Home > GENERAL LIFE > GENERAL LIFE HT25S RF Wireless Room Thermostat User Manual
GENERAL LIFE HT25S RF Wireless Room Thermostat User Manual
RECEIVER
RECEIVER PLACEMENT
ROOM THERMOSTAT HEATING / COOLING MODES
Your Room Thermostat has heating and cooling modes. In order to switch easily
betweenheating and cooling modes:
ENGLISH
1-Manual Operation Button:
Deactivates the Receiver and allows you to use
The important things to note for the Receiver
placement is avoiding physical contact between the
Receiver and heating/cooling unit, and protecting it
against materialssuch asliquid, dust etc.
1
2
3
heating/cooling unit manually.
2-Pairing Button:
While yourdeviceis turned off, pressand hold thebutton for 3 seconds.
DIGITAL ROOM THERMOSTAT
Pressthebutton until the“
You can switch between “
button to right or leftin the“
” menu appears.
” (heating) and “
” menu.
Pairs the Receiver and the Room Thermostat.
3-Receiver LED Light
4-Receiver Power Cable Input
5-Heating/Cooling Unit Connection Cable Input
” (cooling) modes by turning the
generallife.com.tr
To savethesettingsand exit, pressthebutton until thedeviceturns off.
The settings you have made have been saved. Once you turned on your device, it
willoperatewiththechanged settings.
SERIES:
MITRA, ARUNA, CERES, GAIA, ILLONA, NORA, SENNA, THERMA
The devices should be placed in order to minimize the damage to the received and
transmittedsignals bypayingattentiontothefollowingpoints;
The devicesshould not be mounted on metalsurfaces.
OPEN WINDOW DETECTION FEATURE
HT25 RF/HT25S RF/HT26S RF USER MANUAL
The devices should not be installed close to electrical cables and electronic
equipment such ascomputers and televisionunits.
If a window is left open, cold air will enter and the temperature in the room will drop
rapidly. In cooling systems, hot air will enter and the temperature in the room will
rise rapidly. The Room Thermostat, which detects this situation, tries to keep the
room temperature at the desired level by operating the heating or cooling system
more. The open window detection feature allows the Room Thermostat to operate
the heating/cooling system more efficiently in case the temperature in the room
dropsor risesrapidly.
4
5
The devices should not be installed near large metal structures or other building
materialsusing finemetalmeshes such asspecialglass or specialconcrete.
Distance between the Room Thermostat and the Receiver should not exceed 20
metersor 2 floors.
GENERAL SPECIFICATIONS
RECEIVER LED DESCRIPTIONS
Constant Red
HT25 RF/HT25S RF/HT26S RF is a wireless room thermostat. The user can adjust
the room temperature with the required temperature and get more comfortable and
economic heating/cooling.
Receiver has power but Receiver and Room
Thermostat are not paired.
Blinking Green
Constant Green
Waiting for pairing signal from the Room Thermostat.
Receiver and Room Thermostat are paired.
Heating/cooling unit is not operating.
Operate the heating/cooling unit signal has reached to
the Receiver.
Heating/cooling unit is operating.
Shut the heating/cooling unit down signal has reached
to the Receiver.
Heating/Cooling unit operates in manual mode.
Receiver did not get any signal from the Room
Thermostat for 22 minutes or longer.
Heating/cooling unit has shut down.
PreciseTemperatureMeasurement
Heating calibration
ON/OFFControl
WirelessConnection
TPIAlgorithm
Receivermust be installed atleast50cmawayfromtheheating/cooling unit.
This featureis used to saveenergyand to ensuremoreefficient operation of heating
and ccoling systems. Thanks to the open window detection feature, unnecessary
energyexpenditureispreventedand allows theuser to saveenergycosts.
RECEIVER SETUP
Heating/Cooling Modes
3 Short Orange
Blinking
Constant Orange
3 Short Green
Blinking
First, shut down your heating/cooling unit and your heating/cooling unit's power
sourcewithallelectricalcurrent(fuse, socketetc.)
Open Window DetectionFeature
When the Room Thermostat is in heating mode and the Open window detection
feature is active, if it detects a sudden drop in room temperature up to the degree
adjusted in the Set menu (factory setting 5oC) within 15 minutes, it switches to
alarm status, the open window icon flashes on the display of the Room Thermostat
and switches off the heating/cooling unit. The heating/cooling unit remains off for
the time adjusted in the Run Menu. If the Room Thermostat detects that the window
is closed or if a manual intervention is made on the Room Thermostat, the detection
is deactivated and heating/coolin unit continues to operate from where it left off. If
a sudden drop in ambient temperature is detected again, the Room Thermostat
goes into alarmstatus.
As shown in the connection diagram, connect one end of the heating/cooling unit
connection cableto theCOMand theother to theNO input of theReceiver.
Connect the other ends of the cable -which youconnected to the Receiverto room
thermostat connection terminal as shown in your heating/cooling unit's user
manual.
HT25 RF/HT25S RF/HT26S RF ve APARATLARI
Room Thermostat
Holder
Alkaline
Battery
Receiver
Dowels and Screws
Blinking Orange
Blinking Red
You must first connect the Receiver power cable to the Receiver and then to the
fuse to which theheating/cooling unit is connected.
ROOM THERMOSTAT PLACEMENT
After completing the cable connection process, firstly turn on your fuse and then
yourheating/cooling unit.
If the Room Thermostat is operated in cooling mode, the sudden temperaturerise in
taken to consideration.
Room Thermostat needs to be placed in the room which is used most frequently.
For instance; living room or lounge. Placing the Room Thermostat in a spot that
have air circulation like entrance of a room or side of window should be avoided.
