Honeywell TH8732WFH5004 Round Smart Thermostat User Guide
ISU # Description
Setting
Setup options
1
4160
4220
8100
Minimum setpoint
50°F to 99°F
From the Contractor Menu, highlight Set Up and press OK.
(Note: Setting applies 10.0°C to 37.0°C
to both heat and cool
setpoints)
2
Press s or t to highlight the setting and press OK. Continue until
all settings have been configured.
Maximum setpoint
40°F to 90°F
3
When all settings are configured, you will be prompted to save
changes. Highlight Yes and press OK to save and exit. To exit setup
early by pressing t to highlight EXIT and press OK.
(Note: Setting applies 4.5°C to 32.0°C
to both heat and cool
setpoints)
Humidifier type
0 = None
1 = Steam
2 = Bypass or fan powered
ISU # Description
Setting
1160
Temperature
indication scale
0 = Fahrenheit
1 = Celsius
8120
8140
Humidification -
window protection
0 = Off
1 = On
2120
2140
Heating system type
1 = Conventional forced air heat
2 = Heat pump
3 = Radiant heat
Humidification
control
0 = Humidify only when heat is On
1 = Humidify only when fan is On
2 = Humidify on demand: Thermostat
controls fan
5 = None (cool only)
Heating equipment
type
Conventional Forced Air Heat:
1 = Standard efficiency gas forced air
2 = High efficiency gas forced air
3 = Oil forced air
3 = Humidify on demand: Humidifier controls
fan
9100
Dehumidification
equipment
0 = None
4 = Electric forced air
5 = Hot water fan coil
1 = A/C with low speed fan
2 = A/C with high speed fan
4 = Whole house dehumidifier
Heat Pump:
7 = Air to air heat pump
8 = Geothermal heat pump
9140
9160
9180
Dehumidification
equipment setup
0 = Normally open
1 = Normally closed
Radiant Heat:
9 = Hot water radiant heat
12 = Steam
Dehumidification -
overcooling limit
0, 1, 2, 3°F
0.0, 0.5, 1.0, 1.5°C
Dehumidifier fan
control
0 = Thermostat controls fan
1 = Equipment controls fan
2160
2180
2200
2220
Reversing valve O/B
0 = O (O/B on cool)
1 = B (O/B on heat)
10100 Ventilation type
0 = None
1 = ERV / HRV
Cool stages /
compressor stages
0, 1, 2
2 = Passive (fan only)
3 = Fresh air damper
Heat stages /
backup heat stages
Heat stages: 0, 1, 2
Backup heat stages: 0, 1
10160 Ventilation fan
control
0 = Thermostat controls fan
1 = Equipment controls fan
Fan operation in heat 0 = No fan
1 = Equipment controls fan
2 = Thermostat controls fan
10240 Ventilation percent
on time
10% to 100% (in 10% increments)
2240
2260
Backup heat type
31 = Electric forced air
32 = Gas/Oil Forced air (or Fossil forced air)
10280 Ventilation low
temperature lockout
Off
-20°F to 40°F (in 5°F increments)
-29.0°C to 4.5°C (in 2.5°C or 3.0°C
increments)
External Fossil Fuel
Kit
0 = Thermostat controls backup heat
1 = External Fossil Fuel Kit controls backup
heat
10300 Ventilation high
temperature lockout
Off
3120
Staging control
- backup heat
differential
Comfort
2.0°F to 15.0°F from setpoint (in 0.5°F
increments)
80°F to 110°F (in 5°F increments)
26.5°C to 43.5°C (in 2.5°C or 3.0°C
increments)
1.0°C to 7.5°C from setpoint (in 0.25°C
increments)
10320 Ventilation high dew
point lockout
Off
65°F to 85°F (in 5°F increments)
18.5°C to 29.5°C (in 2.5°C or 3.0°C
increments)
3140
3160
Backup heat upstage Off
timer 30, 45, 60, 75, 90 minutes
2, 3, 4, 5, 6, 8, 10, 12, 14, 16 hours
11100 Home heat setpoint
11120 Home cool setpoint
40°F to 90°F
4.5°C to 32.0°C (in 0.5°C increments)
Compressor lockout / Off
balance point
5°F to 60°F (in 5°F increments)
-15.0°C to 15.5°C (in 2.5°C or 3.0°C
increments)
50°F to 99°F
10.0°C to 37.0°C (in 0.5°C increments)
11140 Setpoint for away
mode
0 = Away setpoints
1 = Smart temperature setpoints
3180
Backup heat lockout
Off
5°F to 65°F (in 5°F increments)
-15.0°C to 18.5°C (in 2.5°C or 3.0°C
increments)
11160 Away heat setpoint
40°F to 90°F
4.5°C to 32.0°C (in 0.5°C increments)
3200
3220
Cool cycles per hour
1 - 6
11180 Away cool setpoint
50°F to 99°F
10.0°C to 37.0°F (in 0.5°C increments)
Cool cycles per hour
- stage 2
1 - 6
14020 Temperature display
offset
-3°F to 3°F
3240
3260
Heat cycles per hour
1 - 12
14025 Humidity % offset
-12% RH to 12% RH
Heat cycles per hour
- stage 2
1 - 12
3280
4120
Backup heat cycles
per hour
1 - 12
Adaptive intelligent
recovery
0 = No
1 = Yes
3
| General | Details |
|---|---|
| Name | Honeywell TH8732WFH5004 Round Smart Thermostat User Guide |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.36 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell D1-528 Direct Thermostat Installation Guide

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide