TECH EU-295 Underfloor Heating Room Thermostat User Manual

11. UNDERFLOOR HEATING HYSTERESIS  
Underfloor heating hysteresis defines the tolerance for the maximum  
and minimum temperature. The settings range is 0,2°C to 5 °C.  
If the floor temperature exceeds the maximum temperature, the  
underfloor heating will be disabled. It will be enabled only after the  
temperature has dropped below the maximum floor temperature minus  
hysteresis value.  
Example:  
Maximum floor temperature - 33°C  
Hysteresis - 2°C  
When the floor temperature reaches 33°C, the underfloor heating will be disabled. It will be activated again when the  
temperature drops to 31°C.  
If the floor temperature drops below the minimum temperature, the underfloor heating will be enabled. It will be disabled  
after the floor temperature has reached the minimum value plus hysteresis value.  
Example:  
Minimum floor temperature - 23°C  
Hysteresis - 2°C  
When the floor temperature drops to 23°C, the underfloor heating will be enabled. It will be disabled when the  
temperature reaches 25°C.  
VIII. TECHNICAL DATA  
Specification  
Value  
5oC ÷ 35oC  
Range of room temperature setting  
Baterie 2xAAA 1,5V  
+/- 0,5OC  
Supply voltage  
Accuracy of room temperature measurement  
Potential-free cont. nom. out. Load (EU-295v3)  
230V AC / 0,5A (AC1) *  
24V DC / 0,5A (DC1) **  
5oC ÷ 50oC  
Operating temperature  
Frequency (EU-295v2)  
868MHz  
* AC1 load category: single-phase, resistive or slightly inductive AC load.  
** DC1 load category: direct current, resistive or slightly inductive load.  