LAE AC1-2W Digital Thermostat Instruction Manual
reference instrument.
■ Exit from calibration by pressing button
TECHNICAL DATA
REF; HEA Refrigerating control (REF) or heating control mode (HEA) for the auxiliary output.
2CH
2HY
2T0
.
AC1-2W INSTRUCTION FOR USE
0...19.9°
Differential of thermostat 2. With 2HY=0 the auxiliary output always remains off.
Power supply
CONFIGURATION PARAMETERS
Thank you for having chosen a LAE electronic product. Before installing the instrument, please read these instructions carefully
to ensure maximum performance and safety.
AC1-2W…D
AC1-2W...E
AC1-2W...U
12Vac/dc ±10%, 2W
0...30min
Minimum off time.
230Vac±10%, 50/60Hz, 2W
115Vac±10%, 50/60Hz, 2W
■ To get access to the parameter configuration menu, press button
+
for 5 seconds.
After output 2 has been turned off, it remains inactive for 2T0 minutes regardless of the temperature
value measured.
DESCRIPTION
INDICATION
■ With button
or
select the parameter to be modified.
■ Press button
■ By keeping button
■ When button
to display the value.
OUT1
Channel 1 output
0...30min
Minimum on time.
2T1
2PF
Relay outputs (AC1-2W..R..)
pressed, use button
or
to set the desired value.
After output 2 has been turned on, it remains active for 2T1 minutes regardless of the temperature
value measured.
OUT2 Channel 2 output
OUT1
OUT2
8(3)A
8(3)A
is released, the newly programmed value is stored and the following parameter is displayed.
■ To exit from the setup, press button
or wait for 30 seconds.
L1
Channel 1 setpoint modification
ON/OFF
Auxiliary output state in case of probe failure.
SSR drive (AC1-2W..F..)
PAR
RANGE DESCRIPTION
Channel 2 setpoint modification
Alarm
NON;
ABS;
REL
Alarm threshold management.
ATM
OUT1
OUT2
15mA 12Vdc
15mA 12Vdc
NON : all temperature alarms are inhibited (the following parameter will be SB).
ABS : the values programmed in ALA and AHA represent the real alarm thresholds.
REL : the values programmed in ALR and AHR are alarm differentials referred to 1SP and 1SP+1HY.
1°C;
2°C;
°F
Readout scale (see table of input specifications)
Caution: upon changing the SCL value, it is then absolutely necessary to reconfigure the param-
eters relevant to the absolute and relative temperatures (SPL, SPH, 1SP, 1HY etc..)
SCL
Info / Enter button
Modify Setpoint 1 / Decrease button
Inputs
see table of input specifications
ON
ON
-50°...SPH Minimum limit for 1SP setting
SPL
SPH
1SP
1CM
Exit / Stand-by button
Increase / Modify Setpoint 2 button
T[°]
T[°]
SPL...150° Maximum limit for 1SP setting.
OFF
O
F
F
Measurement range
see table of input specifications
1SP 1SP+1HY+AHR
1SP-ALR
SPL... SPH Setpoint (value to be maintained in the room).
1SP+AHR
1SP-1HY-ALR
1SP
Temperature alarm with relative thresholds,
refrigerating control (ATM=REL, 1CH=REF)
Fig.1 - Front panel
Temperature alarm with relative thresholds,
heating control (ATM=REL, 1CH=HEA).
HY; PID
Control mode.
INSTALLATION
With 1CM=HY you select control with hysteresis: parameters 1HY, 1T0 and 1T1 are used.
With 1CM=PID you select a Proportional-Integral-Derivative control mode: parameters 1PB, 1IT,
1DT, 1AR, 1CT will be used.
Measurement accuracy
see table of input specifications
-50°...AHA Low temperature alarm threshold.
ALA...150° High temperature alarm threshold.
■ The AC1-2W sizes 110x75x55 mm (WxHxD). Fix the plate to the panel using 2 cheese-headed screws with 4 or 5 mm diameter
and then apply the instrument casing to the plate. This should be done for vertical panels and for correct positioning of the
instrument with the outlets at the bottom.
■ Make sure that electrical connections comply with the paragraph “wiring diagrams”. To reduce the effects of electromagnetic
disturbance, keep the sensor and signal cables well separate from the power wires.
ALA
Operating conditions
-10 … +50°C; 15%...80% r.H.
REF; HEA Refrigerating (REF) or Heating (HEA) control mode.
