NT NetX X5N-NX Thermostat Instruction Manual
7. Reconnect power to the HVAC equipment. You are now
ready to configure your thermostat for operation.
°F or °C Temperature Display
Select between °F (Fahrenheit) or °C (Celsius) temperature
display. °F (Fahrenheit) is the default.
COMMON CONTROL SETUP
Minimum On Time
Default: 2 minutes Select between 0-5 Minutes. The value is
displayed on the main display. The system will operate for a
minimum of 0 minutes to 5 minutes depending on your setting.
ONE COMPRESSOR CONFIGURATION
Aux Heat Differential (Heat Pump Operation)
Default: 1˚F (0.5˚C) Select between 1-6˚F (0.5-3˚C). The value
is displayed on the main display. Proceed to Aux Heat Delay.
TOUCHSCREEN INSTALLER MENU SETTINGS
TWO COMPRESSOR CONFIGURATION
2nd Stage Differential
Press and hold the Menu Button
on the lower left of the
D
Minimum Off Time
Default: 4 minutes Select between 2 to 5 Minutes. The value is
displayed on the main display. The system will allow equipment
recovery for 2 to 5 minutes before turning on again.
thermostat touchscreen for 5 seconds to access. Installer
Menu will briefly display in the Dot Matrix Area followed by
Conventional/HP. To save a setting and advance to the next
Default: 1˚F (0.5˚C) Select between 1-6˚F (0.5-3˚C). The value
menu item, press the Checkmark Button
(Right Arrow). To
M
is displayed in the main display.
return to the previous menu item, press the Back Button
L
Remote Sensor (Averaging)
(Left Arrow).
2nd Stage Delay
Switching between Remote Only or Remote + Tstat, the X5N-
NX thermostat can either use the remote sensors (default) or can
average the remote sensor and the internal temperature sensor.
Default: 20 minutes. Select between 5-40 Minutes in 5
Conventional/ Heat Pump
Select between Conventional or Heat Pump operation.
Conventional is the default.
1
2
3
minute increments. The value is displayed in the main display.
� NOTE: The preceding options only apply to multi-stage
A NOTE: If no remote sensors are detected, the thermostat will
default to the internal temperature sensor regardless of the
selected option.
WARNING: Your thermostat is NOT ready to use. You
C
heat pump configuration.
� NOTE: If Conventional is Selected Proceed to Stages Cool.
must complete the Thermostat Setup section before using
the thermostat. Failure to do this can result in damage to your
equipment.
If Heat Pump is selected, proceed to # of Compressors.
Aux Heat Delay
Default: 20 minutes. Select between 5-40 Minutes in 5
minute increments. The value is displayed in the main display.
Temperature Override Range (During Lockout)
Default: ±3˚F (±1.5˚C) This setting adjusts the temperature
variance allowed from the scheduled setpoint when the
faceplate locked. The range is from ±2˚F (±1˚C) to ±8˚F(±4˚C).
CONVENTIONAL SETUP
Stages Cool
Default: 1 Select between 1 or 2 Stages Cool. The value is
displayed in the main display.
THERMOSTAT SETUP
High & Low Balance Point Configuration
The Dot Matrix Display will provide feedback on the
User Menu or Installer Menu configuration and selected
If the thermostat is being used as a Heat Pump thermostat and
current weather conditions are enabled or an outdoor sensor is
connected to the remote sensor terminals, the thermostat can
be configured to disable the use of auxiliary heat during
warmer weather and to lock out the compressor during colder
weather. If the weather conditions are enabled the high and
low balance point settings are available in the installer menu.
Override Timer
options. The Up Button
and Down Button
are used to
J
K
select parameters while the LEFT ARROW (Back Button) and
RIGHT ARROW (Accept button) are used to accept settings
and navigate through the menu. At any time you can use the
CANCEL BUTTON to leave the User or Installer Menu.
Stages Heat
Default: 8 Hours Set the amount of time a setpoint override
from the normal schedule is active from 0 hours - 24 hours, in 10-
minute increments. At the end of the override time, the normal
schedule will resume. Set to 0 hours to completely remove
setpoint adjustability from the thermostat front panel.
Default: 1 Select between 1 or 2 Stages Heat. The value is
displayed in the Main Display.
Gas or Electric Heat
