Home > terneo > terneo BeeRT Digital Thermostat Instruction Manual

terneo BeeRT Digital Thermostat Instruction Manual

Outlet of heat  
transfer medium  
from boiler  
External  
IN THE BOX  
Thermostat  
It is necessary for the temperature controller to switch  
theꢀcurrent to no more than 2/3 of the maximum current  
specified in the specification. If the current exceeds this  
value, the load must be connected through a contactor  
(magnetic actuator, power relay), which is optimized  
forꢀthis current (Wiring 1).  
programmer  
smart control of heating  
Аir sensor  
1 piece  
2 piece  
Temperature sensor  
with connecting wire  
Feed  
sensor  
BeeRT  
Technical data sheet and  
installation and operation manual  
and warranty card  
L
N
In order to protect from short circuits and excess power  
events appearance in the load circuit, it is necessary  
toꢀinstall an automatic circuit breaker (CB), which should  
be installed in the live wire break, as shown on Wiring 1.  
1 piece  
1 piece  
Technical data sheet and  
1
3
installation and operation manual  
1
2
3
4
5
6
t°  
t°  
А
1
The packing box  
°С  
Boiler  
Terneo BeeRT thermostat is designed to control electric  
heating systems based on electrode or heating element  
boilers with the ability to control the operation of the pump  
and monitor its serviceability. terneo BeeRT also allows  
you to connect an external programmer for maximum  
comfort and energy savings.  
fee  
«fe  
«return» hyste  
pump overrun  
d
r
eturn  
1
3
4
А
1
e
d»  
hysteresis  
r
e
si  
s
The thermostat terminals are designed for a wire  
withꢀsection not more than 2,5 mm2. To reduce  
theꢀmechanical loads on the terminals it is desirable  
toꢀuse aꢀsoft wire. Theꢀwires are tightened in the terminals  
using aꢀscrewdriver with a blade width no more than  
3ꢀmm. Theꢀterminals should be tighten with torque  
0,5ꢀN·m. Use of aluminum is not desirable.  
Theꢀscrewdriver with a blade width more than 3 mm can  
cause mechanical damage to the terminals. This may  
result in the loss of right for warranty.  
t
i
m
e
2
А2  
terneo BeeRT  
А2  
WIRING  
7
8
9
10  
11  
12  
2
4
Return  
sensor  
Thermostat supports two types of sensors: analog sensor  
(R10) or digital sensor (D18).  
Thermostat ensures comfortable and safe operation of  
boiler due to regulation of «feed» and «return»  
temperature. The heating starts when the «return»  
temperature drops to hysteresis value and is turned off  
when the «feed» or «return» temperature reaches the set  
value.  
Connect the analog red «feed» temperature sensor  
toꢀterminals 1 and 2. Digital sensor is connected to  
terminalꢀ1 using red (or yellow) wire and to terminal 2 using  
white wire.  
Inlet of heat  
transfer medium  
to boiler  
Wiring 1. Connecting a single-phase boiler  
using a power relay  
If necessary, it is allowed to shorten and expand sensor  
connecting wires (separate cable not more than 40 m).  
Power wires should not be placed near connection wire  
ofꢀsensor otherwise they may cause interference.  
Connect the analog blue «return» temperature sensor to  
terminals 5 and 6. Digital sensor is connected to terminal 5  
using red (or yellow) wire and to terminal 6 using white  
wire.  
Non-volatile thermostat storage saves all settings  
inꢀtheꢀevent of a power outage.  
Outlet of heat  
IMPORTANT. Before the installation and operation  
of the device, please read by the end of this document.  
This will help to avoid possible danger, mistakes and  
misunderstandings.  
External  
programmer  
transfer medium  
Be sure to select the type of sensor in the functional menu  
of the thermostat when using a digital sensor (see Table 1,  
menu item «Selecting the type of sensor»). If sensors are  
connected incorrectly or one of them fails, when the  
thermostat is turned on, eights are displayed onꢀthe screen  
for 5 seconds, and then «OC» or «SC» (see page 7).  
from boiler  
WARRANTY TERMS  
Аir sensor  
Feed sensor  
The warranty for terneo devices is valid for 36 months  
from the date of sale, provided that the instructions  
areꢀfollowed. The warranty period for products without  
aꢀwarranty certificate is counted from the date  
ofꢀproduction.  
TECHNICAL DATA  
L1 L2 L3 N  
The supply voltage (230 V ±10 %, 50 Hz) is supplied  
toꢀterminals 9 (phase, L) and 10 (zero, N).  
1
3
5
7
Limits of regulation of «feed»  
Limits of regulation of «return»  
15–95 °С, step 1 °С  
5–90 °С, step 0,1 °С  
1–30 °С, step 0,1  
1
2
3
4
5
6
t°  
t°  
А1  
Terminals 7 and 8 (voltage-free relay contacts) are used  
toꢀcontrol the pump.  
°С  
If your device is not working properly, we recommend that  
you first read the section «Possible problems». If you  
cannot find an answer, contact Service Center. In most  
cases, these actions resolve all issues.  
ЕSС 463  
Ith: 50A  
Ui: 440V~  
feed  
return  
«
fe  
e
e
d
»
h
ysteresis  
turn» hyste sis  
ump overrun  
A1  
A2  
1
3
5
7
«
r
r
t
e
im  
230V~  
50 Hz  
p
e
Temperature hysteresis  
Pump overrun time  
Terminals 11 and 12 (voltage-free relay contacts) are used  
to control the boiler heater.  
2
4
6
8
terneo BeeRT  
А2  
7
8
9
10  
11  
12  
2
4
6
8
10–60 sec  
2 х 16 А  
If you continue to have issues with the device, please  
send it to a Service Center or to the store where you  
purchased the device. If your device is defective due  
toꢀour fault, we will repair or replace it under warranty  
within 14 business days.  
Return  
sensor  
The contact group of the temperature programmer  
isꢀconnected to terminals 3 and 4.  
Maximum load current  
(for category AC-1)  
Rated load capacity (for category AC-1)  
Input voltage  
2 х 3 000 VА  
230 V ±10 %  
0,26 kg ±10 %  
52 × 90 × 67 mm  
R10 in heat shrink  
4 m  
INSTALL AND CHECK THE LOAD before installing  
and connecting the thermostat.  
Inlet of heat  
transfer medium  
to boiler  
Please see the full text of the warranty and the data you  
need to send to your Service Center on the website  
aꢀwarranty case, please, contact the General distributor  
inꢀyour area.  
Weight in the complete set  
Overall dimensions (w × h × d)  
Temperature sensor  
POWER OF AUTOMATICS, POWER RELAY,  
magnetic starter should be chosen based on  
maximum power of the boiler.  
Wiring 2. Connecting the automation of a 3-phase boiler  
The length of the sensor  
connected cable  
SERVICE CENTER CONTACT  
+38 (091) 481-91-81  
FOR THE OPERATION OF THE PUMP AND  
THEꢀBOILER, CONNECT APPROPRIATE PHASES  
TO THE CONTROL RELAYS of BeeRT for switching,  
since the relay contacts do not have a galvanic  
connection with the power supply circuits, that is, the  
relays used in the thermostat have a «dry normally  
open contact» (see Wirings 1, 2).  
INSTALLATION  
Viber WhatsApp Telegram  
Number combinations  
under heat, at least  
50 000 cycles  
The thermostat is designed for indoor installation.  
Theꢀingress risk of moisture or liquid into the place of  
installation must be minimized. The ambient temperature  
during installation must be between –5 ... + 45 °C.  
Theꢀinstallation height of the thermostat should  
beꢀinꢀtheꢀrange 0,4...1,7 m above the floor level.  
Number of combinations without  
heating, no less than  
20 000 000 cycles  
WARRANTY CARD  
Сonnection  
no more than 2,5 mm²  
IP20  
serial №:  
date of sale:  
Degree of protection GOST14254  
The thermostat should be mounted in a special cabinet,  
which allows accessible installation and operation.  
Theꢀcabinet must be equipped with a standard 35 mm  
mounting rail (DIN-rail). The temperature controller has  
width of three standard 18 mm modules.  
a seller, a seal:  
place of a seal  
an owner contact  
for a service center:  
1
2
3
GeneralDetails
Nameterneo BeeRT Digital Thermostat Instruction Manual
Maketerneo
LanguageEnglish
FiletypePDF (Download)
File size0.3 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...
terneo rzx Smart Thermostat User Manual
terneo rzx Smart Thermostat User Manual
terneo v3G33 Simple Heat Control Thermostat Instruction Manual
terneo v3G33 Simple Heat Control Thermostat Instruction Manual
terneo bx Smart Thermostat Instruction Manual
terneo bx Smart Thermostat Instruction Manual

