Quick Installation Guide  
Number  
Description  
Options (factory default in bold)  
1 - 6 CPH (3 CPH)  
Note: This ISU is only displayed when Cool /Compressor Stages is set to 1 or more stages. Cycle  
rate limits the maximum number of times the system can cycle in a 1 hour period measured  
at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle  
is 3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load  
conditions are less than or greater than a 50% load.  
Cool 1 CPH (Cooling  
cycle rate stage 1)  
365  
Cool 2 CPH (Cooling  
cycle rate stage 2)  
1 - 6 CPH (3 CPH)  
Note: This ISU is only displayed when Cool /Compressor Stages is set to 2.  
366  
370  
1 - 12 CPH  
Note: This ISU is only displayed when Heat Stages is set to 1 stage or more stages. Cycle rate  
limits the maximum number of times the system can cycle in a 1 hour period measured at a  
50% load. For example, when set to 3 CPH, at a 50% load, the most the system will cycle is  
3 times per hour (10 minutes on, 10 minutes off). The system cycles less often when load  
conditions are less than or greater than a 50% load. The recommended (default) cycle rate  
settings are below for each heating equipment type:  
Heat 1 CPH (Heating  
cycle rate stage 1)  
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil  
Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat  
= 3 CPH; Steam = 1 CPH.  
1 - 12 CPH  
Note: This ISU is only displayed when Heat Stages is set to 2 stages. The recommended  
(default) cycle rate settings are below for each heating equipment type:  
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil  
Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat  
= 3 CPH; Steam = 1 CPH.  
Heat 2 CPH (Heating  
cycle rate stage 2)  
371  
375  
1 - 12 CPH  
Note: This ISU is only displayed when ISU 200 = Heat Pump and ISU 221=1. It is only displayed  
when Auxiliary Heat is configured. The recommended cycle rate settings are below for each  
heating equipment type:  
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil  
Forced Air = 5 CPH; Electric Forced Air = 9 CPH.  
Aux Heat CPH (Heating  
cycle rate Auxiliary  
Heat)  
0 = No  
1 = Yes  
425  
430  
Smart Response  
Note: Smart Response is a comfort setting. Heat or Cooling equipment will turn on earlier,  
ensuring the indoor temperature will match the setpoint at the scheduled time. See page 16.  
50 °F to 99 °F (50 °F)  
10.0 °C to 37.0 °C (10.0 °C)  
Note: The cool temperature cannot be set below this level.  
Minimum Cool  
Temperature Setpoint  
40 °F to 90 °F (90 °F)  
4.5 °C to 32.0 °C (32.0 °C)  
Note: The heat temperature cannot be set above this level.  
Maximum Heat  
Temperature Setpoint  
431  
702  
0 - 1  
Note: This ISU refers to the number of air filters in the system.  
Air Filters  
0 = Off  
10 = 45 Calendar Days  
11 = 60 Calendar Days  
12 = 75 Calendar Days  
13 = 3 Calendar Months  
14 = 4 Calendar Months  
15 = 5 Calendar Months  
16 = 6 Calendar Months  
17 = 9 Calendar Months  
18 = 12 Calendar Months  
19 = 15 Calendar Months  
1 = 10 Run Time Days  
2 = 20 Run Time Days  
3 = 30 Run Time Days  
4 = 45 Run Time Days  
5 = 60 Run Time Days  
6 = 90 Run Time Days  
7 = 120 Run Time Days  
8 = 150 Run Time Days  
9 = 30 Calendar Days  
Air Filter 1  
Replacement Reminder  
711  
Note: Set a reminder for when to change your air filter. Choose either calendar or equipment run  
time-based reminder.  
0= Off, 0 - 5  
Note: Adjust brightness of an inactive backlight (idle screen) from default 0 (backlight off) to 5  
(maximum brightness). Common wire required for settings 1-5.  
1401  
1410  
1415  
Idle Brightness  
Clock Format  
12 hour, 24 hour  
0 = Off  
1 = On  
Note: Set to Off in areas that do not follow Daylight Saving Time.  
Daylight saving time  
NOTE: Once you have cycled through all of the System Setup numbers, Done is displayed. Press Select to  
save and exit.  
10  
GeneralDetails
NameHoneywell RTH8500 Wifi Thermostat User Manual
MakeHoneywell
LanguageEnglish
FiletypePDF (Download)
File size1.11 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TL116A Thermostat Installation Guide
Honeywell TL116A Thermostat Installation Guide
T10 Pro Smart Thermostat with Redlink Room Sensor
T10 Pro Smart Thermostat with Redlink Room Sensor
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell RLV3100 Digital Thermostat Installation Guide
Honeywell RLV3100 Digital Thermostat Installation Guide

Honeywell RTH8500 Wifi Thermostat User Manual