Daintree Networked Wireless Thermostat (WTS10)
Installation Guide
Joining the Zigbee Network
5
Specifications
After successfully completing the Installation Test the WTS10
is ready to communicate with the Daintree Wireless Area
Controller (WAC) and be commissioned and configured using
the ControlScope Manager (CSM) web-based application. The
thermostat automatically tries to join the WAC network every
5 minutes. The WAC must be commissioned and Add New
Devices must be initiated on the WAC before the thermostat
can join the ZigBee wireless network.
Power Supply
Output
24VAC, 50Hz
3A max, 1A each terminal
Operating
Environment
32°F to 113°F (0°C – 45°C). Indoor use only
Compliance
ETL listed, FCC ID: D12CT-EM2606, IC ID:
1700A-CT-EM2606
For information about configuring the thermostat using
CSM, see the on-line help.
Radio
Properties
2405 ~ 2475MHz
Transmit Power max 10dbm
Once the thermostat is joined, it ignores its built in schedules.
The WAC passes configuration information like set point, heat/
cooling mode, lock levels etc. at the start of each CSM schedule.
If the thermostat loses communication with the WAC the
following things will happen: (1) Thermostat continues to use
the existing configuration set by the WAC. (2) Keypad automatically
unlocks after 30 minutes to allow manual changes. (3) If remote
temperature sensor(s) are enabled, and the thermostat does not
receive a remote temperature report within 15 minutes, it will
switch to its built-in temperature sensor.
Fahrenheit or Celsius
Display range: 14°F – 99°F (5°C – 37°C)
Display resolution: 1°F (1°C)
Setting range: 45°F – 90°F (7.0°C – 32.0°C)
Setting resolution: 1°F (0.5°C)
Accuracy: +/- 1°F @ 75°F
Temperature
Measurements
Switching differential 1st stage:
User selectable
• 0.5°F (default), 1.0°F, 2.0°F
(0.25°C, 0.5°C, 1.0°C)
Current Certification
Switching differential 2nd stage:
Fixed 2°F (1°C)
32°F to +113°F (0°C – 45°C)
Operating Environment
Indoor Use Only
Switching differential 3rd stage:
Fixed 2°F (1°C)
2405 ~ 2475MHz
Radio Properties
Control
Transmit Power max 10dbm
Operational differential: Less than +/- 2°F
Control timing:
Radio Equipment Directive
2014/53/EU
Compliance
• Compressor short cycle timer – 5 min
Residual cooling fan delay:
User selectable
Power Supply
24VAC, 50Hz
• 0 (disabled), 30, 60, 90 sec
• Default = 60 sec
Current declares that the radio equipment type (WTS10)
complies with Directive 2014/53/EU
Control Switches:
• Latching relay, 2A max load per relay
Relays:
Max. radiated power: <10 dBm. Frequency: 2405 - 2475 MHz
• 1st stage/Aux heating control
• 2nd stage/Emergency heating control
• Fan Control
• Heating/Cooling O/B control, 3rd stage
conventional heat control
• 1st stage cooling control / 1st stage
heat-pump heating control
• 2nd stage cooling control / 2nd stage
heat-pump heating control
WTS10
Switching
Circuit
CAUTION
RISK OF EXPOSURE IF BATTERY IS REPLACED BY AN
INCORRECT TYPE. DISPOSAL OF USED BATTERIES
ACCORDING TO THE INSTRUCTIONS.
These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation
or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be
referred to GE Current, a Daintree company.
© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the
General Electric Company and are used under license. Information provided is subject to change without notice.
All values are design or typical values when measured under laboratory conditions.
DT103 (Rev. 05/25/2021