INSTALLER SETTINGS  
5
The Installer Settings must be properly configured in order for this thermostat to operate correctly. The Installer  
Settings are menu driven. The portion of these settings that do not apply to your setup will be skipped.  
To Enter Installer Settings Menu  
1
Press and hold down the MENU button for 5 seconds.  
2 Release the MENU button after the first installer  
setting is displayed.  
Change settings as required using the or buttons.  
3
4 Press MENU to move to the next setting.  
5 Menu will exit automatically after last setting.  
*If 0000 IL is displayed, you must enter your 4-digit  
installer lock code to proceed (see Installer Settings  
9 and 10).  
No. Installer Setting  
Displayed Default Available Description of  
Setting Settings Available Settings  
F
C
Select for Fahrenheit temperature display  
Select for Celsius temperature display  
1
2
Temperature Scale  
DEG  
F
Selects a temperature scale of either °F or °C.  
1st Stage Differential DIF1 0.5  
0.5, 1.0, 2.0 Select a 1st stage temperature differential of  
0.5°, 1° or 2° F (0.2°, 0.5° or 1.0° C)  
Selects a 1st stage temperature differential which controls the degree of separation between the setpoint temperature  
and the 1st stage of heating or cooling.  
3
4
2nd Stage Differential DIF2  
2.0  
1.0, 2.0, 3.0 Select a 2nd stage temperature differential of  
4.0, 5.0, 6.0 1°, 2°, 3°, 4°, 5° or 6° F (0.5°, 1.0°, 1.5°, 2.0°,  
2.5° or 3.0° C)  
[1230 only] Selects a 2nd stage temperature differential which controls the degree of separation between the 1st  
and 2nd stage of heating or cooling.  
Compressor Short Cycle CSCP  
Protection (CSCP)  
5
5, 4, 3,  
2, 1, 0  
Select CSCP delay duration in minutes  
Selects the number of minutes the compressor will be locked out after turning off. This delay will run simultaneously with  
any delay built into the equipment.  
5
Heat Setpoint  
Upper Limit  
HIGH HEAT 90  
90 - 45  
Select a Heat Setpoint Upper Limit of 90° to  
(32˚ to 7˚C) 45°F (32° to 7°C)  
Selects the upper setpoint adjustment limit that cannot be exceeded in heat mode.  
45-90 Select a Heat Setpoint Lower Limit of 45° to  
(7˚ to 32˚C) 90°F (7° to 32°C)  
Selects the lower setpoint adjustment limit that cannot be exceeded in heat mode.  
6
7
Heat Setpoint  
Lower Limit  
LOWHEAT 45  
45 - 90  
Select a Cool Setpoint Lower Limit of 45° to  
Cool Setpoint  
Lower Limit  
LOWCOOL 45  
(7˚ to 32˚C) 90°F (7° to 32°C)  
Selects the lower setpoint adjustment limit that cannot be exceeded in cool mode.  
Installer Manual  
6
GeneralDetails
NameBraebur 1230 Non Programmable Thermostat Instruction Manual
MakeBraebur
LanguageEnglish
FiletypePDF (Download)
File size0.24 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

Braebur 1230 Non Programmable Thermostat Instruction Manual