Home > 75F > 75F HyperStat All In one Commercial Thermostat User Manual

75F HyperStat All In one Commercial Thermostat User Manual

75F® HyperSta
MECHANICAL  
Dimensions  
6.5” x 4.5” x 1.18” (165.5mm x  
115mm x 30mm)  
(2) screws in drywall  
Mounting  
2.8” 240x320 pixel TFT LCD  
32°F to 122°F (0°C to 50°C)  
Screen  
Operating Range  
SENSORS  
ELECTRICAL  
Operating range between 32°F to  
122°F (0°C to 50°C); typical  
accuracy of +/- 1°F or 0.2°C  
Power  
24V AC/DC (+/-15%) with nominal  
power consumption 1.0W and  
maximum consumption of 2.5W  
Temperature  
Operating range between 20 to  
85% noncondensing; Typical  
accuracy of +/- 2% RH  
Humidity  
COMMUNICATIONS  
Bluetooth  
BLE4.1; used during commissioning  
Dedicated  
CO2 Sensor  
Range 0-40’000 ppm; Accuracy  
+/-30ppm over range of 400-  
10,000ppm and lifetime of 15  
years  
Mesh  
900 MHz IEEE 802.15.4-compliant;  
used for device communication on  
mesh network  
Ambient light sensor; high-accuracy  
UV index sensor; matches erythemal  
curve; < 100 mix resolution  
Light  
4 wire RS-485 interface  
3 wire connector for low-power  
sensor bus  
Wired  
40-120dB response for 100 Hz to  
10Khz  
Sound  
Passive Infra Red (PIR) with detection  
range of 4m with 30-degree angle  
Occupancy  
OPTIONAL SENSORS  
Detection range of  
PM2.5, PM10  
0-1000ug/m3 and accuracy of +/-  
10ug/m3 (PM2.5, 0-100 ug/m3) or  
+/- 25ug/m3 (PM10, 0-100ug/m3)  
WALL PLATE  
VOC  
TVOC: 0-60’000 ppb. Typical  
Accuracy - 15% of measured value  
Dimensions  
6.1” x 4.5” (154mm x 112mm)  
1800 121 4575 | enquiries@75f.io  
|
HyperStat_0624  
3
GeneralDetails
Name75F HyperStat All In one Commercial Thermostat User Manual
Make75F
LanguageEnglish
FiletypePDF (Download)
File size0.16 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

75F HyperStat All In one Commercial Thermostat User Manual