Go to Menu > Settings > Installer (tap and hold) > AC/HP.  
Thermostat  
Furnace  
AC/HP  
Air Handler  
Defaults  
Warning! These settings are to be used  
by a qualified HVAC contractor ONLY  
BACK  
AC/HP Settings  
Outside Unit Selection – Chooses outdoor unit type:  
Outside Unit Selection  
EcoNet (locked)  
Var-Speed Clamp  
7000  
None  
No  
Cool Airflow Adjust  
Utility Input Enabled?  
• Non-communicating – Allows you to manually enter settings for your outdoor  
unit. If “non-communicating” outdoor unit is selected, change  
the type (AC or HP), number of stages (1 or 2) and size (Tons) to match the  
Outdoor Unit information.  
Heat Source  
No  
Furnace Lock Out Above  
Disabled  
Heat Pump Locked Out Below Disabled  
BACK  
• EcoNet (locked) – Displays “EcoNet” if a communicating EcoNet Enabled  
outdoor unit is discovered. The selection cannot be changed (locked).  
• None – Lets the system know that there is no outdoor unit present.  
Note: Outside Unit Selection is only applicable for furnace installations.  
Var-Speed RPM Clamp - Allows reduction of the maximum compressor speed.  
Can be used to reduce outdoor unit operating noise or indoor blower airflow. This  
will also reduce the operating capacity.  
Cool/Heat Airflow Adjust – Controls airflow adjustment in cooling and heat  
pump heating, None (default), High (+10%), Low (-10%).  
Utility Input Enabled? – If the system is using a “load shedding” device  
provided by the utility company set to ‘Yes’. The device must be connected to  
terminal U2 & U on the VSODU. Once the dry contacts are connected (non-  
powered) between U2 and U, change the setting to ‘Yes’. When set to ‘Yes’ the  
system will not start the condenser when the connection from U2 to U is open.  
Heat Source – Allows selection of using just the furnace, or heat pump, as the  
sole heat source in a dual-fuel installation. If “Both” is selected, the system will  
stage up and down normally using the heat pump for initial heat stages, and then  
the furnace as auxiliary heat.  
Furnace Locked Out Above – Select the outside temperature above which  
the furnace or supplemental electric heat will not run when matched with a heat  
pump. The default is disabled and the temperature can be adjusted  
between 0-55°F.  
Heat Pump Locked Out Below – Selects the outside temperature below  
which the Heat Pump will not operate and your system will rely exclusively on  
the furnace or auxiliary heat source. This should be determined by evaluating the  
regions Heat Pump Balance point. If a non-communicating outdoor unit is paired  
with a Econet enabled furnace an OAT sensor (RXGY-J02) or the Econet internet  
sensor option must be used to lock out the heat pump when only furnace operation  
is desired.  
Note: A difference of two degrees will be enforced between the furnace and heat pump. Lockout  
temperatures will be based off the outdoor temperature sensor connected to the outdoor unit and NOT off  
the temperature provided under weather. In some instances internet connections may be intermittent and  
an OAT sensor would be the most valid option.  
EcoNet® Smart Thermostat User Guide 30  
> Return to Table of Contents  
GeneralDetails
NameEcoNet UETST800SYS Smart Thermostat User Guide
MakeEcoNet
LanguageEnglish
FiletypePDF (Download)
File size6.47 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
EcoNet RETST800SYS Smart Thermostat User Guide
EcoNet RETST800SYS Smart Thermostat User Guide

EcoNet UETST800SYS Smart Thermostat User Guide