terneo BeeRT Digital Thermostat Instruction Manual
Get the free PDF manual for the terneo BeeRT Digital Thermostat Instruction Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

terneo BeeRT Digital Thermostat Instruction Manual Overview

Summary of Contents

  • Page 1: Outlet of heat transfer medium from boiler The terneo BeeRT thermostat is designed to control electric heating systems based on electrode or heating element boilers with the ability to control the operation of the pump and monitor its serviceability. It is necessary for the temperature controller to switch the current to no more than 2/3 of the maximum current specified in the specification. To protect from short circuits and excess power events, it is necessary to install an automatic circuit breaker. The thermostat supports two types of sensors: analog sensor (R10) or digital sensor (D18). The heating starts when the return temperature drops to hysteresis value and is turned off when the feed or return temperature reaches the set value. Non-volatile thermostat storage saves all settings in the event of a power outage. Before the installation and operation of the device, please read by the end of this document. The warranty for terneo devices is valid for 36 months from the date of sale, provided that the instructions are followed. The thermostat is designed for indoor installation, and the ambient temperature during installation must be between –5 ... + 45 °C. The thermostat should be mounted in a special cabinet, which allows accessible installation and operation.
  • Page 2: Exploitation After the end of its service life, the product must be disposed of in accordance with applicable law. Operation principle of terneo BeeRT thermostat with external programmer The feed temperature is the temperature of the coolant at the outlet of the boiler. The programmer controls the heating system based on set schedule. For the operation of the boiler, set the main parameters: the temperature and hysteresis of return and feed. To reset the factory settings, hold the three buttons at the same time for more than 12 sec until dEF message appears on the screen. Safety instructions Connection of the device must be done by a qualified electrician. Do not connect 230 V mains voltage instead of the sensor. Button blocking (child and public protection) Do not immerse the sensor with a connecting wire in the liquid medium.