Home > Network Thermostat > network thermostat NetX X5-CFA Universal Setback Thermostat Instruction Manual
network thermostat NetX X5-CFA Universal Setback Thermostat Instruction Manual
Reattach Faceplate
A NOTE: If Conventional is Selected Proceed to Stages Cool.
COMMON CONTROL SETUP
Minimum On Time
Default: 2 minutes. Select between 0-5 Minutes. The value is
displayed on the main display. The system will operate for a
minimum of 0 minutes to 5 minutes depending on your setting.
FEATURES
CLK Terminals
Selects between Occupied and Unoccupied operation using a
dry contact closure. A shorted contact between CLK1 and
CLK2 places the thermostat in Unoccupied operation.
Removing the short places the thermostat in Occupied
operation.
If Heat Pump is selected, proceed to # of Compressors.
5. Reattach faceplate to backplate by placing the top of the
faceplate over the top lip of the backplate.
Stages Cool
6. Gently swing the thermostat down and press on the
bottom center edge until it snaps in place. This is a tight
connection, but may require a little wiggle to align the pins
on the faceplate with the screw terminals on the backplate
before it snaps into place.
Default: 2 Select between 1 or 2 Stages Cool. The value is
displayed in the main display.
Minimum Off Time
Default: 4 minutes. Select between 2 to 5 Minutes. The value is
displayed on the main display. The system will allow equipment
recovery for 2 to 5 minutes before turning on again.
Stages Heat
Default: 2Select between 1 or 2 Stages Heat. The value is
displayed in the Main Display.
7. Reconnect power to the HVAC equipment. You are now
ready to configure your thermostat for operation.
LED1 Terminal / Filter Indicator
s
When a 24VAC signal is present on the LED1 terminal, the
Gas or Electric Heat
Select between Gas or Electric operation. Gas heat is the default.
Filter icon
will display on the thermostat screen.
s
Calibration Offset
The thermostat and remote sensors are pre-calibrated at the
factory, but in some installations, lack of airflow at the sensor or
proximity to other warming or cooling sources may cause the
temperature to be off by a few degrees. The X5-CFA thermostat
includes a temperature calibration offset with a range of ±6˚F
(±3˚C) in 0.2˚F (0.1˚C) increments.
LED2 Terminal / Service Indicator
N
A NOTE: If you selected Conventional Heat, proceed to
Minimum On Time.
When a 24VAC signal is present on the LED2 terminal, the
Wrench icon will display on the thermostat screen.
N
HEAT PUMP SETUP
# of Compressors
Default: 2 Select between 1 or 2 Stage Compressor. The
value is displayed in the main display. The default is 1.
REMOTE SENSORS
If your NetX™ thermostat has been installed with one or more
NetX™ remote sensors, the sensor information is available on
the small secondary display of the thermostat. There are many
different remote sensor options.
1st Stage Differential
Select between 1-6˚F (0.5-3˚C). The value is displayed in the
main display. 1˚F (0.5˚C) is the default. The 1st Stage Differential
is the temperature degree change required before the
thermostat responds.
1
2
3
Enable Aux/EHeat
Select between Aux/EHeat Mode On (default) or Aux/EHeat
Mode Off.
You can view the remote sensor information by tapping upper
left part of the display to view different attached remotes
sensors.
WARNING: Your thermostat is NOT ready to use. You
C
must complete the Thermostat Setup section before using
the thermostat. Failure to do this can result in damage to your
equipment.
A NOTE: For single compressor setup go to the One
Compressor Configuration. For two compressors setup go to
Two Compressor Configuration.
A NOTE: If the Aux/EHeat ON is selected, proceed to Heat Pump
Option. Otherwise, proceed to the Minimum On Time option.
The X5-CFA thermostat uses one or more NT-ROOM-S remote
sensors for temperature control. See the NT-ROOM-S
installation instructions for details.
ONE COMPRESSOR CONFIGURATION
Aux Heat Differential (Heat Pump Operation)
Default: 1˚F (0.5˚C) Select between 1-6˚F (0.5-3˚C). The value is
displayed on the main display. Proceed to Aux Heat Delay.
THERMOSTAT SETUP
Heat Pump Option
Select between HP Regular (default) or HP Dual Fuel.
A NOTE: If no remote sensors are detected, the thermostat
will default to the internal temperature sensor.
The Dot Matrix Display will provide feedback on the HVAC
Settings Menu configuration and selected options. The Up
If needed, the thermostat will perform the function of a fossil
fuel kit. When HP Dual Fuel is selected the thermostat will turn
off the compressor with a call for AUX heat. The HP Regular
