Home > Honeywell > Honeywell RCHT8610WF T5 Plus Smart Thermostat Installation Guide

Honeywell RCHT8610WF T5 Plus Smart Thermostat Installation Guide

Equipment Setup Options  
Note: ISU options available may vary upon the thermostat model and equipment setup.  
# ISU ISU Name  
ISU Options (defaults in bold)  
Notes  
120  
Schedule Type  
No Schedule  
You can change default MO-FR, SA-SU schedule here. To edit periods during days, tempera-  
ture setpoints, or to turn Schedule On/Off, from the home screen, go to MENU/SCHEDULE.  
MO-SU = Every day the same  
MO-FR, SA, SU = 5-1-1 schedule  
MO-FR, SA-SU = 5-2 schedule  
Each Day = Every day individual  
125  
130  
Temp Scale  
Fahrenheit, Celsius  
Outdoor Temp  
No, Internet  
Select outdoor temperature data source. This ISU automatically defaults to Internet when  
registered to the Resideo app. An outdoor temperature is required to set the following ISUs: ISU  
355 Compressor Lockout, ISU 356 Aux Heat Lockout.  
200  
205  
System Type  
Conventional Forced Air  
Heat Pump  
Boiler  
Basic selection of system your thermostat will control.  
Cool Only  
Equipment Type Conventional Forced Air Heat:  
Standard Gas (STD GAS), High Efficiency Gas  
(EFF GAS), Oil, Electric, Fan Coil*  
This option selects the equipment type your thermostat will control. Note: This option is NOT  
displayed if ISU 200 is set to Cool Only.  
* Fan coil setting is for a residential application with a hot water coil in an air-handler.  
Heat Pump:  
Air To Air, Geothermal  
Boiler:  
Hot Water, Steam  
218  
220  
Reversing Valve  
0/B on Cool, 0/B on Heat  
This ISU is only displayed if ISU 200 is set to Heat Pump. Select whether reversing valve O/B  
should energize on cool or on heat  
Cool Stages  
(#200=Conv./  
200=HP)  
0, 1, 2  
221  
Heat Stages/  
Aux/E Stages  
(#200=Conv./  
200=HP)  
Heat Stages: 0, 1, 2  
AUX/E Stages: 0, 1  
Maximum of 2 Heat Stages for conventional systems. Maximum of 1 Aux/E stages for heat  
pump systems.  
230  
300  
Fan Control  
Equipment, Thermostat  
This ISU is only displayed if ISU 205 is set to Electric Forced Air or Fan Coil.  
Auto Changeover On, Off  
OFF: The user must select heating or cooling as needed to maintain the desired  
indoor temperature.  
ON (Automatic): On (enabled) Allows user to select Auto Changeover as one of the system  
modes from the home screen. In auto mode, the thermostat can control either heating or cool-  
ing to maintain the desired indoor temperature.  
303  
Auto Differential 0 °F to 5 °F or 0.0 °C to 2.5 °C  
Differential is the minimum number of degrees rise or fall required during off cycle to switch  
from the last active mode (heat or cool) to the opposite mode when the thermostat is in  
auto-changeover. Differential is NOT deadband. The deadband temperature between when  
heating (or cooling) cycles on and cycles off to maintain setpoint is not adjustable. The T5  
thermostat uses an algorithm that fixes deadband at 0 °F.  
355  
356  
365  
Balance Point  
(Compressor  
Lockout)  
Off, 5 °F to 60 °F (in 5 °F increments) or -15.0 °C Compressor Lockout requires an outdoor temperature. Set Compressor Lockout to the  
to 15.5 °C (in 2.5 °C or 3.0 °C increments)  
temperature below which it is inefficient to run the heat pump. When outside temperature is  
below this setting, thermostat will lockout heat pump and run Aux Heat only. This ISU is only  
displayed if ISU 130 = Internet, ISU 200 is set to Heat Pump, ISU 221 Aux/E stages = 1,.  
Aux Heat Lock  
Out (Aux Heat  
Outdoor Lockout) ments)  
Off, 5 °F to 65 °F (in 5 °F increments) or  
-15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C incre-  
Aux Heat Lockout requires an outdoor temperature. Set Aux Heat Lockout to optimize energy  
bills and to not allow it to run the more expensive Aux Heat source above certain outdoor tem-  
perature limit. This ISU is only displayed if ISU 200 is set to Heat Pump, AND if ISU 221 Aux/E  
stages = 1.  
Cool 1 CPH  
(Cooling cycle  
rate stage 1)  
1 - 6 CPH (3 CPH)  
This ISU is only displayed when Cool /Compressor Stages is set to 1 or more stages. Cycle rate  
limits the maximum number of times the system can cycle in a 1 hour period measured at a  
50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is 3  
times per hour (10 minutes on, 10 minutes off). The system cycles less often when load condi-  
tions are less than or greater than a 50% load.  
366  
Cool 2 CPH  
(Cooling cycle  
rate stage 2)  
1 - 6 CPH (3 CPH)  
This ISU is only displayed when Cool /Compressor Stages is set to 2.  
6
GeneralDetails
NameHoneywell RCHT8610WF T5 Plus Smart Thermostat Installation Guide
MakeHoneywell
LanguageEnglish
FiletypePDF (Download)
File size0.66 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TL116A Thermostat Installation Guide
Honeywell TL116A Thermostat Installation Guide
T10 Pro Smart Thermostat with Redlink Room Sensor
T10 Pro Smart Thermostat with Redlink Room Sensor
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide
Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide

Honeywell RCHT8610WF T5 Plus Smart Thermostat Installation Guide