  
Default: 1 Select between 1 or 2 Stages Cool. The value is  
displayed in the main display.  
THERMOSTAT SETUP  
High & Low Balance Point Configuration  
The Dot Matrix Display will provide feedback on the  
User Menu or Installer Menu configuration and selected  
If the thermostat is being used as a Heat Pump thermostat and  
current weather conditions are enabled or an outdoor sensor is  
connected to the remote sensor terminals, the thermostat can  
be configured to disable the use of auxiliary heat during  
warmer weather and to lock out the compressor during colder  
weather. If the weather conditions are enabled the high and  
low balance point settings are available in the installer menu.  
Override Timer  
options. The Up Button  
and Down Button  
are used to  
J
K
select parameters while the LEFT ARROW (Back Button) and  
RIGHT ARROW (Accept button) are used to accept settings  
and navigate through the menu. At any time you can use the  
CANCEL BUTTON to leave the User or Installer Menu.  
Stages Heat  
Default: 8 Hours Set the amount of time a setpoint override  
from the normal schedule is active from 0 hours - 24 hours, in 10-  
minute increments. At the end of the override time, the normal  
schedule will resume. Set to 0 hours to completely remove  
setpoint adjustability from the thermostat front panel.  
Default: 1 Select between 1 or 2 Stages Heat. The value is  
displayed in the Main Display.  
Gas or Electric Heat  
Default: Gas Select between Gas or Electric operation.  
TOUCHSCREEN USER MENU SETTINGS  
TIP: Refer to the manufacturers heat pump equipment  
B
Calibration Offset  
manual for temperature cut-offs on the equipment.  
Tap the Menu Button  
on the lower left of the thermostat  
D
NOTE: If you selected Conventional Heat, proceed to  
The thermostat is pre-calibrated at the factory, but in some  
installations, lack of airflow at the sensor or proximity to other  
warming or cooling sources may cause the temperature to be off by a  
few degrees. The X5N-NX thermostat includes a temperature  
calibration offset with a range of ±6˚F (±3˚C) in 0.2˚F (0.1˚C) increments.  
touchscreen to access the User Menu. The Dot Matrix Area  
will guide you through the User settings. To save a setting  
and navigate to the next menu item, press the Checkmark  
Low Balance Point  
Default: -54˚F (-48˚C) Select between -54˚F to 39˚F (-48˚C to  
4˚C). The value is displayed in the main display. This will lock out  
the heat pump at the selected outdoor temperature.  
Minimum On Time.  
HEAT PUMP SETUP  
# of Compressors  
Default: 1 Select between 1 or 2 Stage Compressor. The  
value is displayed in the main display.  
Button  
(Right Arrow). To return to the previous menu item,  
M
press the Back Button  
(Left Arrow). Use the Up  
and  
L
J
Down  
Buttons to select from the available options for each  
K
Maximum Heat Temperature  
Default: 88˚F (31˚C) Sets the Maximum Temperature range  
between 43˚F to 88˚F (6˚C to 31˚C)  
High Balance Point  
Default: 118˚F (48˚C) Select between 41˚F-118˚F (5˚C-48˚C).  
The value is displayed in the main display. This will lock out the  
auxiliary heat at the selected outdoor temperature.  
setting.  
Brightness - Screen Brightness  
Default: Auto Select brightness of the touchscreen display  
between Auto, High, Medium, and Low.  
Enable Aux/EHeat  
Select between Aux/EHeat Mode On (default) or Aux/EHeat  
Mode Off.  
Minimum Heat Temperature  
Default: 38˚F (4˚C) Sets the Minimum Temperature range  
between 38˚F to 82˚F (4˚C to 28˚C)  
CLK Terminals  
Color - Display color  
Default: Cyan Select the color of your display. Between Cyan,  
Purple, Yellow, White, Red, Green, and Blue.  
Select between OCC/UNOCC (occupied/unoccupied) or OFF.  
When OFF is selected, a signal received will turn off the HVAC  
system. When OCC/UNOCC is selected, the HVAC system will  
switch between the DAY (Occupied) and NIGHT (Unoccupied)  
setpoint settings.  
NOTE: If the Aux/EHeat ON is selected, proceed to Heat Pump  
Option. Otherwise, proceed to the Minimum On Time option.  
Maximum Cool Temperature  
Default: 108˚F (42˚C) Sets the Maximum Temperature range  
between 66˚F to 108˚F (18˚C to 42˚C)  
Heat Pump Option  
Default: HP Regular Select between HP Regular or HP Dual  
Fuel.  
Display Complexity  
Default: Full There are three different resting display options.  
Thermostat Address  
Sets the thermostat address to receive and transmit data and  
control signals.  
Minimum Cool Temperature  
Default: 60˚F (16˚C) Sets the Minimum Temperature range  
between 60˚F to 102˚F (16˚C to 39˚C)  
NOTE: If needed, the thermostat will perform the function of  
a fossil fuel kit. When HP Dual Fuel is selected the thermostat  
will turn off the compressor with a call for AUX heat. The HP  
Regular option will allow the compressor and AUX heat to run  
simultaneously.  
Options:  
Full: (default) Shows entire screen all the time  
Minimal: if nothing is noticed by the sensor for 5 seconds  
only room temperature shows.  
Dark: if nothing is noticed by the sensor for 5 seconds the  
whole screen goes blank.  
ATTENTION: This is adjustable from 1-99 but the NT-IPXB  
C
1st Stage Differential  
Default: 1˚F (0.5˚C) Select between 1-6˚F (0.5-3˚C). The value is  
displayed in the main display. The 1st Stage Differential is the  
temperature degree change required before the thermostat responds.  
controller can only support 32 thermostats. Each thermostat  
must have its own unique address.  
Page 2  
GeneralDetails
NameNT NetX X5N-NX Thermostat Instruction Manual
MakeNT
LanguageEnglish
FiletypePDF (Download)
File size0.26 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
NT NetX X-Series Thermostat Installation Guide
NT NetX X-Series Thermostat Installation Guide
NT NetX X5 IP Ethernet Thermostat Instruction Manual
NT NetX X5 IP Ethernet Thermostat Instruction Manual
NT NetX X5N-SM Thermostat Installation Guide
NT NetX X5N-SM Thermostat Installation Guide

NT NetX X5N-NX Thermostat Instruction Manual