MODINE 5-580.4 Programmable Room Thermostat Installation Guide
5-580.4
5H0762650000
March, 2024
INSTALLATION INSTRUCTIONS
programmable room thermostat
gas-fired duct furnace/make-up air units
Model Series: “D”,”H”,”I”, & “O”
Figure 1.1 – Room Programmable Thermostat
WARNING
1. Disconnect power supply before making wiring
connections or working on this equipment. Folllow all
applicable safety procedures to prevent accidental
power up. Failure to do so can result in injury or death
from electrical shock or moving parts and may cause
equipment damage.
2. All appliances must be wired strictly in accordance
with wiring diagram furnished with the appliance. Any
wiring different from the wiring diagram could result in
a hazard to persons and property.
3. All wiring must be done with a wiring material having
a remperature rating of at least 105°C.
IMPORTANT
1. The use of this manual is specifically intended for a
qualified installation and service agency. A qualified
installation and service agency must perform all
installation and service of these appliances.
2. Modine manuals may contain excerpts from
component supplier literature adapted for Modine
products. Any accompanying component supplier
literature is for general information.
Table 1.1—Specifications
Model Number:
Model Description:
Hardwire Power:
Battery Power:
1F95-1280
Programmable room thermostat
20-30 VAC
2 AA batteries
Application
1.5A per terminal, 2.5A max
between all terminals.
Terminal Load:
Set Point Range:
Dimensions:
Emerson 1F95-1280 is a mercury free thermostat with
damper control and automatic heat/cool changeover option
that allows users to keep temperatures in a comfortable
range. Seven day programming makes heating or cooling a
space more efficient.
45˚F to 99˚F (7˚C to 37˚C)
4-9/16"H x 5-13/16"W x 1-
3/16"D
Output:
4-20mA (max 500Ω)
Features
Humidity Limits:
90% RH Non-Condensing
32˚F to 105˚F (0˚C to 41˚C)
Fast 1.2˚F ; Slow 1.7˚F
Fast 0.6˚F ; Slow 1.5˚F
Room Programmable thermostat includes:
Temperature Limits:
Rated Differentials Cool:
Rated Differentials Heat:
Automatic or manual fan operation.
Automatic or manual heat/cool switching capabilities.
Celsius or Fahrenheit Temperature display.
Copy Feature for fast programming.
Temperature override (for temporary or continuous
override).
Contents
Thermostat (body and base)
2 “AA” Alkaline batteries
2 mounting screws
Automatic daylight savings setting.
Total or partial (limited temperature range) keypad
lockout with combination.
2 plastic screw anchors
Built-in Short Cycle equipment protection setting.
Occupied/Unoccupied damper control.
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
| General | Details |
|---|---|
| Name | MODINE 5-580.4 Programmable Room Thermostat Installation Guide |
| Make | Modine |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.14 MB |

MODINE DFG Mild Temperature Thermostat Installation Guide

MODINE 5-580.4 Programmable Room Thermostat Installation Guide Overview
Summary of Contents
- Page 1: Installation instructions for programmable room thermostat for gas-fired duct furnace/make-up air units. Disconnect power supply before making wiring connections or working on this equipment to prevent injury or death. All appliances must be wired strictly in accordance with the wiring diagram furnished with the appliance. Wiring must be done with a material having a temperature rating of at least 105°C. The use of this manual is specifically intended for a qualified installation and service agency. Emerson 1F95-1280 is a mercury-free thermostat with damper control and automatic heat/cool changeover option. Seven-day programming makes heating or cooling a space more efficient. Temperature set point range is 45˚F to 99˚F (7˚C to 37˚C). Features include automatic or manual fan operation and temperature override. Contents include thermostat body and base, batteries, mounting screws, and plastic screw anchors.
- Page 2: Installation Pull the thermostat body off of the thermostat base. Caution: Forcing or prying on the thermostat will cause damage to the unit. Place base over hole in wall and mark mounting hole locations in the wall using the base as a template. Connect wires to terminal block on base using appropriate wiring schematic. Push excess wire into wall and plug hole with a fire resistant material to prevent drafts from affecting thermostat operation. Configuration menu settings can be accessed from the main screen by selecting “Menu” and holding down “Installer Config.” Confirm the following settings are selected: SCREEN #1 – SET TO “MS2,” SCREEN #2 – SET TO “ELE,” SCREEN #37 – SET TO “OFF.” Wiring installation must conform with local building codes or the National Electric Code ANSI/NFPA 70 - Latest Edition. Battery location includes (2) “AA” alkaline batteries included in the thermostat at the factory. Power stealing switches should be left in the On position to run the thermostat off of the 24 volt transformer with a battery backup.