Honeywell T7350 Programmable Thermostat Owner’s Manual
NOTES: The ranges mentioned can be limited
based upon setpoints and stops:
1. The greater of the Minimum Heat
Stop and the Not Occupied Heat set-
points determines the lowest setting
to which the occupied heat setpoint
can be adjusted: Stop/NotOcc ≤
Clearing Program Start Times
1. Press Occupied or Not Occupied until the
start period to be cleared is displayed.
2. Press Day until desired day is displayed.
3. Press Clear Start Time.
4. Repeat steps 1 through 3 for all the start
times to be cleared.
5. Press Run Schedule.
OccHeat ≤ (OccCool - 2).
2.
The lesser of Maximum Cool Stop
and Not Occupied Cool setpoints
determines the highest setting to
which the occupied cool setpoint
can be adjusted: Stop/NotOcc ≥
OccCool ≥ (OccHeat + 2).
Temperature Setpoints
Setpoint Limits
The setpoint temperature range is 40°F to 90°F
(4°C to 32°C) for heating and 45°F to 99°F
(7°C to 37°C) for cooling.
3.
4.
The Maximum Occupied Heat Set-
point is limited by Occupied Cool
Setpoint – 2.
The Minimum Occupied Cool Set-
point is limited by the Occupied
Heat Setpoint + 2.
9
63-2638
| General | Details |
|---|---|
| Name | Honeywell T7350 Programmable Thermostat Owner’s Manual |
| Make | Honeywell |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.25 MB |

Honeywell T6 Pro Programmable Thermostat User Manual

Honeywell D1-528 Direct Thermostat Installation Guide

Honeywell FocusPRO P200 Programmable Thermostat User Guide

Honeywell RCHT8610WF Series Smart Thermostat Installation Guide

Honeywell T9 Smart Thermostat Installation Guide

Honeywell TH2320WF4011 FocusPRO Smart S200 Series Thermostat User Guide

Honeywell TL116A Thermostat Installation Guide

T10 Pro Smart Thermostat with Redlink Room Sensor

Honeywell TH6320WF2003 Lyric T6 Pro Wi-Fi Programmable Thermostat User Guide

Honeywell RTH9580 Wi-Fi Color Touchscreen Programmable Thermostat User Guide