Home > Smith s > Smith s HAGA95001 Remote Wired Room Thermostat Owner’s Manual

Smith s HAGA95001 Remote Wired Room Thermostat Owner’s Manual

Accessories - Glossary  
Remote (Wired) Room Thermostat  
Caspian EC linking kit (EC only)  
This accessory measures room temperature and switches off the  
heater when the set temperature is reached. This thermostat is hard  
wired and connects directly into either the heaters terminal block or  
power supply.  
The linking kit allows for the creation of master and slave units (up to  
four units), by allowing a 0-10 V signal to be transmitted through its  
cabling. This allows one fan speed controller, or room thermostat to  
control multiple units. It can also be used to control multiple units by  
means of a BMS. Where master and slave units are required this must  
be clearly identified at time of ordering.  
Remote (Wired) Room Thermostat Tamper Proof  
This accessory measures room temperature and switches off the  
heater when the set temperature is reached. This thermostat is hard  
wired and connects directly into either the heaters terminal block  
or power supply. The thermostat has a secure cover that deters  
unwanted adjustment of the room temperature set point.  
External control harness (EC only)  
This accessory is generally used to permit a remote manual speed  
adjustment on an EC variant Caspian. It is possible to provide speed  
control to a master unit and to then utilise the EC linking kit to link to  
any slave units.  
Wall mounted control switch  
Allows the product to be controlled from a switch mounted on  
the wall rather than the product. Linking to the heater is made by  
replacing the existing switch connections with the connections on the  
control switch.  
Proportional Heat Output Controller  
This accessory controls the fan speed and hence the heat output of  
the unit. These controls are available in integral (low level units) and  
in a remote format (high level units). PHOCs are available in two  
standard temperature settings, either 15 - 25oC, or 11 - 21oC.  
When the room temperature is at or below the lowest set point  
(11oC or 15oC) the fan speed will run at its maximum speed to give  
fastest heat up time. As the room temperature increases towards the  
upper set point (21oC or 25oC), the fan speed modulates downwards  
towards a minimum level. Customised temperature ranges can be  
produced upon request  
Flexible hoses  
Flexible connections are a convenient way of connecting a heater into  
your system. They will provide an easy to achieve connection from  
your first-fix pipe work. In addition they will provide for a level of  
expansion and contraction in rigid pipe work and mitigating possible  
sound and vibration transmission.  
Thermostat T1  
Adjustable low temperature cut-out (LTC)  
This is a factory fitted air thermostat suited to EC products installed  
at low level. This control provides a tamperproof room temperature  
control and is ideal for use in public buildings.  
This cut out device allows the user to set the water temperature  
(between 30oC and 90oC) at which the product will start to emit  
heat. It is more accurate than the standard fitted LTC (set at 35oC)  
and enables more flexible use with both low system temperature heat  
pumps and higher system temperature boilers including biomass that  
can produce 80oC flow temperatures.  
Thermostat T2  
A T2 thermostat is used to control the fan speed on low level products  
only. The objective in using this control is to facilitate a faster heat  
up period in a room. An installer or commissioning engineer can  
determine the temperature set point at which the fan speed is  
changed from high to low utilising our speed change circuit board. A  
typical set point would be 16oC, where temperatures below this level  
would trigger a higher fan speed.  
Plinth  
The optional plinth creates an attractive floor standing unit and also  
conceals the pipe work from view. This can also be invaluable where  
it is necessary to prevent contact with heating pipes by vulnerable  
groups. A plinth can also add an additional level of protection from  
the ingress of dust on hard flooring surfaces. Available in 100mm and  
150mm high versions and in black or white.  
Thermostat and Auto-Speed control (T1/T2)  
This accessory serves two purposes. Firstly, it becomes an integral  
room thermostat for the unit providing localised control and secondly,  
the heat output will be changed according to the temperature in the  
room. For example, the fan may work on full power up to 18oC and  
above this temperature move to a lower fan speed. Normally the fan  
speeds used will be medium and low. The components used are as per  
the thermostat T1 and thermostat T2 detailed above.  
As part our commitment to continuous improvement Smiths Environmental Products may change the specifications of its products without prior  
notification or public announcement. All descriptions, illustrations, drawings and specifications in this publication present only general particulars and  
shall not form part of any contract. All dimensions are in mm unless otherwise stated. Please visit our website for the most up to date information.  
Issue 003 | January 2025  
+44 (0) 1245 324 900 | sales@smithsep.co.uk | SmithsEP.co.uk  
GeneralDetails
NameSmith s HAGA95001 Remote Wired Room Thermostat Owner’s Manual
MakeSmith s
LanguageEnglish
FiletypePDF (Download)
File size0.05 MB
Download PDF
1 Star2 Stars3 Stars4 Stars5 Stars (1 votes, average: 5.00 out of 5)
Loading...

Smith s HAGA95001 Remote Wired Room Thermostat Owner’s Manual
Get the free PDF manual for the Smith s HAGA95001 Remote Wired Room Thermostat Owner’s Manual and access setup steps, usage instructions, and troubleshooting tips. 👉 View online or download now to keep your thermostat running smoothly!

Smith s HAGA95001 Remote Wired Room Thermostat Owner’s Manual Overview

Summary of Contents

  • Page 1: Accessories - Glossary Remote (Wired) Room Thermostat measures room temperature and switches off the heater when the set temperature is reached. This thermostat is hard wired and connects directly into either the heater’s terminal block or power supply. Caspian EC linking kit allows for the creation of master and slave units by transmitting a 0-10 V signal through its cabling. Remote (Wired) Room Thermostat Tamper Proof has a secure cover that deters unwanted adjustment of the room temperature set point. External control harness permits a remote manual speed adjustment on an EC variant Caspian. Wall mounted control switch allows the product to be controlled from a switch mounted on the wall. Proportional Heat Output Controller controls the fan speed and heat output of the unit, available in integral and remote formats. Flexible hoses provide an easy connection from first-fix pipe work and mitigate sound and vibration transmission. Adjustable low temperature cut-out (LTC) allows the user to set the water temperature at which the product will start to emit heat. A T2 thermostat controls the fan speed on low level products to facilitate a faster heat up period in a room. The optional plinth creates an attractive floor standing unit and conceals the pipe work from view.
  • Page 2: Accessories - Matrix Caspian products include various models such as SL/FF/UV/TT, EXT, UVC, Skyline, and Skyline E. Caspian adjustable low temperature cut-out options are available. Caspian thermostat (T1) and EC auto-speed control (T2) with circuit board are offered. Caspian proportional heat output controllers are available in different temperature ranges and configurations. Caspian remote switching on/off relay (24V AC coil) is included. Factory fitted controls are standard across products. Bespoke RAL paint finishes can be requested. Antibacterial and antimicrobial paint finishes are available. Specifications may change without prior notification. All dimensions are in mm unless otherwise stated.