GLOBAL Touch Screen Thermostat HY08AC User Manual
Valve Control temperature 1℃,open motorized valve;when room temperature reach
setting temperature,close motorized valve,fan coil continues to work(it can
be set as fan close together with valve in advanced setting).
2:Cancel Children Lock
A3
A4
Setting Temperature Lowest Limit
1-25℃
5℃
35℃
Setting Temperature Highest Limit 30-70℃
Ventilation mode(fan coil unit is not under controlling)
0=Fan Under Control
A5
Fan Coil Units Control
0
0
Fan coil unit is under controlling,it is valve and fan coil unit close together.
1=Fan Isn’t Under Control
0=Timing Turn On/Off For
One Time
Key Lock function:if thermostat opens key lock function,no any operation
Key Lock
Function
after 10 minutes will lock keys automatically(screen display “
”
A6
Timing Turn On/Off Running Way
icon),press
“
” for 5 seconds will unlock(“ ” disappears)
1=Timing Turn On/Off For
Cycle Running
00:S1 Connect S2 Means
Put-in Card Status;
01:S1 Disconnect S2 Means
Pull-out Card Status.
Enter into energy saving mode by door card.When pull out door card,
Door Key
Energy Saving
Mode
“
”door card icon flashing,if thermostat is in cooling mode,temperature
set as 26℃ automatically,fan run in low speed;if thermostat is in heating
mode,temperature set as 18℃ automatically,fan run in low speed
A7
A8
Key Card Status
00
(HY08AC-K)
Sensor occurs fault,thermostat close fan coil and motorized valve and
display“ ” and“E1”and“E2”.
After Door Card Pull Out To Cool
Temperature
After Door Card Pull Out To Heat
Temperature
Valve Output Choose
Return To Factory Default Setting
Setting Range 22 ~32 ℃
26℃
Alarm
E1:sensor short circuit alarm
E2:sensor open circuit alarm
When temperature higher than 55℃ displays “HI”when temperature lower
than 0℃ displays“LO”
A9
AA
Setting Range 10~21℃
18℃
2: 2Pipes
4:4 Pipes
4
Programmable Mode Setting And Working
Display A o,Long Press Fan
Key To Return To Factory
Default Setting
HY08AC fan coil units thermostat can set different time different temperature;there is
AB
“
”(manual programmable) and “ ”(cancel programmable) 2 programs can be chosen.
Manual Programmable
Long press “ ”for 3-5 seconds to enter into setting screen,,short press " ”to choose “
and press “ ”to confirm and enter into manual programmable setting.
Wiring Diagram
”
After enter into manual programmable,To begin with the first period(“ ” flashing) of
Monday,press “ ” to confirm,starting time(default 6:00),it can press“ ”or“ ”to adjust by
yourself,press every one time to increase or decrease 30 minutes and then press “ ”,press
“
”or“ ” to adjust temperature,press “ ” enter into the second period “ ” setting,the
same as above to finish 4 periods setting,then enter into Tuesday setting,the same setting
method as Monday,then finish 7 days setting,no any operation for 5 seconds will save and
exit automatically.
Cancel programmable:long press “ ”for 3-5 seconds to enter into setting screen,short press
“
” to choose “ ”programmable,press “ ”to confirm and to cancel programmable mode
Cautions on Installation and Use
back to upper setting screen.Press “ ”to choose next setting or waiting for 5 seconds to exit
Default Setting
1. To prevent the thermostat display from a high fluctuation, special treatment has been made
to the program. Therefore, it is normal that the thermostat cannot immediately display the
sudden change of temperature.
Period
Period Setting
Default Time
Default Temperature
2. The thermostat installed on 1.5m above the ground.
1
2
3
4
06:00
8:00
17:30
22:00
23
26
26
23
3. For the thermostat installed,please take care not to install it to the wall corner, door /
window side or behind the door or in such unheated area as exterior wall. Avoid hot / cold
air duct, radiator, flue or thermal pipe.
Monday
To
Sunday
4. If you have any problem for the installed ,please contact our company hysen, we will make
a demonstration for you
5. Only the professional technicians are permitted to open the transmitting and receiving box
of the thermostat for installation. When install the power supply, make sure that the power
cable is well insulated.
Advanced Setting
In turn off state,long press “ ” for 5 seconds to enter into advanced setting.Press“ ”or“ ”to
set,short press “ ”to next option and press“ ”or“ ”to set
6. The thermostat is unrepairable product. The user shall not open the internal circuit board.
7. HY08AC series thermostat design for the standard 75x75x 35mm wall mount box installed.
Follow the instructions to open the rear cover base, mount it on the wall and wire it.
8. Before installing the thermostat, make sure that the system is disconnected. The maximum
voltage of the system shall meet the requirements specified in the Instruction Manual (Max.
AC Voltage: 250V).
Display
Sign
Factory
Default
Setting Options
Data Setting Function
-9-+9℃
0.5℃
(Display room temperature,
A1
A2
Measure Temperature Calibration
Accuracy
Press
,
to calibrate room
Calibration
temperature)
Warranty:
0:Half Lock;(can turn on/off
and adjust temperature)
1:Full Lock
We offer the warranty of 18 months, from the sales day. The products of our company can have
lifetime warranty ,if it is not the quality problems, or beyond the warranty period, we will charge
for the after-sale service.
Children Lock Setting
0
| General | Details |
|---|---|
| Name | GLOBAL Touch Screen Thermostat HY08AC User Manual |
| Make | GLOBAL |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.19 MB |

GLOBAL WIFI Digital Heating Thermostat User Manual

GLOBAL WiFi Heating Thermostat User Manual

GLOBAL HY09RF WIFI Wireless Thermostat User Manual

GLOBAL CEG Series Convector with Thermostat Instruction Manual

GLOBAL Digital Heating Thermostat User Manual

GLOBAL HY06RF-BW/WW/WE Thermostat User Manual