Home > Vive Comfort > VIVE COMFORT TP-N-721 Non Programmable Thermostat Instruction Manual

VIVE COMFORT TP-N-721 Non Programmable Thermostat Instruction Manual

Wiring (For professional technicians only)  
Wiring Diagrams (For professional technicians only)  
Power supply  
Caution:  
Electrical Hazard  
Warning:  
Use either O or B terminals for changeover valve.  
Optional 24 VAC common connection when thermostat is used in battery power mode.  
Factory-supplied jumper  
Failure to disconnect the power  
before beginning to install this  
product can cause electrical  
shock or equipment damage.  
All components of the  
control system and the  
thermostat installation must  
conform to Class II circuits  
per the NEC Code.  
2H/1C Heat Pump System - Factory Default Setting  
Wiring  
C
Note: In many systems  
with no emergency heat  
relay a jumper can be  
used between E and W2.  
L2  
L1(HOT)  
1.  
If you are replacing a thermostat,  
make note of the terminal  
Installation Tip  
R
R
COMPRESSOR  
RELAY  
connections on the thermostat  
that is being replaced. In some  
cases the wiring connections will  
not be color coded. For example,  
the green wire may not be  
Y
C
Do not overtighten terminal  
block screws, as this can  
damage the terminal block.  
A damaged terminal block  
can keep the thermostat  
from fitting on the subbase  
correctly or cause system  
operation issues.  
COOL CHANGE  
OVER VALVE  
W/E  
G
O
B
FAN RELAY  
AUXILIARY  
HEAT CHANGE  
OVER VALVE  
W2  
connected to the G terminal.  
2.  
3.  
Loosen the terminal block  
screws. Insert wires then  
retighten terminal block screws.  
Typical 2H/1C Heat Pump System with separate emergency heat  
C
Place nonflammable insulation  
into wall opening to prevent  
drafts.  
Max Torque = 6in-lbs.  
L2  
L1(HOT)  
R
R
COMPRESSOR  
RELAY  
Y
C
W/E  
Terminal Designations  
COOL CHANGE  
OVER VALVE  
O
B
EMERGENCY  
RELAY  
Heat Pump System  
1 HEAT 1 COOL / 2 HEAT 1 COOL  
Conventional System  
1 HEAT 1 COOL / 2 HEAT 1 COOL  
HEAT CHANGE  
OVER VALVE  
G
FAN RELAY  
AUXILIARY  
W2  
Transformer Power  
Transformer Power  
Transformer Common  
Energized in HEAT  
R
Transformer Common  
C
Conventional System 1H/1C, 2H/1C (Heat pump set to“OFFin tech settings)  
Changeover Valve  
Energized in HEAT  
B
C
Note: This  
thermostat is only  
compatible with  
ONE transformer  
systems.  
Changeover Valve  
Energized in COOL  
L2  
L1(HOT)  
Energized in COOL  
Fan Relay  
O
R
Y
Fan Relay  
G
R
COMPRESSOR  
RELAY  
First Stage of Emergency HEAT  
First Stage of HEAT  
Second Stage of HEAT  
First Stage of COOL  
W/E  
C
W/E  
G
HEAT RELAY  
FAN RELAY  
Second Stage of HEAT/  
EMERGENCY HEAT  
W2  
W2  
First Stage of HEAT and COOL  
Y
HEAT RELAY 2  
5
6
Technician Setup (For professional technicians only)  
Technician Setup (For professional technicians only)  
Tech Settings  
LCD Will Show Adjustment Options Default  
Tech Settings  
1. Select OFF with the System Switch for Tech Settings. Select Heat or Cool for Swing  
and Limit settings. They are set separately.  
2. Hold down the + and - buttons together for 3 seconds.  
3. Use the + and - to change setting for that step, and the glow in the dark light button to  
move from one step to another.  
This feature controls the number  
of stages in Emergency Heat  
mode. It only appears if the  
Technician Setup Step for HEAT  
PUMP is ON.  
Use the  
select 1-stage or 2-stage  
operation.  
or  
key to  
Emergency  
Heat Stages  
1
This feature allows the thermostat  
to keep multiple stages of heat  
energized until setpoint is  
satisfied.  
Use the  
turn ON or OFF.  
or  
key to  
To exit setup slide the system switch to different position or wait approximately 20 seconds.  
Satisfy  
Setpoint  
OFF  
LCD Will Show Adjustment Options Default  
Tech Settings  
This feature allows the installer  
to change the calibration of the  
room temperature display. For  
example, if the thermostat reads  
70 degrees and you would like it  
to read 72 then select +2.  