Default: Gas Select between Gas or Electric operation.
TOUCHSCREEN USER MENU SETTINGS
TIP: Refer to the manufacturer’s heat pump equipment
B
Calibration Offset
manual for temperature cut-offs on the equipment.
Tap the Menu Button
on the lower left of the thermostat
D
� NOTE: If you selected Conventional Heat, proceed to
The thermostat is pre-calibrated at the factory, but in some
installations, lack of airflow at the sensor or proximity to other
warming or cooling sources may cause the temperature to be off by a
few degrees. The X5N-NX thermostat includes a temperature
calibration offset with a range of ±6˚F (±3˚C) in 0.2˚F (0.1˚C) increments.
touchscreen to access the User Menu. The Dot Matrix Area
will guide you through the User settings. To save a setting
and navigate to the next menu item, press the Checkmark
Low Balance Point
Default: -54˚F (-48˚C) Select between -54˚F to 39˚F (-48˚C to
4˚C). The value is displayed in the main display. This will lock out
the heat pump at the selected outdoor temperature.
Minimum On Time.
HEAT PUMP SETUP
# of Compressors
Default: 1 Select between 1 or 2 Stage Compressor. The
value is displayed in the main display.
Button
(Right Arrow). To return to the previous menu item,
M
press the Back Button
(Left Arrow). Use the Up
and
L
J
Down
Buttons to select from the available options for each
K
Maximum Heat Temperature
Default: 88˚F (31˚C) Sets the Maximum Temperature range
between 43˚F to 88˚F (6˚C to 31˚C)
High Balance Point
Default: 118˚F (48˚C) Select between 41˚F-118˚F (5˚C-48˚C).
The value is displayed in the main display. This will lock out the
auxiliary heat at the selected outdoor temperature.
setting.
Brightness - Screen Brightness
Default: Auto Select brightness of the touchscreen display
between Auto, High, Medium, and Low.
Enable Aux/EHeat
Select between Aux/EHeat Mode On (default) or Aux/EHeat
Mode Off.
Minimum Heat Temperature
Default: 38˚F (4˚C) Sets the Minimum Temperature range
between 38˚F to 82˚F (4˚C to 28˚C)
CLK Terminals
Color - Display color
Default: Cyan Select the color of your display. Between Cyan,
Purple, Yellow, White, Red, Green, and Blue.
Select between OCC/UNOCC (occupied/unoccupied) or OFF.
When OFF is selected, a signal received will turn off the HVAC
system. When OCC/UNOCC is selected, the HVAC system will
switch between the DAY (Occupied) and NIGHT (Unoccupied)
setpoint settings.
� NOTE: If the Aux/EHeat ON is selected, proceed to Heat Pump
Option. Otherwise, proceed to the Minimum On Time option.
Maximum Cool Temperature
Default: 108˚F (42˚C) Sets the Maximum Temperature range
between 66˚F to 108˚F (18˚C to 42˚C)
Heat Pump Option
Default: HP Regular Select between HP Regular or HP Dual
Fuel.
Display Complexity
Default: Full There are three different resting display options.
Thermostat Address
Sets the thermostat address to receive and transmit data and
control signals.
Minimum Cool Temperature
Default: 60˚F (16˚C) Sets the Minimum Temperature range
between 60˚F to 102˚F (16˚C to 39˚C)
� NOTE: If needed, the thermostat will perform the function of
a fossil fuel kit. When HP Dual Fuel is selected the thermostat
will turn off the compressor with a call for AUX heat. The HP
Regular option will allow the compressor and AUX heat to run
simultaneously.
Options:
● Full: (default) Shows entire screen all the time
● Minimal: if nothing is noticed by the sensor for 5 seconds
only room temperature shows.
● Dark: if nothing is noticed by the sensor for 5 seconds the
whole screen goes blank.
ATTENTION: This is adjustable from 1-99 but the NT-IPXB
C
1st Stage Differential
Default: 1˚F (0.5˚C) Select between 1-6˚F (0.5-3˚C). The value is
displayed in the main display. The 1st Stage Differential is the
temperature degree change required before the thermostat responds.
controller can only support 32 thermostats. Each thermostat
must have its own unique address.
Page 2
| General | Details |
|---|---|
| Name | NT NetX X5N-NX Thermostat Instruction Manual |
| Make | NT |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.26 MB |

NT NetX X-Series Thermostat Installation Guide

NT NetX X5 IP Ethernet Thermostat Instruction Manual

NT NetX X5N-SM Thermostat Installation Guide