1CH
AHA
ALR
AHR
0...19.9°
OFF/ON thermostat differential. With 1HY=0 the output is always off.
1HY
-12.0...0°
0...12.0°
Low temperature alarm differential.
With ALR=0 the low temperature alarm is excluded.
ON
■ Place the probe T1 inside the room in a point that truly represents the temperature of the stored product.
ON
CE (Reference Norms)
EN60730-1; EN60730-2-9;
EN55022 (Class B); EN50082-1
OPERATION
DISPLAY
High temperature alarm differential.
With AHR=0 the high temperature alarm is excluded.
OFF
OFF
1SP 1SP+1HY T[°]
1SP-1HY 1SP
T[°]
During normal operation, the display shows either the temperature measured or one of the following indications:
Front protection
IP55
0...120min Delay before alarm temperature warning.
ATD
ON/OFF refrigerating control
(1CM=HY, 1CH=REF)
ON/OFF heating control
(1CM=HY, 1CH=HEA)
Controller in stand-by
Controller in autotuning
In tuning: timeout1 error
In tuning: timeout2 error
In tuning: overrange error
NO/YES
ST1/SN4
Stand-by button enabling.
SB
Probe T1 overrange or failure
Room high temperature alarm
Room low temperature alarm
0...30min
0...30min
Minimum off time.
1T0
1T1
1PB
Sensor input selection (see table of input specifications).
INP
After output 1 has been turned off, it remains inactive for 1T0 minutes regardless of the
temperature value measured.
In the models AC1-2WT... only.
MENU INFO
The information available in this menu is:
Minimum on time. (the following parameter will be 1PF).
After output 1 has been turned on, it remains active for 1T1 minutes regardless of the temperature
value measured.
-19.9...RHI Minimum range value (in the models AC1-2WA… only)
RLO
RHI
RLO takes the minimum value measured by the transmitter (i.e. the value matching 0V).
Maximum temperature recorded
Minimum temperature recorded
Keypad state lock
RLO...99.9 Maximum range value (in the models AC1-2WA… only)
RHI takes the maximum value measured by the transmitter (i.e. the value matching 1V)
0...19.9°
Proportional bandwidth.
Overshoot
Access to menu and information displayed.
■ Press and immediately release button
Steady-state error
-12.5...12.5° Probe T1 offset.
OS1
TLD
SIM
.
Temperature control takes place by changing the
ON time of the output: the closer the temperature
to the setpoint, the less time of activation. A small
proportional band increases the promptness of
response of the system to temperature variations,
but tends to make it less stable.
proportional control stabilises the temperature
within the proportional band but does not cancel
the deviation from setpoint.
1SP
■ With button
or
select the data to be displayed.
1...30min
0...100
Delay for minimum temperature (TLO) and maximum temperature (THI) logging.
Display slowdown
■ Press button
to display value.
■ To exit from the menu, press button
Reset of THI, TLO recordings
or wait for 10 seconds.
1PB
Process
1...255
AC1-2W address for PC communication
ADR
■ With button
■ Display the value with button
■ While keeping button pressed, use button
CHANNEL 1 SETPOINT (display and modification of desired temperature value)
■ Press and release button : the LED L1 blinks, the display shows 1SP for 1 second and then the setpoint associated value.
■ Press buttons or to set the desired value (adjustment is within the minimum SPL and maximum SPH limit).
■ To store the new value press button , or wait for 10 seconds.
or
select the data to be reset.
A
purely
temperature
.
.
INPUT SPECIFICATIONS
Time
With 1PB=0 the output is always off.
RANGE [MEASUREMENT ACCURACY]
Overshoot
0...999s
Integral action time.
MODEL
INPUT
1IT
SCL=1°C
SCL=2°C
SCL=°F
---
■ To go back to normal mode without saving the new value, press
.
The steady-state error is cancelled by inserting an
integral action. The integral action time, determines
the speed with which the steady-state temperature
is achieved, but a high speed (1IT low) may be the
cause of overshoot and instability in the response.
With 1IT=0 the integral control is disabled.
1SP
AC1-2WA..
0÷1V
RLO÷RHI [< ± 3mV]
CHANNEL 2 SETPOINT
■ With the auxiliary output set as thermostat control (OAU=THR), it’s possible to modify setpoint 2 during the normal operation
PTC 1000 Ω -50/-19.9 ÷ 99.9/150°C
(LAE ST1..) [<±0.3°C(-30÷130°),±1°C] [<±0.3°C(-30÷130°), ±1°C] [< ±0.6°F(-20÷260°),±2°F]
-50 ÷ 150°C
-60 ÷ 300°F
INP=ST1
INP=SN4
of the controller.
