The following table shows the different default modes, the different  
output types for Output 1, and their corresponding settings in the  
configuration menu.  
4.2 Application Types  
The following table shows the different thermostat applications and  
their corresponding settings in the configuration menu.  
Menu setting  
1A & 1A2T models  
1F & 1F2T models  
Menu setting  
Description  
Cool / 0-10 V analog  
(max. of 10 min. refresh)  
Cool  
0
Internal  
0
To control the ambient temperature using the internal  
(built-in) sensor  
(24 V tri-state floating)  
sensor  
Heat / 0-10 V analog  
(max. of 10 min. refresh)  
Heat  
1
2
3
To control the ambient temperature using the AC144-03  
temperature sensor (the internal sensor is not used)  
(24 V tri-state floating)  
1
2
Room  
Cool / 2-10 V analog  
(max. of 10 min. refresh)  
To control the temperature at the air return using the  
AC146-410 temperature sensor (the internal sensor is  
not used)  
Air return  
Heat / 2-10 V analog  
(max. of 10 min. refresh)  
To control the temperature at the fresh air supply using  
the AC146-410 temperature sensor (the internal sensor  
is not used)  
4.3.2 Minimum Opening  
3
4
Air supply  
The minimum damper opening can be set between 0 and 50 %.  
To control the ambient temperature using the internal  
sensor. The AC146-410 temperature sensor is used for  
automatic changeover. See section 5.5.1.  
Note: It is not recommended to set the minimum damper opening to  
0 % (fully closed) when a duct heater is connected to Output 2 or 3.  
Automatic  
changeover  
4.3.3 Opening time (1F and 1F2T models only)  
To use the outdoor air for cooling whenever possible.  
The AC146-410 temperature sensor is used to measure  
the outdoor air temperature. The internal temperature  
sensor measures the room temperature which is then  
compared with the setpoint. If the room temperature is  
lower than the setpoint, the air intake damper remains  
closed. If the room temperature is higher than the  
setpoint, the latter is then compared with the outdoor  
temperature. If the fresh air temperature is lower than  
the setpoint by more than 3°C (5.4°F), the damper  
opens to allow cool air in.  
The damper opening time can be set between 80 and 160 seconds.  
4.4 Output 2 (models TH150-1A2T and TH150-1F2T)  
Limited  
cooling  
Output 2 controls heating only, regardless of the thermostat’s mode.  
When the thermostat is in heat mode, Output 2 is activated as soon  
as Output 1 reaches its full capacity. When the thermostat is in cool  
mode, Output 2 is activated when the measured temperature drops  
below the setpoint.  
5
4.3 Output 1  
Output 1 is used to control a damper. It controls heating when the  
thermostat is in heat mode or cooling when the thermostat is in cool  
mode.  
The following table shows the output types for Output 2 and their  
corresponding settings in the configuration menu.  
Menu setting Description  
0
Not used  
Set the following configuration parameters:  
24 VAC pulsed (triac) / 1 sec. cycle  
(e.g., 24 V SSR such as Aube’s RT850 or RT850T)  
1
• Default mode  
24 VAC pulsed (triac) / 10 min. cycle / direct action  
(e.g., N.C. thermal valve)  
• Output type (1A and 1A2T models only)  
• Minimum opening  
• Opening time (1F and 1F2T models only)  
2
3
24 VAC pulsed (triac) / 10 min. cycle / reverse action  
(e.g., N.O. thermal valve)  
4.3.1 Default Mode / Output Type  
24 VAC pulsed (triac) / 15 min. cycle (e.g., mechanical  
relay such as Aube’s RC840 or RC840T)  
4
5
6
The default mode (heat/cool) is used for the following:  
0-10 V pulsed / 1 sec. cycle (e.g., 3-32 V SSR)  
• The default mode is the thermostat’s mode at power-up.  
0-10 V analog / 1 sec. refresh  
(e.g., SCR controlled device such as a re-heater)  
• The default mode is the active mode when the N.O. changeover  
contact is open (see section 5.5.2).  
7
8
0-10 V analog / max. of 10 min. refresh (e.g., valve)  
2-10 V analog / max. of 10 min. refresh (e.g., damper)  
• When configured as a contact (see section 4.5), Output 3 controls  
either heating or cooling depending on whether the default mode  
is set to heat or cool respectively.  
Note: If 0-4 is selected, set the SW6 switch to Triac. If 5-8 is  
selected, set the switch to Analog (see section 4.7)  
TH150  
400-150-000-C  
5/9/06  
4/6  
More user manuals on ManualsBase.com  
GeneralDetails
Nameaube technologies TH150 Series VAV Thermostat User Guide
Makeaube technologies
LanguageEnglish
FiletypePDF (Download)
File size0.65 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
aube technologies TH108PLUS Electronic Thermostat User Guide
aube technologies TH108PLUS Electronic Thermostat User Guide
aube technologies TH104PLUS 5-2 Day Programmable Electric Thermostat Owner’s Manual
aube technologies TH104PLUS 5-2 Day Programmable Electric Thermostat Owner’s Manual
aube technologies TH115-AF-GA Programmable Thermostat Owner’s Manual
aube technologies TH115-AF-GA Programmable Thermostat Owner’s Manual
aube technologies CT230-120GA Slave and Master Thermostat Instruction Manual
aube technologies CT230-120GA Slave and Master Thermostat Instruction Manual
aube technologies TH110A-DP-P Thermostat User Manual
aube technologies TH110A-DP-P Thermostat User Manual
aube technologies TH104PLUS Programmable Thermostat Owner’s Manual
aube technologies TH104PLUS Programmable Thermostat Owner’s Manual

aube technologies TH150 Series VAV Thermostat User Guide