Home > Legrand > legrand WZ3TSTATH Thermostat Instruction Manual

legrand WZ3TSTATH Thermostat Instruction Manual

GRN  
RED  
BLK  
Ground  
RS-485 B (+)  
RS-485 A (-)  
2. INSTALLATION  
Header 3  
The thermostat is typically mounted to an industry standard double gang  
junction box or trim ring about 5 feet above the floor. Example Legrand  
part numbers are shown in the chart below.  
TER DAM R 24VAC  
TER DAM NO Normal Closed  
TER DAM NO Normal Open  
Thermostats should be placed away from windows to avoid solar heating  
to improperly affect the units temperature sensitivity. Be certain that the  
thermostat will not be covered by objects such as a bathroom or closet  
door when open. The thermostat should not be mounted near the heating/  
cooling equipment in a manner where direct airflow, or the waterfall effect  
of a heating or cooling unit would impact the measurement of the overall  
room.  
Header 2  
Header 4  
ORG  
PPL  
GRY  
Low Fan  
Fan Power  
Valve Power  
WHT  
YEL  
Heat Valve  
Cool Valve  
Header 1  
Ground  
GRN  
RED  
BLK  
2.1 Flush Mounting  
24V AC  
Common  
Not Used  
BLU  
BRN  
High Fan  
Med Fan  
Analog Input  
GRY  
PPL  
BLU  
GRN  
YEL  
0-10V VFD Fan  
Digital Input 3  
Digital Input 2  
Digital input 1  
NOT USED  
ORG  
RED  
12V DC  
Ground  
BRN  
Figure 5 – Wiring Harness Locations  
2.3.1 Harness 1 – Main Harness PN WATSTATH101  
Pin Number  
Function  
Color  
Green  
Red  
1
2
Ground  
Figure 3 – Flush Mounting  
24 VAC  
3
Common  
Black  
Blue  
Applicable Legrand Double Gang Boxes  
4
High Fan  
Medium Fan or Second Stage Heat  
Cold Water Valve or Compressor Signal (Heat Pump)  
Hot Water Valve or Reversing Valve (Heat Pump)  
Valve Power  
New Work Plastic  
New Work Steel Stud  
Screw Steel Stud  
Old Work Plastic  
S235RAC  
S235S50AC  
S235RACS  
S232W  
5
Brown  
Yellow  
White  
Grey  
6
7
8
2.2. Wall Mounting  
9
Fan Power  
Violet  
Orange  
The product may also be wall mounted using the included wall mount  
bracket. The bracket can mount over a double gang wall box pattern or  
secured appropriately to the wall using suitable fasteners.  
10  
Low Fan  
2.3.2 Harness 2 – Digital Wiring Harness PN WATSTATH201  
Pin Number  
Function  
Color  
Grey  
1
2
3
Analog Input - Remote Thermistor  
Analog Output - 0-10V VFD Fan  
Digital Input 3 - External PIR/motion sensor  
Purple  
Blue  
Digital Input 2 - Balcony Door/Window, 2 transitions  
to active  
4
Green  
5
6
7
8
Digital Input 1 - Entry Door, 2 transitions to active  
Yellow  
Orange  
Red  
Figure 4 – Wall Mounting  
2.3. Wiring  
The WZ3TSTATHx Thermostat can connect to various different types of  
HVAC systems. It utilizes 4 different wiring harness to access specific  
features.  
Not Used  
VEE (12 Vdc)  
GND Ground  
Brown  