PECO TW180 Thermostat Instruction Manual
TW180 THERMOSTAT
INSTALLATION INSTRUCTION
CONTROL
SYSTEMS
PECO TW180 THERMOSTAT
!
WARNING
▲
Thank you for choosing a PECO® TW180 thermostat. The TW180 thermostat
is intended for use in commercial and residential enviroments. It supports both
programmable and non-programmable operation.
• READ THESE INSTRUCTIONS CAREFULLY BEFORE ATTEMPTING TO
INSTALL, OPERATE OR SERVICE THIS THERMOSTAT.
• Failure to observe safety information and comply with instructions could
result in PERSONAL INJURY, DEATH AND/OR PROPERTY DAMAGE.
• To avoid electrical shock or damage to equipment, disconnect power
before installing or servicing and use only wiring with insulation rated for full
thermostat operating voltage.
Key features include: auto-changeover; optional remote sensor; three levels of
keypad lockout with optional PIN access code; a heat/cool Demand Indicator;
up to four scheduled events per day, a 365-day calendar, 20 holidays, holiday
override and temporary override.
• Use care to avoid electrostatic discharge.
• To avoid potential fire and/or explosion do not use in potentially flammable
or explosive atmospheres.
Applications
The PECO® TW180 applications include fan coil, PTAC and conventional
system with a single or multi speed fan operation.
System Mode Selections: Off-Heat-Cool-Auto
• Retain these instructions for future reference.
• This product, when installed, will be part of an engineered system whose
specifications and performance characteristics are not designed or
controlled by PECO® . Review applications and national and local codes to
assure that the installation will be functional and safe.
Outputs: 1 Cool and up to 2 Heat
Fan Control: Cycling (Auto) or Continuous (On); Up to 3 Speeds or Staged
Permanent Memory: All device settings are stored in permanent memory.
Optional Connections: Remote Sensor, Pipe Sensor, Fault Detection,
Setback, Occupancy and Door Switch
SPECIFICATIONS
Temperature Control Range: 50 to 90°F (10 to 32°C
Differential: 1°F
Physical Dimensions: 4.4”H x 5.8”W x 1.1”D
Construction of Control: Independently Mounted
Operating Temperature: 0°F to 120°F (-18° to 49°C)
Shipping/Storage Temperature: -20°F to 130°F (-29°C to 54°C)
Operating Humidity: 5%-95% RH, non-condensing
Low Voltage Terminal Connections: 18 -12 AWG
Remote Sensor: 10K NTC Type 2
OUTPUT RATINGS
Inductive
Resistive
!
Voltage
Pilot Duty
Amps
FLA
NA
4.4
2.2
1.8
LRA
NA
24 VAC
120 VAC
240 VAC
277 VAC
NA
4.5
4.3
4.2
24 VA
125 VA
125 VA
125 VA
26.4
13.2
10.8
Agency Approvals: UL, UL Canada
COMBINED LOAD CURRENT NOT TO EXCEED 20 AMPS
MOUNT ONLY TO A GROUNDED METALLIC BOX
LOW VOLTAGE WIRING IS CLASS 2
Wiring Diagram
120-277 VAC Operation
24 VAC Operation
MOVE Input Power Jumper
to TB2-1 and TB2-2
for 24 VAC Operation.
Unused
TB2-1
TB2-2
TB2-3
TB2-1
TB2-2
TB2-3
Input Power Jumper (Default Postion)
for 120-277 VAC Operation.
Black
Black (Switched Side)
L1 HOT
Yellow
Yellow
Red
L2 Neutral
Red
HEAT 1
COOL
HEAT 1
Blue
Blue
COOL
FAN HI
White/Orange
White/Red
White/Brown
White/Orange
White/Red
White/Brown
FAN HI
CAUTION
Individually wirenut
off unused leads
CAUTION
Individually wirenut
off unused leads
FAN MED
FAN LO
FAN MED
FAN LO
Brown
Brown
Outside Air
or HEAT 2
Outside Air
or HEAT 2
24 VAC 1 (Switched Side)
24 VAC 2
Unused
Unused
Remote Temperature Sensor
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
Remote Temperature Sensor
Pipe Sensor
Pipe Sensor
Occupancy
Occupancy
Door/ Window Switch
Sensor Common
Door/ Window Switch
Sensor Common
© COPYRIGHT 2023 PECO, INC. ALL RIGHTS RESERVED.
P/N 74150 3220-2384 REV 04
1
| General | Details |
|---|---|
| Name | PECO TW180 Thermostat Instruction Manual |
| Make | PECO |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.56 MB |