Also anywhere close to heating/cooling units such as radiator, stove and spots
which get direct sun lights would not be suitable. Room Thermostat needs to be
located above the floor 150 cm height. Few trials may be made to find the most
convenientspot.
This featureisactivein factory setting.
By pressing the Receiver's manual usage button for 2 seconds, you should see
the Orange Light blinking on the Receiver. In this way, after making sure that the
heating/cooling unit is operating, press the same button again for 2 seconds and
seethattheOrange LEDturns off.
Itcan be deactivatedfromtheRoom Thermostatsettings.
To deactivatetheopen window detectionfeature:
TECHNICAL DATA
Room Thermostat
Dimensions
Operating Current
Temperature Measurement Accuracy
Operating Temperature Range
Battery Life
Pressthe“ON/OFF”button for 3 seconds while yourdeviceis turned off.
Pressthe“ON/OFF”button until the“ ” menu appears.
While in the“ ” menu, turn thebutton to left. The “ ” option willappear.
85.7mm / 85.7mm / 33.5mm
3V DC (2 x AAA alkaline battery)
0.1oC
Setup theRoom Thermostatto pair theReceiverwiththeRoom Thermostat.
(5oC) – (30oC)
AC
(230V)
RECEIVER WIRING DIAGRAM
To savethesettingsand exit, pressthe“ON/OFF”button until thedeviceturns off.
The settings you have made are saved. Your device will work with the setting you
havemade when youopen it.
1 Years (2 x AAA)
COM
NO
min. 20 cm
Operating Temperature
Storage Temperature
(-10oC) – (+50oC)
(-20oC) – (+60oC)
Heating/Cooling Unit
Off
On
On
Room
Temperature
Receiver
22oC
Dimensions
Operation Current
Relay NO Switching Current
90mm / 90mm / 25mm
230V AC
7A (240VAC – Resistive load)
10A (120VAC – Resistive load)
(-20oC) – (+60oC)
17oC
Storage Temperature
HEATING/COOLING UNIT
Time
15 min.
25 min.
40 min.
Warning!
OPEN WINDOW DETECTION OPERATION SETTINGS
- SET MENU
Operations within the heating / cooling unit or the electrical installation must be
carriedout byprofessionally qualified persons.
ROOM THERMOSTAT
SetMenu allows youto set the value of the sudden temperature change (celsius)
required for your Room Thermostat to activate the open window detection feature.
The factory setting of the required sudden temperature change value is 5oC. This
valuecan be adjusted between2oC and 10oC.
PAIRING THE ROOM THERMOSTAT AND THE RECEIVER
3
Primarily press the sync button of receiver for 2 seconds and see blinking green
light of receiver.
1
2
BATTERY PLACEMENT
4
5
6
To change theopen window operating temperature:
While yourdeviceis turned off, pressand hold thebutton for 3 seconds.
Pressand hold thebutton for 3 seconds while thedeviceis switchedoff.
Pressthebutton until the“ ” menu appears.
In the “ ” menu that appears, adjust the operating temperature by turning the
Pressthebutton until the“
” menu appears.
Then turn up thebutton to right or leftway.
If the pairing is successful, the green flashing LED on the receiver will be
constant.
7
button to theright or left.
To savethesettingsand exit, pressthebutton until thedeviceswitches off.
The settings you have made have been saved. Once you turn on your device, it will
operatewiththechanged settings.
Receiverand Room Thermostathavebeen pairedto eachother.
1
2
3
4
Room Temperature
Open Window Detection Feature
Battery Indicator
Set Temperature
Heating Indicator
- If the Heating Indicator is blinking, the heating unit is working.
- If the Heating Indicator is steady, the heating unit is not working.
Cooling Indicator
- If the Cooling Indicator is blinking, the cooling unit is working.
- If the Cooling Indicator is steady, the cooling unit is not working.
ON/OFF and Temperature Setting Button
ROOM THERMOSTATTEMPERATURE CALIBRATION
Temperature sensors which are used in Room Thermostats are highly sensitive.
You may need to calibrate your Room Thermostat if you would like to get the same
temperaturevalueswithother thermometersin yourliving space.
- RUN MENU
Remove the battery cover located on the back of your Room Thermostat. Insert 2
new AAA alkaline batteries into the battery housing with the correct battery
directionand close thebattery cover. Replaceboth batteriesatthesametime.
Run Menu allows you to set the off time of the heating/cooling unit while the open
window detection feature of your Room Thermostat is active. The factory setting
for off timeis 10minutes.
5
While yourdeviceisturned off, pressand hold thebutton for 3 seconds.
Press the button until the “ ” menu appers. In order to see the desired
Low Battery Warning: When the “
” icon appears on the screen, it means “low
To settheoff time:
temperature, set the temperature difference by turning the button to right or left.
This valuecan be arranged between“-8oC" and “+8oC".
6
7
battery warning”. It is recommended to replace the batteries when this warning
appears.
Pressand hold thebutton for 3 seconds while yourdeviceis switchedoff.
Pressthebutton until the“ ” menu appears.
Set the operating time of the open window detection featureby turning the button
to theright or leftin the“ ” menu.
To savethesettingsand exit, pressthe"On/Off" button until thedeviceturns off.
Note:Recommended tempreturecalibration is“0.0oC”.
Warning: When the product is not used for a long period (more than 15 days), remove
thebatteries. Otherwise, malfunctions thatmay occurwouldbeoutof warranty.
Pleasethrowyourdead batteries into thewastebin forbatteries.
To savethesettingsand exit, pressthebutton until thedeviceswitchesoff.
The settings you have made have been saven. Once you turn on your device, it will
operatewiththechanged settings.
2
1
3
4
| General | Details |
|---|---|
| Name | GENERAL LIFE HT25S RF Wireless Room Thermostat User Manual |
| Make | GENERAL LIFE |
| Language | English |
| Filetype | PDF (Download) |
| File size | 2.06 MB |

