DAIKIN TRC-11 One Lite Connected Thermostat Instruction Manual
Installing Daikin One Lite Thermostat
. Maximum wire distance between the Daikin One Lite and the translation adaptor should not exceed
125 feet using four conductor 18-gauge field supplied wire.
. Seal the hole made for routing the wiring to the thermostat’s terminal subbase.
. Check for proper voltage before and after wiring is installed.
. 0.6VDC between Data 1 and 2.
. 24VAC between R and C.
. Line voltage 230VAC
Note: If wired incorrectly, you will receive an error.
. If power wires are reversed the PWR LED will flash green.
1
2
Data Line 1
Data Line 2
24 volt common
C
R
24 volt power
Aux to Aux C is a 24V AC Dry contact.