Home > GENERAL LIFE > GENERAL LIFE FC220 Digital Fan Coil Thermostat User Manual
GENERAL LIFE FC220 Digital Fan Coil Thermostat User Manual
FAN COIL THERMOSTAT PLACEMENT
FAN COIL THERMOSTAT WIRING DIAGRAM
ENGLISH
In order to mount FC220 to the wall, separate the upper case from the
bottom casewiththehelp of ascrewdriverfrom theplaces asshown below.
DIGITAL FAN COIL THERMOSTAT
generallife.com.tr
FC220 USER MANUAL
GENERAL SPECIFICATIONS
DIGITAL FAN COIL THERMOSTAT
FC220 is a digital fan coil thermostat. The user can adjust the Fan Coil
Thermostat with the required temperature and fan speed to get more
comfortable and economic heating/cooling.
UserFriendly Interface
For 2 pipe systems
3 StageFan Speed
Touch Button
Manual heating and cooling option
Large LCD Display& Backlight
FC220
USER MANUAL
FC220and EQUIPMENTS
FC220 Fan Coil Thermostat
Dowels and Screws
TECHNICAL DATA
Dimensions ( H / W / D )
Operating Current
Relay NO Switching Current
90mm / 145mm / 27mm
110-220V AC 50/60 Hz
5A (277VAC – Resistive Load)
3A (30VDC – Resistive Load)
Temperature Measurement Accuracy 0.1oC
Operating Sensivity
0.1oC – 1.0oC
Operating Temperature Range
Operating Temperature
Storage Temperature
(5oC) – (35oC)
(-10oC) – (+50oC)
(-20oC) – (+60oC)
FAN COIL THERMOSTAT
Fan Coil Thermostat needs to be placed in the room which is used most
frequently. For instance; living room or lounge. Placing the Fan Coil
Thermostat in a spot that have air circulation like entrance of a room or side
of window should be avoided. Also anywhere close to heating units (such as
radiator, stove, etc.) and spots where get direct sun lights would not be
suitable. Fan Coil Thermostat needs to be located above the floor 150 cm
height. Fewtrialsmaybe made to find the most convenientspot.
9
1
2
3
4
10
11
C
12
13
14
5
6
7
8
1
2
Fan Speed Adjustment Button
High Fan Speed Symbol
Medium Fan Speed Symbol
Low Fan Speed Symbol
min.20 cm
3
4
5
ON/OFF and Mode Select Button
Cooling Mode Symbol
Off Symbol
6
7
8
Heating Mode Symbol
Temperature Adjustment Button (Increase)
Room Temperature
9
10
11
12
13
14
Temperature Adjustment Button (Decrease)
Set Temperature
Heating Mode Fan Coil is operating
Cooling Mode Fan Coil is operating
generallife.com.tr
1
2
3
| General | Details |
|---|---|
| Name | GENERAL LIFE FC220 Digital Fan Coil Thermostat User Manual |
| Make | GENERAL LIFE |
| Language | English |
| Filetype | PDF (Download) |
| File size | 2.06 MB |

GENERAL LIFE HT330S RF Room Thermostat User Manual

GENERAL LIFE FH103S Underfloor Heating Thermostat User Manual

GENERAL LIFE HT250 RF Digital Room Thermostat User Manual

GENERAL LIFE FH104S Underfloor Heating Thermostat User Manual

GENERAL LIFE ARUNA 302S Digital Room Thermostat User Manual

GENERAL LIFE FH250S Underfloor Heating Thermostat User Manual

GENERAL LIFE HT220S RF Digital Room Thermostat User Manual

GENERAL LIFE 270S RF Room Thermostat User Manual

GENERAL LIFE 270 Wireless Room Thermostat User Manual

GENERAL LIFE HT25 RF Wireless Room Thermostat User Manual

GENERAL LIFE FC220 Digital Fan Coil Thermostat User Manual Overview
Summary of Contents
- Page 1: Fan coil thermostat placement is crucial for optimal performance. The thermostat should be mounted in frequently used rooms, avoiding areas with poor air circulation or near heating units. It is recommended to place the thermostat at a height of 150 cm above the floor. The FC220 is a digital fan coil thermostat that allows users to adjust temperature and fan speed for comfort and efficiency. It features a user-friendly interface, manual heating and cooling options, and a large LCD display with backlight. The technical specifications include dimensions of 90mm x 145mm x 27mm and an operating current of 110-220V AC. Temperature measurement accuracy is 0.1°C, with an operating temperature range of 5°C to 35°C. The thermostat is designed for 2 pipe systems and has a 3-stage fan speed. Materials may be needed to find the most convenient placement for the thermostat. The user manual provides detailed instructions for installation and operation.
- Page 2: Warranty conditions state that the warranty period starts from the invoice date and covers manufacturing defects for 5 years. Devices and equipment are delivered in working condition, and on-site commissioning is subject to a service fee. Repairs covered by the warranty must be carried out at the company factory, with transportation costs borne by the customer for on-site services. Malfunctions during the warranty period are tested to determine if they are due to customer or manufacturer faults. Customers must report any damages to the manufacturer from the start of the warranty duration to maintain their rights. Malfunctions caused by improper use or external factors are not covered by the warranty. The warranty document must be retained by the customer, and a replacement will not be issued if lost. The Fan Coil Thermostat measures ambient temperature every 5 seconds to maintain a set temperature range. Temperature calibration can be adjusted between -8°C and +8°C to synchronize with local thermometers. The product operates in Celsius by default, but the temperature unit can be changed to Fahrenheit in the settings menu.