Home > Pelican > PELICAN TC4 Commercial Connected Thermostat Installation Guide

PELICAN TC4 Commercial Connected Thermostat Installation Guide

Notes  
1
Connect to 24 VAC class 2 circuits only.  
2
3
4
Latching relays are rated for 24 VAC @ 2 amps continuous load.  
Latching relays are rated for 24 VAC @ 1 amp continuous load.  
All wire to be installed by customer in accordance with local electrical  
codes.  
4a  
5
Use 18 gauge unshielded thermostat wire.  
Only found for actuators that are 24 VAC floating type.  
Troubleshooting  
If the Pelican thermostat does not power on, check the following:  
1. Check that all wires are properly inserted into the terminal blocks at the thermostat  
and at the HVAC equipment. Lightly pull on the wires to make sure they are not loose.  
2. Use a multi-meter to ensure that 24 VAC power is being supplied by HVAC  
equipment. If 24 VAC is not found, check that the master power has been turned back  
on for the HVAC equipment or verify that the HVAC electrical breaker has not tripped. If  
the breaker has tripped contact a Licensed Professional to assist, otherwise damage can  
occur to the equipment or you can get hurt.  
3. Use a multi-meter to ensure that 24 VAC power is found at the thermostat. If 24 VAC  
was not found, but is found at the HVAC equipment, check for loose or spliced wires.  
4. If you used the Wiring Module, use a multi-meter to ensure that 24 VAC power is  
found at the Wiring Module and the thermostat. Check that the (R), (C), and (D) wires are  
properly connected between the Wiring Module and the thermostat.  
If the thermostat still does not power on, contact Pelican technical support for further  
assistance at 888.512.0490.  
If the Pelican thermostat does not show up on the Pelican App, check the  
following:  
1. Check the thermostat upper right hand corner.  
18  
GeneralDetails
NamePELICAN TC4 Commercial Connected Thermostat Installation Guide
MakePelican
LanguageEnglish
FiletypePDF (Download)
File size0.35 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
PELICAN TC1 Commercial Connected Thermostat Installation Guide
PELICAN TC1 Commercial Connected Thermostat Installation Guide
PELICAN TC3 Commercial Connected Thermostat Installation Guide
PELICAN TC3 Commercial Connected Thermostat Installation Guide

PELICAN TC4 Commercial Connected Thermostat Installation Guide