GENERAL LIFE HT330S RF Room Thermostat User Manual

GENERAL LIFE FH103S Underfloor Heating Thermostat User Manual

GENERAL LIFE HT250 RF Digital Room Thermostat User Manual

GENERAL LIFE FH104S Underfloor Heating Thermostat User Manual

GENERAL LIFE ARUNA 302S Digital Room Thermostat User Manual

GENERAL LIFE FH250S Underfloor Heating Thermostat User Manual

GENERAL LIFE FC220 Digital Fan Coil Thermostat User Manual

GENERAL LIFE HT220S RF Digital Room Thermostat User Manual

GENERAL LIFE 270S RF Room Thermostat User Manual

GENERAL LIFE 270 Wireless Room Thermostat User Manual

GENERAL LIFE HT25S RF Wireless Room Thermostat User Manual Overview
Summary of Contents
- Page 1: Receiver placement is important to avoid physical contact with heating/cooling units and protect against liquids and dust. The room thermostat has heating and cooling modes, which can be switched easily. The open window detection feature helps maintain room temperature by adjusting the heating or cooling system when a sudden temperature change is detected. The receiver must be installed at least 50 cm away from the heating/cooling unit. Distance between the room thermostat and the receiver should not exceed 20 meters or 2 floors. The receiver LED light indicates various statuses, such as pairing and operation. Battery placement requires inserting two new AAA alkaline batteries in the correct direction. The run menu allows setting the off time of the heating/cooling unit during open window detection. Temperature calibration may be necessary to align the room thermostat with other thermometers. Warnings include removing batteries if the product is not used for an extended period to prevent malfunctions.
- Page 2: Factory settings reset The warranty period starts from the invoice date and is warranted against manufacturing defects for 2 years. Your room thermostat sends the last status signal to the receiver every 6 minutes. If the signal cannot reach the receiver from the room thermostat for 22 minutes, it perceives that the connection is broken and stops the heating/cooling operation for safety reasons. You can reset your room thermostat to its default factory settings. The maintenance of devices and apparatus is done in our company. Your room thermostat works with the TPI algorithm, which predicts when the temperature will rise above or below the set temperature. In case of malfunctioning devices under warranty, it is tested whether the malfunction is caused by customer or manufacturer fault. If the TPI room thermostats are de-energized, the learning process will restart. Malfunctions resulting from the use of devices contrary to the user manual are not covered by the warranty.