5.5 Mode Changeover  
6. Technical Specifications  
The thermostat can switch between heat mode and cool mode  
either via:  
Power: 24 VAC  
Current consumption: 25 mA  
Output signals: Depends on output configurations  
Output ratings:  
• the automatic changeover  
• the changeover input  
- Triac output: 0.5 A maximum @ 24 VAC  
- Analog output (SCR connection): 0 - 10 V, 10 kW minimum  
- Analog output (SSR connection): 0 - 10 V, 45 mA maximum  
Setpoint range: 10°C to 35°C (50°F to 95°F)  
Temperature display: 0°C to 60°C (32°F to 140°F)  
Temperature display resolution: 0.5°C (1°F)  
Mode hysteresis: 2°C (4°F)  
Automatic changeover deadband: 5°C (9°F)  
Duty cycle: Depends on output configurations  
NSB offset: Programmable 1°C to 9°C (2°F to 18°F)  
NSB override period: 2 hours  
5.5.1 Automatic changeover  
In automatic changeover, the thermostat detects when the system  
switches between heat mode and cool mode by comparing the air  
supply temperature with the ambient temperature. If the thermostat  
is in heat mode, it switches to cool mode when the air supply is  
cooler than ambient by 5°C (9°F) or more. If it is in cool mode, it  
switches to heat mode when the air supply is warmer than ambient  
by 5°C (9°F) or more.  
Note: Neither the heat mode icon ( ) nor cool mode icon (  
)
Memory protection: Configuration and setpoint  
Temperature control: Proportional integral adaptive (P.I.A.)  
Operating temperature: 32°F to 140°F (0°C to 60°C)  
Storage temperature: -4°F to 122°F (-20°C to 50°C)  
Humidity limits: 0 to 95% R.H., non-condensing  
Dimensions: 69 x 118 x 27 mm (2.7 x 4.6 x 1.0 in.)  
appears when TH150 is placed in automatic changeover.  
5.5.2 Changeover Input  
The thermostat is in the default mode when the contact between ter-  
minals 9 and 11 is open and switches mode when the contact is  
closed. The default mode is set via the configuration menu .  
Note: The changeover contact state is ignored if TH150 is config-  
ured in automatic changeover or in limited cooling.  
7. WARRANTY  
5.6 Night Setback  
Aube warrants this product, excluding battery, to be free from defects in the work-  
manship or materials, under normal use and service, for a period of three (3)  
years from the date of purchase by the consumer. If at any time during the war-  
ranty period the product is determined to be defective or malfunctions, Aube shall  
repair or replace it (at Aube's option).  
The Night Setback (NSB) mode is activated when the  
contact between terminals 9 and 12 is closed. When  
TH150 is in the NSB mode, indicated by the ECONO  
display, the temperature is lowered or raised by the set  
NSB value depending whether the thermostat is in heat  
mode or cool mode respectively. The NSB value is set via the con-  
figuration menu.  
If the product is defective,  
(i)  
return it, with a bill of sale or other dated proof of purchase, to the place  
from which you purchased it, or  
(ii)  
contact Aube. Aube will make the determination whether the product  
should be returned, or whether a replacement product can be sent to you.  
This warranty does not cover removal or reinstallation costs. This warranty shall  
not apply if it is shown by Aube that the defect or malfunction was caused by  
damage which occurred while the product was in the possession of a consumer.  
Aube's sole responsibility shall be to repair or replace the product within the terms  
stated above. AUBE SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF  
ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES  
RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WAR-  
RANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PROD-  
UCT. Some provinces, states or regions do not allow the exclusion or limitation of  
incidental or consequential damages, so this limitation may not apply to you.  
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY AUBE MAKES ON  
THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUD-  
ING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PAR-  
TICULAR PURPOSE, IS HEREBY LIMITED TO THE THREE-YEAR DURATION  
OF THIS WARRANTY. Some provinces, states or regions do not allow limitations  
on how long an implied warranty lasts, so the above limitation may not apply to  
you.  
Night Setback Override  
To temporarily override the NSB mode, press the Over-  
ride button. The NSB mode is lifted for the next 2 hours  
or until the Override button is pressed again. During the  
override, the normal setpoint is used and OVERRIDE is  
displayed.  
5.7 Error Codes  
The following error codes can appear at the top of the display.  
E1: The internal temperature sensor is defective  
E2: The internal temperature sensor is shorted  
E3: The external temperature sensor is defective or not connected  
E4: The external temperature sensor is shorted  
This warranty gives you specific legal rights, and you may have other rights which  
vary from one province, state or region to another.  
8. SERVICE  
If you have any questions on the product installation or operation, contact us at:  
705 Montrichard Avenue  
Saint-Jean-sur-Richelieu, Quebec  
J2X 5K8  
Canada  
Tel.: (450) 358-4600  
Toll-free: 1-800-831-AUBE  
Fax: (450) 358-4650  
Email: aube.service@honeywell.com  
For more information on our products, visit us at:  
TH150  
400-150-000-C  
5/9/06  
6/6  
GeneralDetails
Nameaube technologies TH150 Series VAV Thermostat User Guide
Makeaube technologies
LanguageEnglish
FiletypePDF (Download)
File size0.65 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
aube technologies TH108PLUS Electronic Thermostat User Guide
aube technologies TH108PLUS Electronic Thermostat User Guide
aube technologies TH104PLUS 5-2 Day Programmable Electric Thermostat Owner’s Manual
aube technologies TH104PLUS 5-2 Day Programmable Electric Thermostat Owner’s Manual
aube technologies TH115-AF-GA Programmable Thermostat Owner’s Manual
aube technologies TH115-AF-GA Programmable Thermostat Owner’s Manual
aube technologies CT230-120GA Slave and Master Thermostat Instruction Manual
aube technologies CT230-120GA Slave and Master Thermostat Instruction Manual
aube technologies TH110A-DP-P Thermostat User Manual
aube technologies TH110A-DP-P Thermostat User Manual
aube technologies TH104PLUS Programmable Thermostat Owner’s Manual
aube technologies TH104PLUS Programmable Thermostat Owner’s Manual

aube technologies TH150 Series VAV Thermostat User Guide