The following table shows the different default modes, the different
output types for Output 1, and their corresponding settings in the
configuration menu.
4.2 Application Types
The following table shows the different thermostat applications and
their corresponding settings in the configuration menu.
Menu setting
1A & 1A2T models
1F & 1F2T models
Menu setting
Description
Cool / 0-10 V analog
(max. of 10 min. refresh)
Cool
0
Internal
0
To control the ambient temperature using the internal
(built-in) sensor
(24 V tri-state floating)
sensor
Heat / 0-10 V analog
(max. of 10 min. refresh)
Heat
1
2
3
To control the ambient temperature using the AC144-03
temperature sensor (the internal sensor is not used)
(24 V tri-state floating)
1
2
Room
Cool / 2-10 V analog
(max. of 10 min. refresh)
To control the temperature at the air return using the
AC146-410 temperature sensor (the internal sensor is
not used)
Air return
Heat / 2-10 V analog
(max. of 10 min. refresh)
To control the temperature at the fresh air supply using
the AC146-410 temperature sensor (the internal sensor
is not used)
4.3.2 Minimum Opening
3
4
Air supply
The minimum damper opening can be set between 0 and 50 %.
To control the ambient temperature using the internal
sensor. The AC146-410 temperature sensor is used for
automatic changeover. See section 5.5.1.
Note: It is not recommended to set the minimum damper opening to
0 % (fully closed) when a duct heater is connected to Output 2 or 3.
Automatic
changeover
4.3.3 Opening time (1F and 1F2T models only)
To use the outdoor air for cooling whenever possible.
The AC146-410 temperature sensor is used to measure
the outdoor air temperature. The internal temperature
sensor measures the room temperature which is then
compared with the setpoint. If the room temperature is
lower than the setpoint, the air intake damper remains
closed. If the room temperature is higher than the
setpoint, the latter is then compared with the outdoor
temperature. If the fresh air temperature is lower than
the setpoint by more than 3°C (5.4°F), the damper
opens to allow cool air in.
The damper opening time can be set between 80 and 160 seconds.
4.4 Output 2 (models TH150-1A2T and TH150-1F2T)
Limited
cooling
Output 2 controls heating only, regardless of the thermostat’s mode.
When the thermostat is in heat mode, Output 2 is activated as soon
as Output 1 reaches its full capacity. When the thermostat is in cool
mode, Output 2 is activated when the measured temperature drops
below the setpoint.
5
4.3 Output 1
Output 1 is used to control a damper. It controls heating when the
thermostat is in heat mode or cooling when the thermostat is in cool
mode.
The following table shows the output types for Output 2 and their
corresponding settings in the configuration menu.
Menu setting Description
0
Not used
Set the following configuration parameters:
24 VAC pulsed (triac) / 1 sec. cycle
(e.g., 24 V SSR such as Aube’s RT850 or RT850T)
1
• Default mode
24 VAC pulsed (triac) / 10 min. cycle / direct action
(e.g., N.C. thermal valve)
• Output type (1A and 1A2T models only)
• Minimum opening
• Opening time (1F and 1F2T models only)
2
3
24 VAC pulsed (triac) / 10 min. cycle / reverse action
(e.g., N.O. thermal valve)
4.3.1 Default Mode / Output Type
24 VAC pulsed (triac) / 15 min. cycle (e.g., mechanical
relay such as Aube’s RC840 or RC840T)
4
5
6
The default mode (heat/cool) is used for the following:
0-10 V pulsed / 1 sec. cycle (e.g., 3-32 V SSR)
• The default mode is the thermostat’s mode at power-up.
0-10 V analog / 1 sec. refresh
(e.g., SCR controlled device such as a re-heater)
• The default mode is the active mode when the N.O. changeover
contact is open (see section 5.5.2).
7
8
0-10 V analog / max. of 10 min. refresh (e.g., valve)
2-10 V analog / max. of 10 min. refresh (e.g., damper)
• When configured as a contact (see section 4.5), Output 3 controls
either heating or cooling depending on whether the default mode
is set to heat or cool respectively.
Note: If 0-4 is selected, set the SW6 switch to Triac. If 5-8 is
selected, set the switch to Analog (see section 4.7)
TH150
400-150-000-C
5/9/06
4/6
More user manuals on ManualsBase.com
| General | Details |
|---|---|
| Name | aube technologies TH150 Series VAV Thermostat User Guide |
| Make | aube technologies |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.65 MB |

aube technologies TH108PLUS Electronic Thermostat User Guide

aube technologies TH104PLUS 5-2 Day Programmable Electric Thermostat Owner’s Manual

aube technologies TH115-AF-GA Programmable Thermostat Owner’s Manual
aube technologies CT230-120GA Slave and Master Thermostat Instruction Manual

aube technologies TH110A-DP-P Thermostat User Manual

aube technologies TH104PLUS Programmable Thermostat Owner’s Manual