Home > SAVANT > SAVANT CLI-W220X-00 Multistat Smart Thermostat User Guide

SAVANT CLI-W220X-00 Multistat Smart Thermostat User Guide

Climate Modules  
Savant offers a family of Climate Modules. These climate modules expand the capabilities of the thermostat. The  
modules available are as follows:  
CLI-1WIRE2 - Adds up to four 1-wire smart sensors to the system.  
CLI-10K4IN - Adds up to four 10KΩ type temperature sensors to the system.  
CLI-AUX3 - Adds up to three additional auxiliary relays to the system.  
CLI-REL1AUX1 - Adds a set of climate relays (W1, W2, Y1, Y2, G, O) and one auxiliary relay to the system.  
CLI-PTAC1K1 - Adds relays W1, W2, Y1, Y2, G, O for use with a PTAC and one 10KΩ temperature sensor to the  
system.  
Connect Power To Climate Modules  
Savant climate modules require 24V AC for power. The 24V AC used to power the thermostat can also power the  
climate modules. The diagram below displays the power connections between the thermostat and a climate module.  
Climate Module  
Status  
+5V  
1Wire  
Gnd  
1
Climate Module  
+5V  
1Wire  
Gnd  
S/N: SHR155674596  
UID: 001AAE09CA770095  
2
Power can be  
daisy-chained  
to other modules  
24V AC  
from HVAC  
~
~
24VAC  
Connect RS-485 To Climate Modules  
Savant climate modules communicate with the thermostat over RS-485. The diagram below shows the required  
connections.  
HELPFUL!  
RS-485 wiring must be connected  
using a daisy-chained fashion. Do  
not install the RS-485 wires in a  
home run type topology.  
Climate Module  
Left Side View  
A 120Ω terminating resistor  
installed between TX+ and TX- on  
the last climate module in the chain  
may be required on longer wire  
runs. Adding a terminating resistor  
will prevent stability issues that can  
occur with longer wire runs.  
(TX+)  
(TX-)  
GND  
RS-485 Cable  
Daisy-chain the RS-485 cable  
to the next climate module.  
HELPFUL  
For more information on each module, see the following guides on the Savant Customer Community.  
(009-1829-xx) - Sensor Module with Two 1-Wire Sensor Interfaces [CLI-WIRE2] - QRG  
(009-1798-xx) - Sensor Module with Four 10K Thermistor Inputs [CLI-10K4IN] - QRG  
(009-1799-xx) - Relay Module with Three Aux Relays [CLI-AUX3] - QRG  
(009-1806-xx) - Relay Module for PTAC with one 6-port Climate Relay and One 10K Thermistor [CLI-PTAC1K1] -  
QRG  
(009-1805-xx) - Relay Module with one 6-port Climate Relay and One Aux Relay [CLI-REL1AUX1] - QRG  
(009-1959-xx) - Multistat Smart Thermostat Deployment and User Guide  
Multistat Smart Thermostat Quick Start Guide | 009-2428-01  
Copyright ©2025 Savant Systems, Inc 240318  
6
of  
8
45 Perseverance Way, Hyannis MA 02601  
Savant.com | 508.683.2500  
|
GeneralDetails
NameSAVANT CLI-W220X-00 Multistat Smart Thermostat User Guide
MakeSAVANT
LanguageEnglish
FiletypePDF (Download)
File size0.32 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

SAVANT CLI-W220X-00 Multistat Smart Thermostat User Guide