INSTALLATION GUIDE
HYPERSTAT (7C-HS-C2W-X)
INTRODUCTION
HyperStat is a wall-mount thermostat. Its thoughtful design ensures that it blends into most
commercial spaces while still giving a fresh and contemporary feel compared to dated
building control interfaces.
PACKAGE CONTENTS
Scan this QR
code to get a
more detailed
version of the
Installation
Guide
•
•
HyperStat device
Mounting accessories
SPECIFICATIONS
P
o
w
e
r
Power Source: 24V AC/DC input (+/- 15%)
Peak consumption: 1.4VA Maximum
Temperature 32 to 122°F (0°C to 50°C)
Humidity 20-85% non-condensing.
Operating range
Communication
Sensor bus for daisy chained sensor communication and low power 3V dc.
4-wire interface for RS 485 communication @ 115200 baud and 5V
DC, 100mA power source
900-928 MHz Mesh IEEE 802.15.4-compliant, for communications to CCU
Bluetooth: BLE 4.1 for commissioning, and communication to wireless sensors
Temperature range of 32 to 122°F with an accuracy of +/-1°F
Humidity 0 to 100% with an accuracy of 2%
Onboard Sensors
CO2 sensor with a range of 0 - 40,000 ppm, accuracy of +/-30ppm
VOC sensor; Typical Accuracy: 15% of measured value; TVOC: 0 - 60,000
ppb;
Occupancy sensor based on passive infrared (PIR) with a detection range of
4m with a 15-degree angle
Light Sensor. Ambient light sensor • <100 LUX resolution • High-accuracy UV
index sensor • Matches erythermal curve
Sound sensor with 40-120dB response for 100Hz to 10KHz
PM2.5, PM10 sensor (optional). Detection range of 0-1000µg/m3 and accuracy
of +/-10µg/m3 (PM2.5, 0-100µg/m3) or +/-25µg/m3 (PM10, 0-
100µg/m3). Maximum long-term mass concentration precision limit drift:
•
•
0 to 100 µg/m3 ±1.25 µg/m3/year
100 to 1000 µg/m3 ±1.25 % mV/year
2 x 10K Type-2 thermistor inputs with 2% accuracy
Inputs
2 x 0-10V Analog voltage inputs with 2% detection accuracy (2-10V)
Touch slider for temperature control along with 3 mechanical buttons
For more information, contact your local Carrier Controls Expert
©2023 Carrier. All Rights Reserved. Cat. No. 11-808-959-01
| General | Details |
|---|---|
| Name | HyperStat 7C-HS-C2W-X Wall Mount Thermostat Installation Guide |
| Make | HyperStat |
| Language | English |
| Filetype | PDF (Download) |
| File size | 0.15 MB |

HyperStat 7C-HS-C2W-X Wall Mount Thermostat Installation Guide Overview
Summary of Contents
- Page 1: Installation guide for HyperStat (7C-HS-C2W-X). HyperStat is a wall-mount thermostat designed to blend into commercial spaces with a contemporary feel. Package contents include the HyperStat device and mounting accessories. Power source is 24V AC/DC input with a peak consumption of 1.4VA maximum. Operating temperature range is 32 to 122°F (0°C to 50°C) with humidity levels of 20-85% non-condensing. Communication features include a sensor bus for daisy chained sensor communication and a 4-wire interface for RS 485 communication. Bluetooth BLE 4.1 is available for commissioning and communication with wireless sensors. Onboard sensors include CO2, VOC, occupancy, light, sound, and optional PM2.5 and PM10 sensors. Detection ranges and accuracies for various sensors are specified, including CO2 sensor accuracy of +/-30ppm. Inputs consist of 2 x 0-10V analog voltage inputs with 2% detection accuracy and a touch slider for temperature control.
- Page 2: Outputs include 6 relays rated for 24V DC/1A and 3 analog outputs (0-10V or 4-20mA). The device features a 2.8 240x320 pixel TFT display. Precautions highlight the importance of wiring devices with correct polarity to avoid damage. It is essential to never connect or disconnect wiring with the power on. Powered wires should not touch circuit boards, and installation must comply with all state and local codes. The front should not be assembled to the back plate while powered on. The HyperStat requires seven days to auto-calibrate after installation. Mechanical stress on the CO2 sensor should be avoided for accurate readings. Mounting components include the HyperStat interface, main unit, rubber covers, gang box, Allen head screws, PHP screws, and backplate.
- Page 3: HyperStat Interface - Conventional Place the HyperStat Interface-Conventional and the back plate on the gang box. Fix these two items to the wall gang box with the PHP screws provided. Align the HyperStat main to lock onto the HyperStat Interface-Conventional. Use the Allen head screws to make this entire setup tamper-proof. Rubber covers 1 and 2 must be fixed to cover the programming pins. Connect the antenna to the device and rotate it clockwise to lock it in place. If the HyperStat is mounted on the wall, hold the front plastic and pull it away from the wall. Insert a flat head screwdriver in the notch to separate the front and back plastic.
- Page 4: Carrier ClimaVision technical support Installation and servicing of control systems can be hazardous due to electrical components. Only trained and qualified service personnel should install, repair or service control system components. For more information on wiring, commissioning, or usage of the ClimaVision product line, refer to any documentation provided with the job. If no documentation was provided, use the ClimaVision Help Center for application specific wiring schematics and helpful user guides and videos. Scan the QR code to get a more detailed version of the installation guide. Operating ambient temperature: 0°C to 50 °C. Indoor use only. Powered by Class 2 power source.