option will allow the compressor and AUX heat to run
simultaneously.
Button
and Down Button
are used to select parameters
J
K
RS1 – RS2 – RS+V Terminals / Remote Sensor Bus
Used for connection of a wide variety of NetX™ remote
sensors. See NetX sensor instructions for use.
while the LEFT ARROW (Back Button) and RIGHT ARROW
(Accept button) are used to accept settings and navigate
through the menu. At any time you can use the CANCEL
BUTTON to return to normal operation.
TWO COMPRESSOR CONFIGURATION
2nd Stage Differential
Select between 1-6˚F (0.5-3˚C). The value is displayed on the
main display. 3˚F (1.5˚C) is the default.
A NOTE: If no remote sensors are detected, the thermostat
will default to the internal temperature sensor.
High & Low Balance Point Configuration
INSTALLER MENU
Press and hold the MODE Button
If the thermostat is being used as a Heat Pump thermostat and
current weather conditions are enabled or an outdoor sensor is
connected to the remote sensor terminals, the thermostat can
be configured to disable the use of auxiliary heat during
warmer weather and to lock out the compressor during colder
weather. If the weather conditions are enabled the high and
low balance point settings are available in the installer menu.
Emergency Heat Indicator
Q
for 5 seconds to access.
F
2nd Stage Delay
Select between 5-40 Minutes in 5 minute increments. The value
is displayed on the main display. 20 Minutes is the default.
HVAC Settings Menu will briefly display in the Dot Matrix
Area followed by Conventional/HP. To save a setting and
advance to the next menu item, press the Checkmark Button
The thermostat is equipped with Emergency Heat icon in the
Q
Current Operation Status Icon area on the faceplate that
indicates when the system has engaged emergency heat mode.
(Right Arrow). To return to the previous menu item, press
M
Aux Heat Differential (Heat Pump Operation)
the Back Button
(Left Arrow).
L
Random Restart
Select between 1-6˚F (0.5-3˚C). The value is displayed in the
TIP: Refer to the manufacturer’s heat pump equipment
After a power failure, the thermostat will delay the HVAC
equipment start-up by 1-24 seconds. When multiple NetX™
X-Series thermostats are used, this minimizes the “in rush”
current (electric power usage) as it reduces the number of
HVAC units that will be turned on simultaneously.
Conventional / Heat Pump
Select between Conventional or Heat Pump operation.
Conventional is the default.
B
main display. 1˚F (0.5˚C) is the default.
manual for temperature cut-offs on the equipment.
Aux Heat Delay (Heat Pump Operation)
Default: 20 minutes. Select between 5-40 Minutes in 5 minute
increments. The value is displayed on the main display.
Low Balance Point
Default: -54˚F (-48˚C). Select between -54˚F to 39˚F (-48˚C to
4˚C). The value is displayed on the main display. This will lock out
the heat pump at the selected outdoor temperature.
CONVENTIONAL SETUP
Power Failures
Thermostat Address
Default: 1 Sets the thermostat address for communications with
the NetX NT-IPXB network controller.
This NetX™ X5-CFA thermostat will maintain the operation
settings during any type of power failure. When power is
restored the thermostat will return to the last MODE (Heat,
Cool, Auto, Off) and the Occupied setpoints. If the CLK
terminals are shorted at power up, the thermostat will operate
using the last Unoccupied setpoints.
High Balance Point
Default: 118˚F (48˚C). Select between 41˚F-118˚F (5˚C-48˚C).
The value is displayed on the main display. This will lock out the
auxiliary heat at the selected outdoor temperature.
A NOTE: Each thermostat connected to a network controller
must have its own unique address. This is adjustable from 1-99
but the NT-IPXB controller can only support 32 thermostats.
Page 2
| General | Details |
|---|---|
| Name | network thermostat NetX X5-CFA Universal Setback Thermostat Instruction Manual |
| Make | Network Thermostat |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.41 MB |

Network Thermostat X7-Series Thermostat Installation Guide

Network Thermostat X7C-WIFI Smart Touchscreen Thermostat Instruction Manual

Network Thermostat X5-WIFI Smart Touchscreen Thermostat Instruction Manual

Network Thermostat NetXTM X-Series Thermostat Installation Guide

network thermostat NetX X Series Thermostat Instruction Manual

network thermostat NetX X-Series Ethernet Thermostat Owner’s Manual

network thermostat X-Series Ethernet Thermostat Instruction Manual

Network Thermostat NetX X7 Series Thermostat Instruction Manual

network thermostat X X7-WIFI Smart Touchscreen Thermostat Instructions