You can adjust the room  
CA  
read 4˚above or below the  
This feature allows a delay to occur  
when a second stage is needed.  
This allows the previous stage  
extra time to satisfy setpoint.  
Use the  
select OFF, 5, 10, 15, 30, 45,  
60, or 90 minutes.  
or  
key to  
Room  
Temperature  
Calibration  
temperature display to  
Staging  
Delay  
factory calibrated reading.  
OFF  
0
0
The compressor short cycle delay  
protects the compressor from  
short cycling. This feature will  
not allow the compressor to be  
turned on for 5 minutes after it  
was last turned off.  
Selecting “ON”will not allow  
the compressor to be turned  
on for 5 minutes after the  
last time the compressor  
LCD Will Show Adjustment Options  
Default  
Swing and Limit Settings  
Cd  
Compressor  
Short Cycle  
Delay  
The swing setting often called  
The cooling swing setting is  
adjustable from 0.2˚ to 2˚. For  
example: A swing setting of  
0.5˚will turn the cooling on at  
approximately 0.5˚ above the  
setpoint and turn the cooling off  
at approximately 0.5˚ below the  
setpoint.  
0N  
“cycle rate, “differential”or “  
anticipation”is adjustable. A  
smaller swing setting will cause  
more frequent cycles and a larger  
swing setting will cause fewer  
cycles.  
was switched off. Select  
“OFF”to remove this delay.  
Cooling  
Swing  
0.8  
Select F for Fahenheit  
temperature read out or select C  
for Celsius read out.  
F for Fahrenheit  
FC  
F or C  
C for Celsius  
o
F
F
This feature allows you to set a  
minimum cool setpoint value.  
The setpoint temperature can’t be  
lowered below this value.  
Use the and  
the minimum cool setpoint.  
key to select  
Cooling  
Setpoint  
Limit  
When set to ON this thermostat  
will operate a heat pump system  
(default). If set to OFF this  
thermostat will operate a  
conventional system, and the next  
tech step will not appear.  
ON - Configured to operate  
heat pump system.  
OFF - Configured to operate  
44  
Heat Pump  
conventional system  
ON  
See page 5 for terminal  
designations.  
The heating swing setting is  
adjustable from 0.2˚ to 2˚. For  
example: A swing setting of  
0.5˚will turn the heating on at  
approximately 0.5˚ below the  
setpoint and turn the heating off  
at approximately 0.5˚ above the  
setpoint.  
The swing setting often called  
“cycle rate, “differential”or “  
anticipation”is adjustable. A  
smaller swing setting will cause  
more frequent cycles and a larger  
swing setting will cause fewer  
cycles.  
OFF will allow Y(1st stage of  
Heat) and W2 (Aux Heat) to run  
together if called for.  
Dual Fuel  
Auxiliary for  
Heat Pump  
Will only appear if  
Heat Pump setting is  
turned ON  
For Dual Fuel applications (Gas/  
Fossil fuel Auxiliary Heat), turn  
this setting ON to LOCKOUT the  
Heat Pump (Y) when Auxiliary  
Heat (W2) is on. If desired- This can  
also be used with Electric Auxiliary.  
Heating  
Swing  
0.8  
OFF  
ON Will de-energize Y terminal  
45 seconds after a call for  
Auxiliary Heat (W2).  
Select GAS for systems that  
control the fan during a call for  
heat. Select ELEC to have the  
thermostat control the fan during  
a call for heat.  
EL - Electric for thermostat  
control  
This feature allows you to set a  
maximum heat setpoint value.  
The setpoint temperature can’t  
be raised above this value.  
Use the and key to select  
the maximum heat setpoint.  
Heating  
Setpoint  
Limit  
Fan  
Operation  
EL  
90  
GS- Gas for system control  
7
8
GeneralDetails
NameVIVE COMFORT TP-N-721 Non Programmable Thermostat Instruction Manual
MakeVive Comfort
LanguageEnglish
FiletypePDF (Download)
File size0.3 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Vive Comfort TP-S-955WH Programmable Thermostat Instruction Manual
Vive Comfort TP-S-955WH Programmable Thermostat Instruction Manual
VIVE COMFORT TP-S-755 Cool Programmable Thermostat Instruction Manual
VIVE COMFORT TP-S-755 Cool Programmable Thermostat Instruction Manual

VIVE COMFORT TP-N-721 Non Programmable Thermostat Instruction Manual