■ Press and release button
1PBx1AR%
integral control
action area
1PB
: the LED L2 blinks, the display shows 2SP for 1 second if setpoint 2 is an absolute threshold
(2SM=ABS), alternatively the display shows 2DF, if setpoint 2 is a threshold relative to setpoint 1 (2SM=REL), then the value
AC1-2WT...
Process
NTC 10K Ω -40/-19.9 ÷ 99.9/125°C -40 ÷ 125°C -40 ÷ 260°F
(LAE SN4..) [<±0.3°C(-40÷100°),±1°C] [<±0.3°C(-40÷100°),±1°C] [<±0.6°F(-40÷210°), ±2°F]
temperature
associated to the parameter appears.
■ Press buttons
■ To store the new value press button
■ To go back to normal mode without saving the new value, press
or
to set the desired value.
or wait for 10 seconds.
Time
WIRING DIAGRAMS
0...999s
Derivative action time.
1DT
Overshoot
.
1SP
STAND-BY
Response overshoot may be reduced by inserting
a derivative Action. A high derivative action (1DT
high) makes the system very sensitive to small
temperature variations and causes instability. With
1DT=0 the derivative control is disabled.
V
RS485
TTL
Button , when pressed for 3 seconds, allows the controller to be put on a standby or output control to be resumed (with SB=YES only).
rH
1PB
KEYPAD LOCK
data I/O
3
4
data I/O
3
4
5
Process
temperature
The keypad lock avoids undesired, potentially dangerous operations, which might be attempted when the controllers is operating
in a public place. In the INFO menu, set parameter LOC=YES to inhibit all functions of the buttons. To resume normal operation
of keypad, adjust setting so that LOC=NO.
VIN V- V+
OUT1
8(3)A
OUT2
8(3)A
OUT1
OUT2
8(3)A
8(3)A
Time
CONTROLLER AUTOTUNING IN PID MODE
Before starting
8
9
10
6
7
0...100%
Reset of integral action time referred to 1PB
8
9
10
6
7
1AR
1CT
In the setup mode (see configuration parameters): set 1CM=PID; make sure that 1CH matches the desired operation mode
(1CH=REF for refrigerating control, 1CH=HEA for heating control); then adjust setpoint 1SP at the desired value.
Start autotuning
Decreasing the parameter 1AR reduces the integral control action zone, and consequently the
overshoot (see figure on paragraph 1IT).
1...255s
Cycle time.
During normal operation, keep buttons
time in order to define the dynamic of the process to be controlled. To abort the autotuning function, press ; to start autotuning
press or wait for 30 seconds.
+
pressed for 3 seconds. 1CT blinks on the display. With
+
or
set the cycle
It’s the period in which the output ON time changes. The quicker the system to be controlled
reacts to temperature variations, the smaller the cycle time must be, in order to obtain higher
temperature stability and less sensitivity to load variations.
+
230V~
230V~
AC1-2WTQ2RE-B
AC1-2WAQ2RE-A
During autotuning
During the entire autotuning phase, the display alternates TUN with the actual temperature measured. In case of power failure,
when power is resumed, after the initial autotest phase, the controller resumes the autotuning function. To abort the autotuning,
ON/OFF
Output state in case of probe failure.
1PF
OAU
NON;
THR;
AL0;
AL1
AUX output operation.
without modifying the previous control parameters, keep button
pressed for 3 seconds. After the autotuning has taken place
NON : output disabled (always off). (the next parameter will be ATM)
THR : output programmed for second thermostat control (the next parameter will be 2SM).
AL0 : contacts open when an alarm condition occurs (the next parameter will be ATM).
AL1 : contacts make when an alarm condition occurs (the next parameter will be ATM).
successfully, the controller updates the control parameters and start to control.
Errors
If the autotuning function failed, the display shows an error code:
■ E1 timeout1 error: the controller could not bring the temperature within the proportional band. Increase 1SP in case of heating
control, vice versa, decrease 1SP in case of refrigerating control and re-start the process.
■ E2 timeout2 error: the autotuning has not ended within the maximum time allowed (1000 cycle times). Re-start the autotuning
process and set a longer cycle time 1CT.
■ E3 temperature overrange: check that the error was not caused by a probe malfunction, then decrease 1SP in case of heating
control, vice versa increase 1SP in case of refrigerating control and then re-start the process.
