T874H,Q,W MULTISTAGE THERMOSTATS AND Q674B,C,G,L SUBBASES  
4600  
4400  
4200  
SETTING  
4000  
3800  
3600  
3400  
3200  
3000  
2800  
2600  
2400  
2200  
2000  
1800  
1600  
1400  
1200  
1000  
800  
C815A THERMISTOR RESISTANCE  
R = 400 ohms 10% AT 77°F (25°C)  
Setting the Heat Anticipator (T874Q Only)  
Set each heat anticipator to match its primary control  
current draw. If the primary control nameplate has no  
rating or if further adjustment is necessary, use the  
following procedure to determine the current draw of each  
stage. (Measure the current draw of each heating stage  
with the thermostat removed and the power on.)  
³
Connect an ac ammeter of appropriate range  
between the heating terminals of the subbase as  
follows:  
Stage 1: between W1 and RH or R.  
Stage 2: between W2 and R.  
600  
400  
200  
0
·
»
Move the system switch to AUTO (if applicable).  
After one minute, read the ammeter and record the  
reading.  
-20  
0
20  
40  
60  
80  
100  
120  
140  
TEMPERATURE OF THERMISTOR (°F)  
M1590A  
¿
After mounting the thermostat, set the adjustable  
heat anticipator(s) to match the respective  
reading(s) measured in step ».  
Fig. 10 Thermistor resistance chart.  
The proper thermistor operation must be verified to assure  
the correct operation of the thermostat. Check the  
thermistor operation as follows:  
Temperature Setting  
Move the heating and cooling levers to the desired  
positions. The minimum differential between the heating  
and cooling setpoints is 3°F (1.7°C), which means the  
setting levers cannot be set closer together than 3°F  
(1.7°C) (5° F [2.8°C] for T874W).  
³
·
Disconnect the T wire on the subbase.  
Use an ohmmeter to measure resistance between  
the T wire and the transformer common.  
Take the outdoor temperature at thermistor location  
and find the correct thermistor resistance on the  
chart in Fig. 10.  
»
¿
Subbase Setting  
System switching positions control thermostat operation as  
follows:  
OFF: Both the heating and cooling systems are off. If  
the fan switch is in the AUTO position, the cooling  
fan is also off.  
If the resistance measured in step · and the  
calculated resistance in step » vary by more than  
15 percent, the thermistor requires replacement.  
Contact the installing dealer for the packaged  
replacement outdoor thermistor.  
AUTO: Thermostat automatically changes between the  
heat and cool modes, depending on the indoor  
temperature.  
HEAT: Heating system is controlled by the thermostat.  
Cooling system is off.  
EM. HT.: Emergency heat relay is energized. The  
cooling system is off. When the compressor has  
failed and the heat pump is not operating, switch to  
the EM. HT. position.  
CHECKOUT  
Heating  
Move the system switch on the Q674 Subbase to HEAT or  
AUTO. Move the heating lever on the T874 about 10°F  
(6°C) above room temperature. Both stages of heating  
start and the fan runs after a short delay. Move the heating  
lever about 10°F (6°C) below room temperature. The  
heating equipment shuts off, and the fan runs for a short  
time, and then shuts off.  
Fan switching positions control fan operation as follows  
(Q674B,C, or L):  
ON: Fan operates continuously.  
AUTO: Fan operates with cooling equipment as  
controlled by the thermostat or with the heating  
equipment as controlled by the plenum switch.  
Cooling  
Move the system switch on the Q674 Subbase to COOL  
or AUTO. Move the cooling lever on the T874 Thermostat  
about 10°F (6°C) below room temperature. The cooling  
equipment and fan start. Move the cooling lever about  
10°F (6°C) above room temperature. The cooling equip-  
ment and fan stop.  
To switch positions, use thumb and index finger to slide  
the lever to the desired position. The switch lever must  
stop in detent over the desired function indicator mark for  
proper circuit operation.  
Emergency Heat  
C815 Outdoor Reset Thermistor (T874W only)  
The T874W is used with a C815 Thermistor mounted in  
the outdoor section. The thermistor must be used; if not,  
thermostat performance will deviate radically from proper  
operation.  
Move the system switch to EM. HT. The EM. HT. LED  
comes on. Move the heating lever about 10°F (6°C) above  
room temperature. The electric strip heater(s) comes on.  
Move the heating lever about 10°F (6°C) below room  
temperature. The electric strip heater de-energizes. The  
EM. HT. LED remains on until the system switch is moved  
to another postion.  
69-0087—6  
7
firealarmresources.com  
GeneralDetails
NameHoneywell T874H Multistage Thermostat Instruction Manual
MakeHoneywell
LanguageEnglish
FiletypePDF (Download)
File size0.19 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell T6 Pro Programmable Thermostat User Manual
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell D1-528 Direct Thermostat Installation Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell FocusPRO P200 Programmable Thermostat User Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell RCHT8610WF Series Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell T9 Smart Thermostat Installation Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide
Honeywell TL116A Thermostat Installation Guide
Honeywell TL116A Thermostat Installation Guide
T10 Pro Smart Thermostat with Redlink Room Sensor
T10 Pro Smart Thermostat with Redlink Room Sensor
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide
Honeywell Lyric T5 Wi-Fi Thermostat Installation Guide
Honeywell Lyric T5 Wi-Fi Thermostat Installation Guide

Honeywell T874H Multistage Thermostat Instruction Manual