Home > HyperStat > HyperStat 7C-HS-C2W-X Wall Mount Thermostat Installation Guide

HyperStat 7C-HS-C2W-X Wall Mount Thermostat Installation Guide

INSTALLATION GUIDE  
HYPERSTAT (7C-HS-C2W-X)  
INTRODUCTION  
HyperStat is a wall-mount thermostat. Its thoughtful design ensures that it blends into most  
commercial spaces while still giving a fresh and contemporary feel compared to dated  
building control interfaces.  
PACKAGE CONTENTS  
Scan this QR  
code to get a  
more detailed  
version of the  
Installation  
Guide  
•
•
HyperStat device  
Mounting accessories  
SPECIFICATIONS  
P
o
w
e
r
Power Source: 24V AC/DC input (+/- 15%)  
Peak consumption: 1.4VA Maximum  
Temperature 32 to 122°F (0°C to 50°C)  
Humidity 20-85% non-condensing.  
Operating range  
Communication  
Sensor bus for daisy chained sensor communication and low power 3V dc.  
4-wire interface for RS 485 communication @ 115200 baud and 5V  
DC, 100mA power source  
900-928 MHz Mesh IEEE 802.15.4-compliant, for communications to CCU  
Bluetooth: BLE 4.1 for commissioning, and communication to wireless sensors  
Temperature range of 32 to 122°F with an accuracy of +/-1°F  
Humidity 0 to 100% with an accuracy of 2%  
Onboard Sensors  
CO2 sensor with a range of 0 - 40,000 ppm, accuracy of +/-30ppm  
VOC sensor; Typical Accuracy: 15% of measured value; TVOC: 0 - 60,000  
ppb;  
Occupancy sensor based on passive infrared (PIR) with a detection range of  
4m with a 15-degree angle  
Light Sensor. Ambient light sensor • <100 LUX resolution • High-accuracy UV  
index sensor • Matches erythermal curve  
Sound sensor with 40-120dB response for 100Hz to 10KHz  
PM2.5, PM10 sensor (optional). Detection range of 0-1000µg/m3 and accuracy  
of +/-10µg/m3 (PM2.5, 0-100µg/m3) or +/-25µg/m3 (PM10, 0-  
100µg/m3). Maximum long-term mass concentration precision limit drift:  
•
•
0 to 100 µg/m3 ±1.25 µg/m3/year  
100 to 1000 µg/m3 ±1.25 % mV/year  
2 x 10K Type-2 thermistor inputs with 2% accuracy  
Inputs  
2 x 0-10V Analog voltage inputs with 2% detection accuracy (2-10V)  
Touch slider for temperature control along with 3 mechanical buttons  
For more information, contact your local Carrier Controls Expert  
©2023 Carrier. All Rights Reserved. Cat. No. 11-808-959-01  
GeneralDetails
NameHyperStat 7C-HS-C2W-X Wall Mount Thermostat Installation Guide
MakeHyperStat
LanguageEnglish
FiletypePDF (Download)
File size0.15 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

HyperStat 7C-HS-C2W-X Wall Mount Thermostat Installation Guide
Get the free PDF manual for the HyperStat 7C-HS-C2W-X Wall Mount Thermostat Installation Guide and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

HyperStat 7C-HS-C2W-X Manual: Questions and Answers

What comes in the box with HyperStat 7C-HS-C2W-X?

Can I use HyperStat 7C-HS-C2W-X outdoors?

No, it is rated for indoor use only. Installation Guide, p. 4

What is the temperature operating range for HyperStat 7C-HS-C2W-X?

32 to 122°F (0°C to 50°C). Installation Guide, p. 1