ABS;
REL
Setpoint 2 mode.
2SM
2SP
Channel 2 setpoint may be absolute (2SM=ABS), or a differential relative to setpoint 1 (2SM=REL)
SPL...SPH Auxiliary output switchover temperature (the next parameter will be 2CH)
ON
ON
■ To eliminate the error indication and return to the normal mode, press button
Control improvement
.
■ To reduce overshoot, reduce the integral action reset 1AR
OFF
OFF
■ To increase the response speed of the system, reduce the proportional band 1PB. Caution: doing this makes the system less stable.
■ To reduce swings in steady-state temperature, increase the integral action time 1IT; system stability is thus increased, although
its response speed is decreased.
■ To increase the speed of response to the variations in temperature, increase the derivative action time 1DT. Caution: a high
value makes the system sensitive to small variations and it may be a source of instability.
2SP 2SP+2HY T[°]
ON/OFF control in refrigeration
2SP-2HY 2SP
ON/OFF control in heating
(2SM=ABS, 2CH=HEA)
T[°]
(2SM=ABS, 2CH=REF)
-19.9...19.9° Temperature differential relative to 1SP. The auxiliary output setpoint is equal to 1SP+2DF
2DF
VIA PADOVA, 25
RECALIBRATION
ON
31046 ODERZO /TV /ITALY
TEL. +39 - 0422 815320
FAX +39 - 0422 814073
ON
■ Have a precision reference thermometer or a calibrator to hand. Ensure that OS1=0 and SIM=0.
■ Switch the controller off then on again.
OFF
OFF
■ During the auto-test phase, press buttons
■ With buttons and select 0AD or SAD: 0AD allows a calibration of 0, inserting a constant correction over the whole scale
of measurement. SAD allows a calibration of the top part of the measurement scale with a proportional correction between the
+
and keep them pressed till the controller shows 0AD.
1SP+2DF-2HY
T[°]
1SP+2DF+2HY T[°]
2DF<0
1SP+2DF
2DF>0
E-mail: sales@lae-electronic.com
1SP
1SP+2DF
1SP
calibration point and 0.
ON/OFF control in refrigeration. Setpoint 2
relative to setpoint 1 (OAU=THR, 2CH=REF)
ON/OFF control in heating. Setpoint 2
relative to setpoint 1 (OAU=THR, 2CH=HEA)
■ Press
to display the value and then use
+
or
to make the read value coincide with the value measured by the
| General | Details |
|---|---|
| Name | LAE AC1-2W Digital Thermostat Instruction Manual |
| Make | LAE |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.43 MB |

lae AC2-2 Two Stage Thermostat Instructions

LAE AC1-2W Digital Thermostat Instruction Manual Overview
Summary of Contents
- Page 1: Thank you for having chosen a LAE electronic product. Before installing the instrument, please read these instructions carefully to ensure maximum performance and safety. Refrigerating control (REF) or heating control mode (HEA) for the auxiliary output. To get access to the parameter configuration menu, press button + for 5 seconds. With button or select the parameter to be modified. Channel 1 output and Channel 2 output specifications. Temperature alarm with relative thresholds, refrigerating control (ATM=REL, 1CH=REF). Temperature alarm with relative thresholds, heating control (ATM=REL, 1CH=HEA). Operating conditions: -10 … +50°C; 15%...80% r.H. The keypad lock avoids undesired, potentially dangerous operations. Controller in stand-by and controller in autotuning indications. Errors during autotuning include timeout errors and temperature overrange.
- Page 2: istruzioni d'uso Prima di procedere all’installazione dello strumento, leggete attentamente il presente foglio d’istruzioni: solo così potrete ottenere massime prestazioni e sicurezza. modo di regolazione refrigerazione (REF) o riscaldamento (HEA) per l’uscita ausiliaria differenziale del termostato. Con 2HY=0 l’uscita ausiliaria rimane sempre spenta. per accedere al menù di configurazione dei parametri, premere per 5 secondi i tasti +. dopo uno spegnimento, l’uscita 2 rimane disattivata per 2T0 minuti indipendentemente dal valore della temperatura. uscita canale 1 uscita canale 2 gestione soglie allarme. attenzione: cambiando il valore di SCL vanno assolutamente riconfigurati i parametri riguardanti le temperature assolute e relative. il blocco dei tasti impedisce operazioni indesiderate, potenzialmente dannose, che possono avvenire qualora il regolatore operi in ambiente pubblico.