Product marking  
0539  
Technical data  
Type  
Range  
[°C]  
Max. permissible bulb temperature  
[°C]  
0843  
II 2G  
RT 9E  
-45 – -15  
-5 – 30  
150  
150  
300  
215  
300  
Ex ia IIC T6...T1 Gb -20 °C Ta 65 °C  
DEMKO 14 ATEX 1406X  
RT 14E  
RT 101E  
RT 107E  
RT 123E  
IECEx ULD 14.0013X  
UL21UKEX2021X  
Ci = 0.5 nF li = 0.5 A Li = 0.2 uH Pi = 1 W Ui = 29 V  
25 – 90  
70 – 150  
150 – 250  
Temperature  
class  
Process temperature  
limit [°C]  
Permissible ambient temperature -20 – 65 °C  
i
U = 29 V  
li = 0.5 A  
Pi = 1 W  
Ci = 0.5 nF  
Li = 0.2 μH  
T1  
T2  
T3  
T4  
T5  
T6  
300  
289  
194  
129  
94  
Intrinsically safe specification  
max. 100 mA, 30 V AC / DC  
min. 1 mA, 5 V AC / DC  
79  
Contact load  
Must be used with a certified Ex ia barrier satisfying the  
input parameters.  
Installation  
A set of Pg13.5 cable gland is attached to the RT in a separate bag. To  
ensure IP66 (units with automatic reset) or IP54 (units with external  
reset) grade of RT enclosure it is necessary to assemble this gland  
as shown in the fig. 2. If this gland is not used with a cable, a metal  
blinding should be also assembled.  
RT units can be fitted in any position. Use the mounting holes (25). With  
outdoor installation, the unit should be protected against rainfall. The  
bulb should be fixed to the wall by means of a bulb holding bracket  
(26). If it is desired to install the bulb in a water or brine tank, this can be  
done by using either a capillary stuffing box (31) or a bulb pocket (30).  
If bulb pocket is to be used, for correct bulb fitting see fig. 4.  
Safety requirements  
1. The refrigeration system must always comply with European Ex  
installation standard, EN 60079-14, any local directive and legislation  
as well as any other regulation applying in the area of installation.  
2. RT-E temperature control must be used only with reliable means of  
limiting the voltage and current to prevent sparks between the  
contact surfaces. The equipment to be used for electrical load  
limiting must be certified for gas group IIC. Also RT-E thermostat  
must be installed as a part of IIC electrical installation.  
3. Cable and cable entries approved for the application must be used.  
Cables must not be in contact with sharp edges. The cable must be  
connected with adequate stress relief in order to prevent that  
pulling forces can be carried through the cable to the terminal.  
4. The cycle frequency of the RT-E switch must be kept as low as  
possible to prevent fatique failure on the bellows. The vibration  
level must be kept as low as possible.  
Electrical connection  
See fig. 5.  
START = make. STOP = break. DIFF. = differential.  
Cable diameter: 6 – 14 mm.  
The earth terminal (38) should be connected to earth.  
5. It is recommended to regularly check the function of the RT-E  
switch.  
Wire dimension: min. 0,75mm  
²
6. Only apparatus designed, constructed and released by Danfoss  
must be used for application concerned. Danfoss can accept no  
responsibility in case of alterations made on the thermostats or  
the use of them against the instructions of Danfoss.  
7. Any overload of the RT switch must be prevented. Overloaded or  
damaged apparatus must be exchanged.  
Adjustment  
Set the thermostat for minimum actuating temperature (range setting).  
Setting is done by rotating the knob (5), at the same time reading the  
main scale (9).  
The differential is set by rotating the differential adjusting nut (19)  
according to the nomogram concerned (fig. 3).  
Maximum actuating temperature is the sum of the temperature setting  
and the differential.  
8. Only authorised persons, who are certified in installing and  
maintaining refrigration system may do the installation, maintenance  
and exchange of the switch. Use only appropriate tools.  
9. Dispose of the switch in an environmentally-friendly way.  
10. RTE switches must be installed in area where is low risk of  
mechanical damage.  
11. Components within the equipment can exceed the enclosure tem-  
perature by 1K (1 °C). When the media temperature exceeds 80 °C, it  
is the responsibility of the user to ensure that the media temperature  
does not cause a thermal ignition risk on parts between the media  
and the switch enclosure. Maximum media temperature on  
temperature switch with 2m or longer capillary tube is 300 °C.  
12. Isolation of the intrinsically safe circuit to ground and to the contact  
mounting screw has been verified through 500 VACrms dielectric  
strength testing, carried out in accordance with IEC 60079-11:2011  
section 10.3.  
Example:  
An RT 123E is required to regulate the temperature in a drying oven.  
Max. temperature 188 °C, min. temperature 180 °C, differential  
188 °C - 180 °C = 8 °C.  
1. Set the thermostat on 180 °C with the knob (5).  
2. Set the differential adjusting nut (19) on number 3 which can be  
found by reading off the nomogram for the RT 123E in fig. 3.  
In general, turning the knob automatically moves both the maximum  
and minimum actuating temperatures (break and make) up or down  
because of the fixed differential. On the other hand, turning the  
differential adjusting nut only, alters the maximum actuating temperature.  
13. Surface of the front cover is sputtered with stainless steel - avoid  
abrasion.  
14. Power must be switched off before maintenance and opening the  
RT-E.  
2 | AN179486440929en-001201  
© Danfoss | Climate solutions | 2024.01  
GeneralDetails
NameDanfoss RT 9E Automatic Thermostat Installation Guide
MakeDanfoss
LanguageEnglish
FiletypePDF (Download)
File size0.42 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss RET-MD Electronic Intelligent Dial Setting Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide
Danfoss VICUQ24M Icon Programmable II Room Thermostat Installation Guide
Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide
Danfoss MBC 8000, MBC 8100 Heavy Duty Thermostat Installation Guide
Danfoss UT 72-UT 73 Universal Thermostat Installation Guide
Danfoss UT 72-UT 73 Universal Thermostat Installation Guide
Danfoss ECtemp 530 Electronic Thermostat Installation Guide
Danfoss ECtemp 530 Electronic Thermostat Installation Guide
Danfoss 014G0251 Eco Radiator Thermostat User Guide
Danfoss 014G0251 Eco Radiator Thermostat User Guide
Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide
Danfoss 014G0013 Z Wave Radiator Thermostat Installation Guide
Danfoss RET230P Electronic Thermostat Instruction Manual
Danfoss RET230P Electronic Thermostat Instruction Manual
Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide
Danfoss TP7000 Range Electronic 7 Day Programmable Room Thermostat Installation Guide
Danfoss RET1000 Series Electronic Thermostat User Guide
Danfoss RET1000 Series Electronic Thermostat User Guide

Danfoss RT 9E Automatic Thermostat Installation Guide