Home > GE current > GE current WTS10 Daintree Wireless Thermostat Installation Guide
GE current WTS10 Daintree Wireless Thermostat Installation Guide
®
Daintree Networked Wireless Thermostat (WTS10)
Installation Guide
Testing Continued
3
Test for Heat Pump Systems Continued
Test for Conventional System
5. Press the (DOWN) button to highlight the setting for
1. Press and hold down the (LEFT) button, then momentarily
press Reset pinhole. The screen will go blank. When you see
INSTALLATION MODE release (LEFT) button. All the outputs
are turned off.
“COOL: Stage1”. Press the + button to toggle the COOL stage 1
output (ON/OFF). For a 2-Stage cooling system, press the
(DOWN) button to highlight “Stage 2”. Press the + button to
toggle the COOL stage 2 output (ON/OFF).
2. “HVAC: ELEC Heat/Cool” indicates SW1 is set for Electric
Conventional System. “HVAC: GAS Heat/Cool” indicates SW1
is set for Gas Conventional System. If the display is incorrect,
please review the SW1 switch positions.
6. Press the (DOWN) button to go to the HEAT test. All cool
outputs will be turned off, and the fan output will keep it’s
current status. HEAT: “Stage 1” is highlighted. Press the +
button to toggle the HEAT stage 1 output (ON/OFF). For a 2 or
3-Stage heat system, press the (DOWN) button to highlight
“Stage 2” Press the + button to toggle the HEAT stage 2
output (ON/OFF). For a 3-Stage heat system, press the
(DOWN) button to highlight “AUX”. Press the + button to
toggle the Auxiliary Heating output (ON/OFF). Press the
(DOWN) button to highlight the “EMER” setting. Press the +
button to toggle the EMERGENCY output (ON/OFF).
3. “FAN” is highlighted. Press the + button to toggle the FAN
output (ON/OFF). After testing the FAN output, it is best to
keep the FAN output ON to test other outputs.
4. Press the (DOWN) button to highlight COOL: “Stage 1”.
Press the + button to toggle the COOL stage 1 output
(ON/OFF).
5. Press the (DOWN) button to highlight “Stage 2”. Press +
7. Press the Reset pinhole to stop the INSTALLATION MODE.
button to toggle the COOL stage 2 output (ON/OFF).
6. Press the (DOWN) button to go to the HEAT test. All cool
outputs are turned off; the fan output will be turned off
for a GAS System, and the fan output will keep current status
for an Electric System.
LED Operation
4
The WTS10 has two LEDs above the display. Upon power-up the
LEDs cycle on and off briefly as the thermostat goes through its
start-up routine. After the start-up routine is complete, the LEDs
operate as described in the tables below.
7. HEAT: “Stage 1” is highlighted, press the + button to toggle
the HEAT stage 1 output (ON/OFF).
8. Press the (DOWN) button to highlight “Stage 2”. Press the +
Left
button to toggle the HEAT stage 2 output (ON/OFF).
(orange) LED
Description
9. Press the (DOWN) button to highlight “Stage 3”. Press the +
Not Lit
Normal operation.
button to toggle the HEAT stage 3 output (ON/OFF).
Orange, flashing
Boot loader reprogramming MCU after
OTA firmware update performed successfully.
10. Press the Reset pinhole to stop the INSTALLATION MODE.
Right
(multicolor) LED
Test for Heat Pump Systems
Description
1. Hold the (LEFT) button, then momentarily press Reset pinhole.
The screen will go blank. When you see INSTALLATION MODE
release the (LEFT) button. All the outputs are turned off.
Not Lit
Normal operation while joined to
ZigBee network.
Red, solid
Thermostat has not joined a ZigBee network.
Thermostat is scanning for a network to join.
2. “HVAC: Heat Pump <O>” indicates SW1 is set for cool
changeover valve O. “HVAC: Heat Pump <B>” indicates SW1 is
set for heat changeover valve B. If the display is incorrect,
please review the SW1 switch positions.
Green, flashing
Green, solid for
3 seconds
Thermostat has joined a ZigBee network.
3. The setting for “STAGE” is highlighted. Press the + button
to scroll through the selections: “1H1C or 2H/1C” and “2H2C or
3H2C.” When the desired STAGE selection is highlighted, press
the (DOWN) button to enter your selection and advance to
the FAN selection.
Amber, solid
HVAC system warning: 24VAC is detected
at thermostat’s L terminal.
Amber, flashing
Thermostat is responding to an “Identify”
command from DCS.
4. Press the + button to toggle the FAN output (ON/OFF).
Keep the FAN output ON while testing the other outputs.